background image

12

CSA B149.2 - latest editions and amendments, then the clay 
tile liner can probably be used as a vent for the gas appliances. 
However, the installer must keep in mind the following factors 
which may render the tile liner unsuitable for use as a vent: 

• 

Extremely cold weather 

• 

Long vent connectors 

• 

Masonry chimneys with no air gap between the liner 
and the bricks. (In practice, this can be diffi cult  to 
detect.) 

• 

Exterior chimneys (The tables in  National Fuel Gas 
Code NFPA 54/ANSI Z223.1 - latest edition and in the 
National Standard of Canada, CAN/CSA B149.1 and 
CAN/CSA B149.2 - latest editions and amendments 
assume interior chimneys.) 

If, in the judgment of the local gas utility, installer, and/or local 
codes; one or more of the above factors is likely to present a 
problem, the chimney must be relined (Fix 4).   

F

IX

 1 - L

INER

 T

ERMINATION

Any cap or roof assembly used with a liner must be approved 
by the liner manufacturer for such use. The liner and cap/roof 
assembly must then terminate above the roof in accordance 
with the manufacturer’s instructions. 

In some cases, a shorter extension above the roof may be 
possible with a liner than would be required with a masonry 
chimney. 

For further information on relining, see Fix 4. 

F

IX

 2 -C

HANGE

 V

ENTING

 A

RRANGEMENTS

If the masonry chimney has more than one channel, it may be 
possible to vent the gas appliances into one channel and vent 
the solid or liquid fuel appliance(s) into another channel(s). 
Do not vent an 80+ Furnace inside of a metal liner with other 
appliances vented outside the liner. 

Alternatively, the homeowner may agree to discontinue use 
of the fi replace (solid fuel appliance). If so, the tile liner must 
be cleaned to remove creosote buildup. The fi replace opening 
must then be permanently sealed.

If oil-fi red appliance(s) are being replaced by gas-fi red appli-
ance(s), the tile liner must fi rst be cleaned to remove the fuel 
oil residue. 

If none of the above options is practical, the furnace may need 
to be vented vertically with a B Vent. 

Under some conditions, a 90%+ furnace could be installed 
rather than an 80% furnace. The 90%+ furnace can be vented 
horizontally or vertically through PVC pipe. 

F

IX

 3 - R

EBUILD

 

THE

 C

ROWN

If the chimney crown is damaged, a qualifi ed mason must re-
pair it in accordance with nationally recognized building codes 
or standards. One such standard which may be referenced is 
the Standard for Chimneys, Fireplaces, Vents, and Solid Fuel 
Burning Appliances, ANSI/NFPA 211. 

Next, use a fl ashlight and small mirror to sight up the liner. B 
vent must be supported so as to not come into direct contact 
with the chimney walls or tile liner. If it is not, it can probably 
be rehung so as to be acceptable. A thimble or fi re stop may 
be helpful here. 

Flexible liners should be hung straight or nearly straight. If it 
is spiraled in the chimney and in good condition, it should be 
rehung. To do this, break the top seal; pull up and cut off the 
excess liner length, and refi t the top seal. Use caution when 
doing this, as the cut edges of fl exible liners may be sharp. 

The surfaces of the liner must be physically sound. If gaps 
or holes are present, the metal liner must be removed and 
replaced (Fix 4).  Finally, confi rm that the metal liner is the 
correct size for the appliances to be installed. Use the GAMA 
tables and rules.

If a metal liner is not present, a clay tile liner must be present, 
or the chimney must be lined (Fix 4). 

Use a fl ashlight and small mirror at the cleanout or vent 
connector to inspect the clay tile liner. If any of the following 
problems are present: 

• 

Tile sections misaligned 

• 

Tile sections missing

• 

Gaps between tile sections

• 

Signs of condensate drainage at the cleanout or vent 
connectors

• 

Mortar protruding from between tile sections

• 

Use of sewer pipe or drainage pipe rather than an 
approved fi re clay tile reline the chimney (Fix 4). 

Next, measure the size of the liner. It may be possible to do 
this from the cleanout. The liner must be at least as large as 
the minimum size established by the tables in National Fuel 
Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the 
National Standard of Canada, CAN/CSA B149.1 and CAN/
CSA B149.2 - latest editions and amendments. If the liner is 
too small or too large, then the chimney must be relined (Fix 4). 

C

HECK

 6 - D

ILUTION

 A

IR

If gas-fi red appliances are to be vented into a clay tile liner, a 
source of dilution air is required. 

Dilution air cannot be obtained through: 

• 

Induced draft appliances 

• 

Natural draft appliances with vent dampers

Suffi cient dilution air can ordinarily be obtained through the 
draft hood of a natural draft appliance only if the appliance’s 
vent connector does not include a vent damper.  If dilution 
air will not be available, the chimney must be relined (Fix 4).  

C

HECK

 7 - C

OMPLETE

 

THE

 I

NSTALLATION

If Checks 1 through 6 have been satisfactory, and the liner is 
an acceptable size as determined by the tables in  National 
Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in 
the National Standard of Canada, CAN/CSA B149.1 and CAN/

Содержание CEC80 Series

Страница 1: ...ver if there is a direct conflict between existing practices and the content of this manual the precautions listed herein take precedence TABLE OF CONTENTS Safety Considerations 2 Product Application...

Страница 2: ...an open flame Use a com mercially available soap solution made specifically for the detection of leaks to check all connections as specified in GAS SUPPLY AND PIPING section of this manual Always ins...

Страница 3: ...INSPECTION All units are securely packed in shipping containers tested ac cording to International Safe TransitAssociation specifications The carton must be checked upon arrival for external damage If...

Страница 4: ...on as possible preferably within five days 4 File the claim with the following support documents within a nine month statute of limitations Original or certified copy of the Bill of Lading or indemnit...

Страница 5: ...FPA 54 and the requirements or codes of the local utility or other authority having jurisdiction Additional helpful publications available from the NFPA are NFPA 90A Installation of Air Conditioning a...

Страница 6: ...als deicing salts or chemicals carbon tetrachloride halogen type refrigerants cleaning solutions such as perchloroethylene printing inks paint removers varnishes hydrochloric acid cements and glues an...

Страница 7: ...venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the National Fuel Gas Code ANSI Z223 1 NFPA 54 or the Natural Gas and Propane Installation Code CSA B149...

Страница 8: ...fen tres les ventilateurs les registres de foyer et tous les autres appareils de combustion aliment s au gaz doivent tre remis dans leur tat initial AVERTISSEMENT Corrections must be in accordance wi...

Страница 9: ...ransition bottom kit part 0270F01119 is needed for proper alignment of the inducer outlet and the vent exit hole in the side of the cabinet The inducer may NOT be rotated on CEC80 model furnaces regar...

Страница 10: ...ent draft hood outlet or flue collar EXTERIOR MASONRY CHIMNEYS CATEGORY I FURNACES ONLY An exterior masonry chimney is defined as a Masonry chim ney exposed to the outdoors on one or more sides below...

Страница 11: ...ing metal liners are correctly installed and in good condition Remove the lowest existing vent connector and examine the inside of the elbow or tee at the base of the liner A small amount of soot may...

Страница 12: ...s Vents and Solid Fuel Burning Appliances ANSI NFPA 211 Next use a flashlight and small mirror to sight up the liner B vent must be supported so as to not come into direct contact with the chimney wal...

Страница 13: ...iners offer an insulation sleeve designed to be added to the liner before it is installed in the chimney Poured insulation either vermiculite or other materials is no longer recommended Insulation wil...

Страница 14: ...filter removal or other maintenance IMPORTANT NOTE To avoid possible equipment malfunc tion route the low voltage wires to avoid interference with filter removal or other maintenance HIGH VOLTAGE TO...

Страница 15: ...NSATISFACTORY OPERATION OF EQUIPMENT DAMAGE DUE TO UNDERFIRING OR EQUIPMENT USE THE PROPER SIZE OF NATURAL PROPANE GAS PIPING NEEDED WHEN RUNNING PIPE FROM THE METER TANK TO THE FURNACE WARNING When s...

Страница 16: ...e of the furnace the installer must supply a straight pipe and a 90 degree elbow to reach the exterior of the furnace A ground joint union drip leg and manual shutoff valve must also be supplied by th...

Страница 17: ...ength Feet 3 8 1 2 5 8 3 4 7 8 1 1 8 1 2 3 4 1 1 1 4 1 1 2 10 39 92 199 329 501 935 275 567 1 071 2 205 3 307 20 26 62 131 216 346 630 189 393 732 1 496 2 299 30 21 50 107 181 277 500 152 315 590 1 21...

Страница 18: ...ad between the filter and the furnace blower Too much external static pressure will result in insufficient air that can cause excessive temperature rise This can cause limit switch tripping and heat e...

Страница 19: ...urn CEC80603B 2 10 X 20 or 1 14 X 25 Top Return CEC80805C 2 14 X 20 or 1 16 X 25 Top Return CEC81005C 2 14 X 20 or 1 20 X 25 Top Return use 2 16 X 25 filters and two side returns or 20 X 25 filter on...

Страница 20: ...nal thermostat requirements Strictly follow the wiring guidelines in the fossil fuel kit instal lation instructions All furnace connections must be made to the furnace two stage integrated control mod...

Страница 21: ...ble ignition The maximum must not be exceeded to prevent unit overfiring HIGH ALTITUDE DERATE Whenthisfurnaceisinstalledathighaltitude theappropriateHigh Altitude orifice kit must be applied This is r...

Страница 22: ...ide the cabinetperlocalcodes 1 2 NPT pipe and fittings are required For models with an L shaped manifold a 4 1 2 long nipple is required For models with a hook shaped manifold a 2 proper furnace opera...

Страница 23: ...CTING WARNING DEVICE IN CASE OF A GAS LEAK SINCE PROPANE GAS IS HEAVIER THAN AIR ANY LEAKING GAS CAN SETTLE IN ANY LOW AREAS OR CONFINED SPACES PROPANE GAS ODORANT MAY FADE MAKING THE GAS UNDETECTABLE...

Страница 24: ...ct pressure must be read between the furnace and the cooling coil This reading is usually taken by removing the A shaped block off plate from the end on the coil drilling a test hole in it and reinsta...

Страница 25: ...lights the burner Do not try to light the burner by hand 5 Move the furnace gas valve manual control to the OFF position 6 Wait five minutes then smell for gas Be sure check near the floor as some typ...

Страница 26: ...ithin the range specified in the Inlet Gas Supply Pressure table If supply pressure differs from table make the necessary adjust ments to pressure regulator gas piping size etc and or consult with loc...

Страница 27: ...onverting from natural gas to L P consult your distributor for proper conversion kit Range Nominal Low Stage 1 6 2 2 w c 1 9 w c High Stage 3 2 3 8 w c 3 5 w c Low Stage 5 7 6 3 w c 6 0 w c High Stage...

Страница 28: ...81 952 918 ON ON OFF G 663 647 597 551 501 458 408 355 OFF ON OFF G 785 754 736 690 650 604 565 527 OFF OFF ON G 1348 1294 1261 1250 1229 1233 1205 1182 OFF ON ON G 591 568 518 463 411 355 300 243 ON...

Страница 29: ...465 402 348 271 219 OFF ON OFF G 1160 1102 1055 1017 970 930 891 847 OFF OFF ON G 1411 1356 1313 1272 1235 1198 1162 1127 OFF ON ON G 716 647 592 541 478 420 368 296 ON OFF ON G 716 647 592 541 478 42...

Страница 30: ...8 487 387 301 235 151 OFF ON OFF G 1223 1144 1081 995 918 839 798 738 OFF OFF ON G 1395 1332 1272 1207 1136 1074 1007 948 OFF ON ON G 1025 850 754 670 594 520 443 366 ON OFF ON G 1025 850 754 670 594...

Страница 31: ...16 645 583 516 405 334 282 OFF ON OFF G 1596 1553 1512 1491 1450 1411 1388 1347 OFF OFF ON G 1757 1713 1691 1664 1625 1588 1552 1522 OFF ON ON G 1040 973 936 918 859 805 770 720 ON OFF ON G 1040 973 9...

Страница 32: ...667 576 495 399 338 302 OFF ON OFF G 1782 1744 1715 1700 1660 1619 1579 1510 OFF OFF ON G 2145 2089 2058 2036 2020 2000 1971 1935 OFF ON ON G 1175 1098 1024 947 883 823 764 703 ON OFF ON G 1175 1098 1...

Страница 33: ...933 1897 ON ON OFF G 803 719 631 540 471 337 298 265 OFF ON OFF G 1820 1769 1726 1685 1642 1603 1557 1521 OFF OFF ON G 2235 2185 2139 2108 2076 2032 2000 1964 OFF ON ON G 1626 1574 1524 1479 1433 1410...

Страница 34: ...47 597 551 501 458 408 355 OFF ON OFF G 785 754 736 690 650 604 565 527 OFF OFF ON G 1348 1294 1261 1250 1229 1233 1205 1182 OFF ON ON G 591 568 518 463 411 355 300 243 ON OFF ON G 591 568 518 463 411...

Страница 35: ...759 715 674 631 OFF ON OFF G 1138 1093 1057 1016 981 945 912 876 OFF OFF ON G 1367 1321 1286 1255 1223 1190 1160 1133 OFF ON ON G 553 496 436 372 308 252 198 N A ON OFF ON G 553 496 436 372 308 252 19...

Страница 36: ...617 566 511 458 405 358 311 OFF ON OFF G 1151 1091 1050 1007 964 926 885 850 OFF OFF ON G 1389 1341 1295 1258 1221 1176 1140 1105 OFF ON ON G 1079 1019 975 934 890 850 808 791 ON OFF ON G 1079 1019 9...

Страница 37: ...589 531 456 384 313 252 OFF ON OFF G 1330 1280 1229 1187 1146 1103 1061 1018 OFF OFF ON G 1465 1416 1382 1340 1299 1278 1257 1219 OFF ON ON G 1155 1100 1048 1002 952 907 861 816 ON OFF ON G 1155 1100...

Страница 38: ...486 404 338 280 232 OFF ON OFF G 1160 1107 1060 1011 965 920 868 818 OFF OFF ON G 1231 1185 1136 1093 1049 1004 956 908 OFF ON ON G 1133 1009 956 903 856 804 774 722 ON OFF ON G 1133 1009 956 903 856...

Страница 39: ...68 599 522 432 366 312 258 OFF ON OFF G 1574 1521 1481 1439 1398 1374 1335 1295 OFF OFF ON G 1782 1726 1684 1645 1610 1574 1542 1506 OFF ON ON G 1130 1071 1027 973 922 870 817 787 ON OFF ON G 1130 107...

Страница 40: ...754 652 566 499 428 346 294 OFF ON OFF G 1466 1399 1347 1290 1230 1170 1112 1054 OFF OFF ON G 1904 1832 1777 1727 1678 1630 1579 1523 OFF ON ON G 1352 1281 1218 1152 1076 1026 964 901 ON OFF ON G 135...

Страница 41: ...88 999 899 772 667 561 490 418 OFF ON OFF G 1698 1621 1553 1497 1437 1393 1328 1270 OFF OFF ON G 2266 2202 2143 2090 2040 1995 1945 1896 OFF ON ON G 1450 1382 1314 1243 1181 1115 1047 973 ON OFF ON G...

Страница 42: ...667 576 495 399 338 302 OFF ON OFF G 1583 1536 1515 1478 1434 1383 1317 1265 OFF OFF ON G 2145 2089 2058 2036 2020 2000 1971 1935 OFF ON ON G 1436 1402 1362 1313 1244 1182 1132 1079 ON OFF ON G 1436...

Страница 43: ...545 458 378 324 273 OFF ON OFF G 1265 1204 1146 1091 1034 973 918 870 OFF OFF ON G 1598 1547 1509 1464 1417 1387 1340 1295 OFF ON ON G 1424 1378 1330 1274 1226 1172 1119 1071 ON OFF ON G 1424 1378 133...

Страница 44: ...590 503 422 362 299 OFF ON OFF G 1627 1566 1520 1470 1420 1398 1391 1343 OFF OFF ON G 2226 2165 2126 2083 2048 2011 1983 1945 OFF ON ON G 1381 1324 1274 1220 1164 1137 1109 1049 ON OFF ON G 1381 1324...

Страница 45: ...RS GAS VALVE TWO STAGE OVERCURRENT CONNECTOR 2 CIRCUIT LOW VOLTAGE 24V GND WH CHASSIS GROUND 2 3 IGNITER SURFACE HOT 2 YL PU 2 C BLOWER DRAFT INDUCED BK PM BK BLOWER COMPARTMENT 115 VAC 1 OVERCURRENT...

Страница 46: ...peration Review the Owner s Manual with the homeowner and discuss proper furnace operation and maintenance Leave literature packet near furnace MAINTENANCE TO AVOID ELECTRICAL SHOCK INJURY OR DEATH DI...

Страница 47: ...s doors etc may be ordered by description Parts are available from your distributor Functional Parts List Gas Valve Blower Motor Gas Manifold Blower Wheel Natural Gas Orifice Blower Mounting Bracket P...

Страница 48: ...ght for the product brand you purchased to be direced to the feedback page GOODMAN BRAND AMANA BRAND Product Registration Thank you for your recent purchase Though not required to get the protection o...

Отзывы: