Amana AVZC20 Скачать руководство пользователя страница 20

20

C

OMFORT

N

ET

™ S

YSTEM

O

VERVIEW

A ComfortNet inverter heating and air conditioning system uses
an indoor unit, outdoor unit and thermostat which digitally com-
municate with one another via a two-way communications path.
The thermostat sends commands to the indoor and outdoor
units. The thermostat may request and receive information from
both the indoor and outdoor units. This information may be dis-
played on the CTK04 thermostat. The indoor and outdoor units
also interact with one another. The outdoor unit may send com-
mands to or request information from the indoor unit. This two-
way digital communications between the thermostat and sub-
systems (indoor/outdoor unit) and between subsystems is the
key to unlocking the benefits and features of the ComfortNet
system.

Two-way digital communications is accomplished using only two
wires. The thermostat needs 24 VAC for power. 4 wires between
the indoor unit and thermostat plus two wires between the in-
door unit and outdoor unit are all that are required to operate
the system.

C

OMFORT

N

ET

 S

YSTEM

 A

DVANCED

 F

EATURES

The ComfortNet™ system permits access to additional system
information, advanced set-up features, and advanced diagnos-
tic/troubleshooting features. These advanced features are orga-
nized into a menu structure. See the 

HEAT PUMP ADVANCED

FEATURES MENU

 section for the menu layout.

D

IRECTIONS

 

TO

 H

EAT

 P

UMP

 A

DVANCED

 F

EATURE

 M

ENUS

Press 

MENU, 

scroll down and press 

COMFORTNET USER MENU

.

Enter the date code (password) when prompted. The date code is
printed on the back of the thermostat; or press 

MENU > EQUIP-

MENT STATUS 

and scroll down to find the date code.  After you

enter the password, select COMFORTNET USER MENU, answer YES
to the following menu and select HEAT PUMP to view the system
menus.

D

IAGNOSTICS

The heat pump’s diagnostics menu provides access to the most
recent faults.  The six most recent faults are displayed on the first
screen.  Six additional faults are displayed under fault history.
Faults are stored in order from most recent to least recent.  Any
consecutively repeated fault is stored a maximum of three times.
Example: A leak in the system, low refrigerant charge or an incom-
pletely open stop valve can cause the unit to flash error code E15.
This error code suggests that the unit is experiencing operation at
low pressure. The control will only store this fault the first three

consecutive 

times the fault occurs.

NOTE: 

It is highly recommended that the fault list be cleared after

performing maintenance or servicing the system.

S

TATUS

This menu displays information about the systems current status.
This menu can be utilized to confirm correct functionality of the
equipment and for troubleshooting purposes.  The following items
will be displayed:

TS

Time Stamp

MD

Mode

CRM

Compressor Reduction Mode

RAD

Requested and Actual % Demand

RAF

Requested and Reported ID CFM

ATOF*

Outdoor Air Temperature and Outdoor Fan RPM

DCT

Discharge Temperature and Outdoor Coil Temperature

DLT

Defrost Sensor and Outdoor Liquid Temperature

PSDST**

Pressure Sensor and Outdoor Suction Temperature

*

Only for AVZC200**1AB or later revision.

ATPRM is shown in AVZC200**1AA revision.

**

Only for AVZC200**1AB or later revision.

PSD is shown in AVZC200**1AA revision.

Time Stamp:

 Provides compressor run time in hours.

Mode:

 Current system operational mode (COOLING, HEATING,

COOLING STARTUP, HEATING STARTUP, OIL RETURN, DEFROST,
STOP).

Compressor Reduction Mode:

 The compressor is running at a

speed lower than what is requested, based on the cooling load.

Requested and Actual % Demand: 

Compares the requested cool-

ing demand to what the equipment is providing.  For steady state
operation, these numbers should match.

Requested and Reported ID CFM:

 Compares the requested in-

door airflow to what the indoor equipment has reported.

Outdoor Air Temperature and Outdoor Fan RPM:

 Displays the

outdoor air temperature as well as the outdoor fan speed (

RPM

).

Discharge Temperature and Outdoor Coil Temperature:

 Displays

the discharge temperature and outdoor coil temperature sensor
readings.

Defrost Sensor and Outdoor Liquid Temperature: 

Displays de-

frost sensor and outdoor liquid temperature sensor readings.

Pressure Sensor:

 Displays the pressure sensor reading.

Содержание AVZC20

Страница 1: ...EPAIR THE EQUIPMENT SPECIFIED IN THIS MANUAL WITHOUT PROPER TRAINING MAY RESULT IN PRODUCT DAMAGE PROPERTY DAMAGE PERSONAL INJURY OR DEATH HEAT PUMP UNIT AVZC20 HEAT PUMP INSTALLATION SERVICE REFERENCE Index All information contained herein is subject to change without notice 2015 2016 Goodman Manufacturing Company L P 5151 San Felipe St Suite 500 Houston TX 77056 www amana hac com is a registered...

Страница 2: ...l not allow for proper operation INVERTER A H MODELS CAN ONLY BE MATCHED WITH AN AV PVC AIR HANDLER OR TXV V EXPANSION VALVE KIT DAMAGE RESULTING FROM OPERATION WITH ANY OTHER COMBINATION IS NOT COVERED BY OUR WARRANTIES NOTICE Outdoor inverter units are approved for operation above 0 F in cooling mode and 20 F RH10 in heating mode with no addi tional kit necessary Damage resulting from operation ...

Страница 3: ...LOSION ENSURE THE HYDROSTATIC TEST DATE DOES NOT EXCEED 5YEARS ENSURE THE PRESSURE RATING MEETS OR EXCEEDS 400PSIG WHEN IN DOUBT DO NOT USE CYLINDER WARNING REFRIGERANTS ARE HEAVIER THAN AIR THEY CAN PUSH OUT THE OXYGEN IN YOUR LUNGS OR IN ANY ENCLOSED SPACE TO AVOID POSSIBLE DIFFICULTY IN BREATHING OR DEATH NEVER PURGE REFRIGERANT INTO AN ENCLOSEDROOM OR SPACE BY LAW ALL REFRIGERANTS MUST BERECLA...

Страница 4: ...ontact with the tubing Use an insulated or suspension type hanger Keep both lines separate and always insulate the gas line Insulation is necessary to prevent condensation from forming and dropping from the gas line Armflex or satisfactory equiva lent with 3 8 min wall thickness is recommended In severe conditions hot high humidity areas 1 2 insulation may be re quired Insulation must be installed...

Страница 5: ... If the paint of the steel filter drier has been burned or chipped repaint or treat with a rust preventative The recommended location of the filter drier is before the expansion device at the indoor unit NOTE Be careful not to kink or dent refrigerant lines Kinked or dented lines will cause poor performance or compressor damage Do NOT make final refrigerant line connection until plugs are removed ...

Страница 6: ...ROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO ELECTRIC SHOCK WIRING MUST CONFORM WITH NEC OR CEC AND ALL LOCAL CODES UNDERSIZED WIRES COULD CAUSE POOR EQUIPMENT PERFORMANCE EQUIPMENT DAMAGE OR FIRE WARNING TO AVOID THE RISK OF FIRE OR EQUIPMENT DAMAGE USE COPPER CONDUCTORS WARNING GROUNDING REQUIRED ALWAYS INSPECT AND USE PROPER SERVICE TOOLS LACK OF INSPECTION OR IMPROPER TOOLS MAY CAUSE EQUIPME...

Страница 7: ...red wires are data lines 1 and 2 R 24 VAC hot and C 24 VAC common 1 2 R C 1 2 R C CTK04 Thermostat Compatible Air Handler Furnace Integrated Control Module Compatible AC HP Integrated Control Module 1 2 R C System Wiring STEP 1 CALCULATE REFRIGERANT CHARGE BASED ON LINE SET LENGTH The heat pump unit is shipped with a predetermined factory charge level as shown below For longer line sets greater th...

Страница 8: ...eat the sealing sur faces Do not introduce liquid refrigerant from the cylinder into the crankcase of the compressor as this may damage the compres sor Break vacuum by fully opening liquid and gas base valve ATTENTIONINSTALLER IMPORTANTNOTICE Please read carefully before installing this unit For AVZC20 do not install the 24 Volt Transformer that is included with the CTK04 Thermostat in the Heat Pu...

Страница 9: ...here is an error Refer to the Troubleshooting section Before starting the SYSTEM TEST turn off the electric heater or gas furnace 1 Ensure the thermostat is installed 2 Apply power to outdoor and indoor units 3 Start up After the application information is entered the initial system test must be run FOR INVERTER H P SYSTEM USING COMFORTNET DO NOT INSTALL A TRANSFORMER NOTICE The HOME screen will b...

Страница 10: ...The password is the Date Code located on the thermostat and is available by entering the EQUIPMENT STATUS menu and scrolling to the bottom 6 Select YES to continue 7 From the ComfortNet USER MENU select HEAT PUMP NOTE Screen may show air handler or furnace depending on the type of system installed ...

Страница 11: ...t to run for its duration 5 15 minutes EQUIP TEST SCREEN will show the system test is ON once selected System test will operate the outdoor unit and the indoor unit through a series of startup tests Please proceed to the next step and allow for startup tests to complete Do not interrupt power to outdoor unit indoor unit or thermostat during system test ...

Страница 12: ...s to clear STEP 4 SET THERMOSTAT TO CHARGE MODE Please follow the following sequence to enter CHARGE MODE CHARGE mode allows for charging of the system System op erates for a duration of approximately one hour while the equipment runs at full capacity After one hour the CHARGE MODE ends and the system resumes normal thermostat operation Before starting the CHARGE MODE turn off the electric heater ...

Страница 13: ...staller password The password is the Date Code located on the thermostat and is available by entering the EQUIPMENTSTATUSmenuand scrolling to the bottom 4 Select YES to continue 5 SelectHEATPUMP 6 SelectMAINTENANCE ...

Страница 14: ...rmostat is set for FAN only mode If charging is not complete after 1 hour repeat 7 and 8 Refer to STEP 5 and STEP 6 for refrigerant charge level adjustment 9 To terminate CHARGE MODE select CHARGE mode screen again Press OFF Press DONE to terminate CHARGE MODE 10 Once CHARGE MODE is complete and has been terminated navigate to HOME screen Enter normal operation with temperature offset or thermosta...

Страница 15: ...kwise to increase and counter clockwise to decrease b If subcooling is low and superheat is 7 to 9 F add charge to rise subcooling to 7 to 9 F then check superheat c If subcooling is low and superheat is high add charge to rise subcooling to 7 to 9 F then check superheat d If subcooling is 7 to 9 F and superheat is high adjust the TXV valve to 7 to 9 F superheat then check subcooling e If subcooli...

Страница 16: ... that outdoor equipment operational sound lev els may increase while the equipment is running in BOOST MODE Disabling BOOST MODE will provide the quietest and most efficient operation NOTE BOOST MODE is applicable only for AVZC200 1AB or later revision BOOST MODE performance is most effec tive when paired with an electronic expansion valve enabled indoor unit BOOST MODE is ON by default and is act...

Страница 17: ...password The password is the Date Code located on the thermostat and is available by entering the EQUIPMENT STATUS menu and scrolling to the bottom 4 Select YES to continue 5 Select HEAT PUMP 6 Select SYS SETUP COOL SET UP ...

Страница 18: ... MODE is ON by default 8 BOOST TEMP adjusts the activation temperature from 70 F to 105 F Always ON option is also available to permanently engage BOOST MODE Factory default is 105 F Heat Pump SYS SETUP BOOST MD Heat Pump SYS SETUP BOOST TEMP 105F ...

Страница 19: ...st be enabled through the Installer Options menu Use the fol lowing procedure to enable and disable dehumidification 1 On the CTK04 HOME screen select MENU 2 From the MENU screen scroll down and select Installer Options 3 Enter installer password if known a The password is the thermostat date code and can be obtained by selecting the red Cancel button and selecting the Dealer Information button b ...

Страница 20: ... most recent to least recent Any consecutively repeated fault is stored a maximum of three times Example A leak in the system low refrigerant charge or an incom pletely open stop valve can cause the unit to flash error code E15 This error code suggests that the unit is experiencing operation at low pressure The control will only store this fault the first three consecutive times the fault occurs N...

Страница 21: ... up to the full demand airflow Profile C also has a one 1 minute 100 OFF delay 100 CFM OFF OFF Profile D default ramps up to 50 of the demand for 1 2 minute then ramps to 82 of the full cooling demand airflow and operates there for approximately 7 1 2 minutes The motor then steps up to the full demand airflow Profile D has a 1 2 minute at 50 airflow OFF delay OFF OFF Airflow Tables COOL RUN VALUES...

Страница 22: ...frost temperature sensor and outdoor liquid temperature sensor reading Current system operation mode COOLING COOLING STARTUP HEATING HEATING STARTUP DEFROST OIL RETURN STOP Displays ON or OFF status ON indicates that the reduction mode is operating and the compressor is running at a lower speed than the cooling load would normally require Displays a 0 100 value based on a ratio of the requested co...

Страница 23: ...ngage BOOST MODE SUBMENU ITEM INDICATION USER MODIFIABLE OPTIONS COMMENTS System Verification Test SYSTEM TEST ON or OFF System Verification Test must be run after installation This is approximately a 5 15 minute test If the thermostat is set to COOL mode the system will enter CHARGE mode upon completion otherwise it will stop Force Defrost Cycle FORCE DF CYCLE ON or OFF This will make the unit ru...

Страница 24: ...he range selected in the COOL RPS RANGE menu Select the appropriate compressor RPS for the installed system configuration SUBMENU ITEM USER MODIFIABLE OPTIONS COMMENTS HT Reset YES or NO Selecting to default factory setting Heat Airflow Trim Hi 15 to 15 in 3 increments Selects the Heating airflow trim amount Heat Airflow Trim Int 15 to 15 in 3 increments Selects the Heating airflow trim amount Hea...

Страница 25: ...URE TRANSDUCER H LPT HIGH PRESSURE SWITCH HPS DS1 DS2 DIP SWITCH SEG1 SEG3 7 SEGMENT DISPLAY Z1C Z4C FERRITE CORE BS1 BS3 PUSH BUTTON SWITCH RVC REVERSING VALVE COIL M1C COMPRESSOR MOTOR M1F FAN MOTOR NOTE 1 1 OFF ON DS1 1 OFF ON DS2 V W U Z3C COIL CIRCUIT LIQUID LINE DISCHARGE LINE DEFROST COLOR CODE RD RED BR BROWN GR GREEN BK BLACK WH WHITE YL YELLOW BL BLUE GY GRAY PU PURPLE 1 THE POSITION OF ...

Страница 26: ...RD L2A L1A RD BK TRANSFORMER 208 240 V 3 1 2 24V L1C L2C TERMINAL BLOCK FIELD WIRING H LPT GND INVERTER BOARD COMPRESSOR TERMINAL ORIENTATION X32A X108A GR Z1C Z2C Z3C X12A COIL CIRC UIT DEFROST LIQUID LINE DISCHARGE LINE V W U GR BK BK WH BK 1 OFF ON DS2 2 NOTE 1 BS1 BS2 BS3 X52A SHARE DATA X111A FIN THERMISTOR SEE NOTE 3 NOTE 3 NOTE 1 1 OFF ON DS1 2 GY BK THERMISTOR TEMPERAT URE SENSOR MOTOR HIG...

Страница 27: ... DISCHARGE LINE NOTE 1 1 OFF ON DS2 BR BK COLOR CODE RD RED BR BROWN GR GREEN BK BLACK WH WHITE YL YELLOW BL BLUE OR ORANGE GY GRAY CURRENT SENSOR 2 NOTE 1 1 OFF ON DS1 2 1 THE POSITION OF THE SELECTOR SWITCHES DS1 DS2 INDICATE FACTORY SE 2 MOTOR OVERLOAD PROTECTION PROVIDED BY INVERTER SEE TABLE 3 USE COPPER CONDUCTORS ONLY 4 CLASS 2 WIRE NOT ES THERMISTOR TEMPERATURE SENSOR MOTOR HIGH LOW PRESSU...

Страница 28: ...MENT POSITION USING A VOM WHILE PAYING ATTENTION NOT TO TOUCH THE CHARGED AREA 4 IMMEDIATELY AFTER MEASURING THE RESIDUAL VOLTAGE DISCONNECT THE CONNECTORS OF THE OUTDOOR UNIT S FAN MOTOR IF THE FAN BLADE ROTATES BY STRONG WIND BLOWING AGAINST IT THE CAPACITOR WILL BE CHARGED CAUSING THE DANGER OF ELECTRICAL SHOCK WARNING Žæ t à ï ª L é ƒR ƒ ƒf ƒ ƒT Ìi à j Ì i à j ƒR ƒ ƒf ƒ ƒT Žæ t à ï ª L é VC T ...

Страница 29: ...THE STATIC ELECTRICITY FROM YOUR BODY TO PREVENT FAILURE OF THE PC BOARD 3 MEASURE THE RESIDUAL VOLTAGE IN THE SPECIFIED MEASUREMENT POSITION USING A VOM WHILE PAYING ATTENTION NOT TO TOUCH THE CHARGED AREA 4 IMMEDIATELY AFTER MEASURING THE RESIDUAL VOLTAGE DISCONNECT THE CONNECTORS OF THE OUTDOOR UNIT S FAN MOTOR IF THE FAN BLADE ROTATES BY STRONG WIND BLOWING AGAINST IT THE CAPACITOR WILL BE CHA...

Страница 30: ...HE STATIC ELECTRICITY FROM YOUR BODY TO PREVENT FAILURE OF THE PC BOARD 3 MEASURE THE RESIDUAL VOLTAGE IN THE SPECIFIED MEASUREMENT POSITION USING A VOM WHILE PAYING ATTENTION NOT TO TOUCH THE CHARGED AREA 4 IMMEDIATELY AFTER MEASURING THE RESIDUAL VOLTAGE DISCONNECT THE CONNECTORS OF THE OUTDOOR UNIT S FAN MOTOR IF THE FAN BLADE ROTATES BY STRONG WIND BLOWING AGAINST IT THE CAPACITOR WILL BE CHAR...

Страница 31: ...X Gas stop valve does not fully open X X X X X X X X X Line set restriction X X X X X X X X X X Line set length is too long X X X Blocked filter dryer X X X X X X X X X X OD EEV coil failure X X X X X X X X X X X X X X X X OD EEV failure X X X X X X X X X X X X X X X X Check valve failure Leakage X X X X X X X High Pressure switch failure X Pressure sensor failure X X X X X X X X X X X X Discharge...

Страница 32: ... stop valve does not fully open X X X X X X Line set restriction X X X X X X X X X X Line set length is too long X X X X X Blocked filter dryer X X X X X X X X X X OD EEV coil failure X X X X OD EEV failure X X X Check valve failure Blocked X X X X X X X X X High Pressure switch failure X Pressure sensor failure X X X X X X X Discharge temp sensor failure X X X X X X X X X Coil temp sensor failure...

Страница 33: ...frequent low pressure faults Control has determined continued operation is acceptable This indicates they may be a problem with the equipment Stop valve not completely open Restriction in refrigerant lines Low refrigerant charge Refrigerant leak Low pressure sensor inoperable or not properly connected Indoor fan motor not functioning correctly Faulty TXV Faulty control board Check the opening of s...

Страница 34: ...compressor Repair replace if needed 32 E32 HI TEMP CTRL1 This error indicates the equipment is experiencing high temperature faults on the outdoor control board Ambient air conditions too high Cooling bracket screw s missing or not properly fastened 2 4 ton only No or poor thermal grease coating between cooling plumbing and cooling bracket on control board 2 4 ton only Outdoor fan low speed 5 ton ...

Страница 35: ...ded Replace control board if necessary 38 E38 COMP VOLTAGE The control has detected a voltage related issue with the compressor High or low voltage from supply The compressor wire is lost phase Faulty control board Correct low high line voltage condition Contact local utility if needed Check the wire between control board and compressor Replace control board if necessary 39 E39 OD CTRL FAIL5 Indic...

Страница 36: ...r motor Indoor fan motor not properly connected Too much static pressure Check ID fan motor wiring and connectors Repair replace if needed Check ID fan motor Replace if needed B9 Eb9 LOW ID AIRFLOW Estimated airflow from motor is lower than the airflow requirement Failed indoor blower motor Indoor fan motor not properly connected Too much static pressure Check ID fan motor wiring and connectors Re...

Страница 37: ...s and the corresponding potential problem LEARN button Used to reset the network Depress the button for approximately 5 seconds to reset the network LED Status Indication Probable Causes Corrective Actions Off Nominal condition None none 1Flash Communications Failure Unknown packet is received Depress learn bu on 2Flash Out of box reset Control power up Learn bu on depressed None Off No power Comm...

Страница 38: ...tion Each mode has its own corresponding Screen within the display itself which allows the user to navigate and use the features Example The Fault Code is accessed and displayed from Screen 0 of the 7 segment display The Fault History is accessed and display using Screen 1 of the display etc FAULT CODE FAULT HISTORY MONITORING SETTING MODE 1 SETTING MODE 2 MODE Fault Code Display Fault Code Histor...

Страница 39: ... shows the most recent fault To access hold the RECALL button for 5 seconds at screen 0 To access hold the RECALL button for 5 seconds at screen 1 To access hold the RECALL button To access hold the RECALL and TEST buttons simultaneously To return to SCREEN 0 of the display press the LEARN button for 5 seconds at screen 2 for 5 seconds at screen 2 The first digit displays the SCREEN Hold RECALL Pr...

Страница 40: ...SCREEN This mode will allow the user to see the six most recent system faults For a list of the fault codes please see the TROUBLESHOOTING tables in this document 1 SCREEN 0 SCREEN 1 The display will change to SCREEN 1 Displays 2nd most recent Fault code 6th most recent Fault Code Hold RECALL Press RECALL Press RECALL Press RECALL Press RECALL ...

Страница 41: ...setting Press RECALL Press RECALL Item number Display flickers at 1 second intervals Value MONITORING MODE NAVIGATION SCR This screen allows the user to monitor system variables as shown in the tables at the end of this section EEN 2 OFF ON Blink interval 0 4 sec On 0 4 sec Off Hold RECALL Press RECALL Press RECALL Press RECALL ...

Страница 42: ...stem settings as shown in the tables at the end of this section SCREEN 0 Press RECALL Press RECALL to increase the value Press TEST to change setting Press RECALL Press TEST to complete setting and return to setting mode SCREEN 2 Press LEARN SCREEN 3 Press RECALL Press RECALL OFF ON Blink interval 0 4 sec On 0 4 sec Off ...

Страница 43: ...e the number Press RECALL Press TEST to change setting Press RECALL Press TEST to complete setting and return to setting mode Press RECALL Press RECALL Press RECALL SCREEN 0 OFF ON Blink interval 0 4 sec On 0 4 sec Off Press RECALL Press RECALL SCREEN 4 Setting Mode 2 allows the user to change system settings See table in back of this section ...

Страница 44: ...e 0 Stop 1 Cooling Start up 2 Heating Start up 3 Oil Return Operation 4 Heating Operation 5 Defrost Operation 6 Cooling Operation 3 Compressor Reduction Mode 0 OFF 1 ON 4 demand unit Cut off the decimal first place 5 act demand unit Cut off the decimal first place 6 Requested ID CFM unit CFM Multiply by 10 7 Reported ID CFM unit CFM Multiply by 10 8 Outdoor FAN RPM unit RPM Multiply by 10 9 Ta Out...

Страница 45: ...m Low 0 15 1 12 2 9 3 6 4 3 5 0 6 3 7 6 8 9 9 12 10 15 11 Heat ON Delay 0 5sec 1 10sec 2 15sec 12 Heat OFF Delay 0 30sec 1 50sec 2 70sec 3 90sec Setting Setting No Contents Setting Installer Serviceman Notes 1 Maximum Defrost Interval 0 30min 1 60min 2 90min 3 120min 2 Set Maximum Current N A Future Use 3 Vertical Rise 0 Same Level 1 Outdoor Lower 2 Indoor Lower 4 System Verification Test 0 ON 1 O...

Страница 46: ...e airflow If cleaning of the outdoor coil becomes necessary hire a qualified servicer Inexperienced people could easily puncture the tubing in the coil Even a small hole in the tubing could eventually cause a large loss of refriger ant Loss of refrigerant can cause poor operation and or severe equipment damage Do not use a condensing unit cover to protect the outdoor unit during the winter unless ...

Страница 47: ...ll ductwork roof curbs and electrical connections Check gas piping for leaks Verify gas pressure to the unit is within the range specified on the serial plate Check to ensure that all fan blades and wheels are secure Check refrigerant piping for rubbing and leaks Repair if necessary Check unit wiring to ensure it is not in contact with refrigerant piping or sharp metal edges Check all electrical c...

Страница 48: ...e Cooling Supply Air Temperature Blower Amps Condenser Fan Amps ELECTRICAL Total External Static Pressure Air Flow Discharge Circuit Heating Supply Air Temperature PRESSURES Gas Inlet Pressure Gas Manifold Pressure BLOWER EXTERNAL STATIC PRESSURE Return Air Static Pressure Supply Air Static Pressure Supply Voltage Compressor Amps Start Up Fill in the blanks from the Status Screen on the CTK04 Ther...

Отзывы: