SERVICING
34
ADVANCED USER MENU
SUBMENU ITEM
USER MODIFIABLE OPTIONS
COMMENTS
CL Reset
YES or NO
Selecting to default factory setting.
Cool Airflow Trim Hi (C TR H)
-15% to +15% in 3% increments
Selects the cooling airflow trim amount.
Cool Airflow Trim Int (C TR I)
-15% to +15% in 3% increments
Selects the cooling airflow trim amount.
Cool Airflow Trim Low (C TR L)
-15% to +15% in 3% increments
Selects the cooling airflow trim amount.
Cool Airflow Profile
A, B, C, or D
Selects the cooling airflow profile.
Cool ON Delay
5, 10, 20, 30 seconds
Selects the indoor blower ON delay.
Cool OFF Delay
30, 60, 90, 120 seconds
Selects the indoor blower OFF delay.
Dehumidification Select
ON or OFF
Selecting OFF disables dehumidification; selecting
ON enables dehumidification.
SUBMENU ITEM
USER MODIFIABLE OPTIONS
COMMENTS
Maximum Compressor RPS Range for Cooling
(COOL RPS RANGE)
Five different compressor RPS
ranges will be provided.
Select the appropriate range for the installed system
configuration.
Maximum Compressor RPS Selection for Cooling
(COOL RPS SELECT)
Ten compressor RPS values will be
provided within the range selected
in the COOL RPS RANGE menu
Select the appropriate compressor RPS for the
installed system configuration.
SUBMENU ITEM
USER MODIFIABLE OPTIONS
COMMENTS
HT Reset
YES or NO
Selecting to default factory setting.
Heat Airflow Trim Hi (H TR H)
-15% to +15% in 3% increments
Selects the Heating airflow trim amount.
Heat Airflow Trim Int (H TR I)
-15% to +15% in 3% increments
Selects the Heating airflow trim amount.
Heat Airflow Trim Low (H TR L)
-15% to +15% in 3% increments
Selects the Heating airflow trim amount.
Heat ON Delay
5, 10, 15 seconds
Selects the indoor blower ON delay.
Heat OFF Delay
30, 50, 70, 90 seconds
Selects the indoor blower OFF delay.
Maximum Defrost Interval
30 min., 1hr., 1.5hrs. and 2hrs.
Selects time defrost interval
SUBMENU ITEM
USER MODIFIABLE OPTIONS
COMMENTS
Maximum Compressor RPS Range for Heating
(HEAT RPS RANGE)
Five different compressor RPS
ranges will be provided.
Select the appropriate range for the installed system
configuration.
Maximum Compressor RPS Selection for Heating
(HEAT RPS SELECT)
Ten compressor RPS values will be
provided within the range selected
in the HEAT RPS RANGE menu
Select the appropriate compressor RPS for the
installed system configuration.
COOL SETUP
HEAT SETUP
SET HEATING RUN VALUES (HT RUN VALUES)
SET COOLING RUN VALUES (CL RUN VALUES)