SERVICING
33
ADVANCED USER MENU
SUBMENU ITEM
USER MODIFIABLE OPTIONS COMMENTS
Reset System Setup Options to Factory
Defaults (SYS SETUP RESET)
NO or YES
Selecting "YES" resets this menu to factory default
settings.
SET MAX CURRENT
N/A
Future use.
VERTICAL RISE
Same Level, Outdoor Lower, or
Indoor Lower
If the outdoor & indoor units are /- 15 ft. vertical
distance, select SAME LEVEL. If the outdoor unit is more
than 15 ft. below the indoor unit, select OUTDOOR
LOWER. If the outdoor unit is more than 15 ft. above the
indoor unit, select INDOOR L
BOOST MODE (BOOST MD)
ON or OFF
BOOST MD turns BOOST MODE OFF or ON. See BOOST
MODE section of this manual for more details.
BOOST MODE TEMPERATURE
(BOOST TEMP)
Always ON, 70, 75, 80, 85, 90, 95,
100, 105°F
BOOST TEMP adjusts the activation temperatire from 70°F
to 105°F. An "Always ON" option is also available to
permanently engage BOOST MODE.
SUBMENU ITEM
INDICATION/USER
MODIFIABLE OPTIONS
COMMENTS
System Verification Test (SYSTEM TEST) ON or OFF
System Verification Test must be run after installation.
This is approximately a 5-15 minute test. If the thermostat
is set to COOL mode, the system will enter CHARGE mode
upon completion, otherwise it will stop.
Force Defrost Cycle (FORCE DF CYCLE)
ON or OFF
This will make the unit run in defrost mode.
SUBMENU ITEM
USER MODIFIABLE OPTIONS COMMENTS
PUMP DOWN
ON or OFF
Enter PUMP DOWN Mode. This procedure runs the
equipment for approximately 15 minutes and allows
accumulation of refrigerant at the outdoor unit for
purposes of removing & replacing the indoor unit or
outdoor unit.
CHARGE MODE
ON or OFF
Enter Charging Mode. This allows for a steady system
operation for a duration of approximately 1 hour to allow
for refrigerant charging of the system via the suction
charge port. The system will stop after completion.
SYSTEM SETUP (SYS SETUP)
EQUIPMENT TEST (EQUIP TEST)
SYSTEM MAINTENANCE