SERVICING
67
H
EAT
P
UMP
A
DVANCED
F
EATURE
M
ENU
SUBMENU ITEM
USER MODIFIABLE OPTIONS
COMMENTS
Reset System Setup Options to Factory
Defaults
NO or YES
Selecting "YES" resets this menu to factory default settings.
SET MAX CURRENT
N/A
Future use.
VERTICAL RISE
Same Level, Outdoor Lower, or
Indoor Lower
If the outdoor & indoor units are /- 15 ft. vertical distance,
select SAME LEVEL. If the outdoor unit is more than 15 ft. below the
indoor unit, select OUTDOOR LOWER. If the outdoor unit is more than
15 ft. above the indoor unit, select INDOOR LOWER.
BOOST MODE (BOOST MD)
ON or OFF
BOOST MD turns BOOST MODE OFF or ON. BOOST MODE is ON by
default. See BOOST MODE section of this manual for more details.
BOOST MODE TEMPERATURE
(BOOST TEMP)
Always ON, 70, 75, 80, 85,
90, 95, 100, 105F
BOOST TEMP adjusts the activation temperature from 70°F to 105°F.
An "Always ON" option is also available to permanently engage BOOST
MODE.
SUBMENU ITEM
INDICATION/USER
MODIFIABLE OPTIONS
COMMENTS
System Verification Test (SYSTEM TEST)
ON or OFF
System Verification Test must be run after installation. This is
approximately a 5-15 minute test. If the thermostat is set to COOL
mode, the system will enter CHARGE mode upon completion,
otherwise it will stop.
Force Defrost Cycle (FORCE DF CYCLE)
ON or OFF
This will make the unit run in defrost mode.
SUBMENU ITEM
USER MODIFIABLE OPTIONS
COMMENTS
PUMP DOWN
ON or OFF
Enter PUMP DOWN Mode. This procedure runs the equipment for
approximately 15 minutes and allows accumulation of refrigerant at
the outdoor unit for purposes of removing & replacing the indoor unit
or outdoor unit.
CHARGE MODE
ON or OFF
Enter Charging Mode. This allows for a steady system operation for a
duration of approximately 1 hour to allow for refrigerant charging of
the system via the suction charge port. The system will stop after
completion.
NOTE: BOOST MODE is applicable only for AVZC200**1AB or later revision.
SYSTEM SETUP (SYS SETUP)
EQUIPMENT TEST (EQUIP TEST)
SYSTEM MAINTENANCE