SERVICING
61
Air Handler Display (B*)
LED Display
Menu Description
L6F
View 6 most recent fault codes and Clear Fault Codes if desired
(furnace)
Lr n
Restart communications between the indoor and outdoor unit.
Cr
Control Firmware Revision Number
5r
Control Shared Data Revision Number
F5d
Constant Fan Speed as percent of maximum airflow. Default = 30%
EHt
Electric Heater Kit Wattage (kW)
EFd
Electric Heat Off Delay (seconds)
End
Electric Heat On Delay (seconds)
ETF
Electric Heat Airflow Trim (percentage)
EST
Percentage of high stage electric heating airflow to run duirng low
stage electric heat operation
CFS
1 = system will try to satisfy the thermostat quickly.
5 (default) = system will try to satsify the thermostat more slowly.
dHL
Select "HI " to enable dehumidification when the thermostat DH
terminal is energized. Select "Lo" to enable dehumidification when
the thermostat DH terminal is de-energized. (default = HI )
ODS
Select number of stages for the non-communicating outdoor unit.
(1AC for single-stage Air Conditioners, 1HP for single stage Heat
Pumps, 2AC for two stage Air Conditioners or 2HP for two stage heat
pumps)
t on
Indoor Airflow for non-communicating outdoor units. (values based
on 400CFM per ton) (default = 3.0 Ton)
Ct F
Cooling Airflow Trim (default 0%)
CAP
Cooling Airflow Profile setting (default = profile D shown as 4)
Cnd
Cooling Airflow On Delay Time (default = 5 seconds)
CFd
Cooling Airflow Off Delay Time. (default = 60 seconds)
CSt
Percentage of high stage cooling airflow to run during low stage
operation. (default = 70%)
dHS
Electric heat operation during defrost. 1 = low stage 2 (default) =
high stage
Ht F
Heat Pump Indoor Airflow Trim (default = 0%)
HFd
Heat Pump Heating Airflow Off Delay Time (default = 60 seconds)
Hnd
Heat Pump Heating Airflow On Delay Time (default = 5 seconds)
HSt
Percentage of high stage heat pump heating airflow to run during
low stage operation. (defaullt = 70%)
EHA
When heat pump heating and electric heat are running at the same
time, this percentage is used for additional airflow trim
dHE
Enables or disables dehumidification feature in the outdoor unit.
(default = Enabled)
CbP
Balance point temperature. The Compressor will not operate below
temperature. (Default = 0
°
F)
EbP
Backup Heat Balance Points
HdI
Compressor run time between defrost cycles. (default = 30 minutes)
(2 stage units)
CdL
Compressor off delay at the beginning and end of a defrost cycle.
(default = 30 seconds)