BLOWER PERFORMANCE SPECIFICATIONS

13

NOTES:

1.

CFM in chart is without filters(s). Filters do not ship with this furnace, but must be provided by the installer.

2.

All furnaces ship as high speed cooling. Installer must adjust blower cooling speed as needed.

3.

For most jobs, about 400 CFM per ton when cooling is desirable.

4.

INSTALLATION IS TO BE ADJUSTED TO OBTAIN TEMPERATURE RISE WITHIN THE RANGE SPECIFIED ON THE RATING PLATE.

5.

The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate. The shaded area indicates
ranges in excess of maximum external static pressure allowed when heating. The data for 0.6" w.c. to 0.8" w.c. is shown for air conditioning purposes only.

6

The dashed (---) areas indicate a temperature rise not recommended for this model.

7.

The above chart is for U.S. furnaces installed at 0-2000 feet. At higher altitudes, a properly derated unit will have approximately the same temperature rise at a
particular CFM, while the ESP at that CFM will be lower.

Tons AC

at 0.5"

0.6

0.7

0.8

ESP

CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM CFM CFM

HIGH

3.0

1521

22

1466

23

1414

24

1373

24

1298

26

1243 1164 1075

*M(H/S)80453A***

MED 

2.5

1160

29

1160

29

1132

29

1121

30

1082

31

1042

997

925

(MEDIUM)

MED-LO

2.0

961

35

955

35

948

35

932

36

913

37

882

821

803

LOW

1.5

781

43

785

42

781

43

773

43

761

44

745

716

668

HIGH

3.0

1422

36

1352

38

1307

40

1197

43

1157

45

1092 1075

983

*M(H/S)80703A***

MED

2.5

1098

47

1081

48

1051

49

1039

50

1021

51

983

924

868

(MEDIUM)

MED-LO

2.0

919

56

913

57

892

58

847

----

829

----

818

792

728

LOW

1.5

758

----

741

----

741

----

733

----

699

----

677

649

626

HIGH

4.0

2134

----

2100

25

2042

25

1975

26

1883

28

1786 1700 1601

*M(H/S)80704B***

MED 

3.5

1668

31

1663

31

1656

31

1645

32

1616

32

1549 1492 1391

(MEDIUM)

MED-LO

3.0

1419

37

1426

36

1426

36

1432

36

1419

37

1378 1328 1261

LOW

2.5

1134

46

1145

45

1166

44

1171

44

1160

45

1144 1111 1071

HIGH

3.0

1607

41

1572

42

1547

43

1498

45

1448

46

1390 1302 1222

*M(H/S)80903B***

MED 

2.5

1159

58

1156

58

1145

58

1127

59

1108

60

1075 1033

957

(MEDIUM)

MED-LO

2.0

938

----

916

----

916

----

900

----

889

----

865

829

785

LOW

1.5

785

----

766

----

743

----

730

----

709

----

683

666

604

HIGH

4.0

2051

----

1983

----

1895

35

1812

37

1725

39

1627 1530 1439

*M(H/S)80904B***

MED 

3.5

1736

38

1708

39

1652

40

1611

41

1540

43

1475 1394 1307

(MEDIUM)

MED-LO

3.0

1493

45

1668

40

1459

46

1429

47

1389

48

1339 1274 1204

LOW

2.5

1200

56

1185

56

1180

56

1173

57

1158

58

1125 1125 1080

HIGH

5.0

2290

----

2229

----

2155

----

2047

----

1960

----

1837 1712 1584

*M(H/S)80905C***

MED 

4.0

1852

36

1820

37

1777

38

1719

39

1641

41

1567 1469 1382

(MEDIUM)

MED-LO

3.5

1615

41

1592

42

1556

43

1516

44

1470

45

1405 1346 1235

LOW

3.0

1290

52

1285

52

1265

53

1235

54

1214

55

1174 1044

904

HIGH

5.0

2323

37

2225

38

2120

40

2040

42

1974

43

1801 1688 1577

*M(H/S)81155C***

MED 

4.0

1858

46

1847

46

1799

47

1744

49

1674

51

1577 1493 1399

(MEDIUM)

MED-LO

3.5

1596

53

1587

54

1571

54

1552

55

1493

57

1397 1326 1217

LOW

3.0

1291

----

1272

----

1261

----

1257

----

1205

----

1168 1118 1060

HIGH

5.0

2469

42

2389

43

2300

45

2223

47

2131

49

2027 1902 1786

*M(H/S)81405D***

MED 

4.0

1575

66

1558

67

1545

67

1513

69

1500

69

1419 1354 1271

(MEDIUM)

MED-LO

3.5

1402

----

1380

----

1343

----

1319

----

1296

----

1245 1183 1106

LOW

3.0

1200

----

1186

----

1161

----

1127

----

1082

----

1042

995

926

(CFM & Temperature Rise vs. External Static Pressure)

0.1

0.2

0.3

0.4

0.5

Model

Heating Speed

As Shipped

Motor 

Speed

EXTERNAL STATIC PRESSURE (Inches Water Column)

(

)

Содержание AMH8

Страница 1: ...ts related companies and is used under license to Goodman Company L P Houston TX All rights reserved Copyright 2009 2010 Goodman Company L P Refer to Service Manual RS6610004 for installation operatio...

Страница 2: ...repair this unit without such background may result in product damage personal injury or death Goodman will not be responsible for any injury or property damage arising from improper service or servi...

Страница 3: ...and disposal of refrigerants introduced into this unit Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines These regulations may vary by j...

Страница 4: ...f the blower door is not in place Keep the blower access door in place except for inspection and maintenance This furnace is also equipped with a self diagnosing elec tronic control module In the even...

Страница 5: ...air as altitude increases The kit will provide the proper design certified input rate within the specified altitude range 2000 3000 4000 4500 5000 6000 7000 8000 US BURNER ORIFICE 44 55 44 55 45 56 4...

Страница 6: ...Blower Door Interlock Switch Integrated Control Module Transformer Circulator Blower 1 2 3 4 5 6 7 8 9 Upflow Horizontal 1 Tubular Heat Exchanger 2 Pressure Switch 3 Flue Pipe Connection 4 Induced Dr...

Страница 7: ...7 AMH8 MODELS A B AMH80453AX AMH80703AX 14 12 1 2 AMH80704BX AMH80903BX AMH80904BX 17 1 2 16 AMH80905CX AMH81155CX 21 19 1 2 AMH81405DX 24 1 2 23 All dimensions are in inches Alt Gas Inlet High Volta...

Страница 8: ...81405DX 0 60 013070142 PRESSURE SWITCH TRIP POINTS AND USAGE CHART SQUARE NOSE ROUND NOSE PRESSURE SWITCH TRIP POINTS AND USAGE CHART For installaions in Canada the AMH8 furnace is certified only to 4...

Страница 9: ...have an insulated Z bracket for use with one size smaller furnace All proper coil combinations are subject to being ARI rated with a matched outdoor unit Coil Matches Amana brand units using R22 and...

Страница 10: ...ILTER SIZE TYPE 45M 160 in2 permanent 70M 241 in2 permanent 90M 320 in2 permanent 115M 400 in2 permanent 140M 370 in2 permanent 45M 320 in2 disposable 70M 483 in2 disposable 90M 640 in2 disposable 115...

Страница 11: ...nace in Low Stage Low Heat Blower Low Heat Blower Call for Heat Call for Heat Safety Circuit Check Safety Circuit Check MODE DIP SWITCH TwinComfort Note This furnace is designed to be used with a sing...

Страница 12: ...0 140 000 Output Natural Gas BTUH 1 36 000 56 000 56 000 72 000 72 000 72 000 92 000 112 000 Output LP BTUH 32 000 48 000 48 000 64 000 64 000 64 000 80 000 96 000 A F U E 80 0 80 0 80 0 80 0 80 0 80...

Страница 13: ...19 56 913 57 892 58 847 829 818 792 728 LOW 1 5 758 741 741 733 699 677 649 626 HIGH 4 0 2134 2100 25 2042 25 1975 26 1883 28 1786 1700 1601 M H S 80704B MED 3 5 1668 31 1663 31 1656 31 1645 32 1616 3...

Страница 14: ...30 40 50 60 70 80 90 110 120 100 130 140 150 100 90 80 70 60 50 40 30 20 10 OUTPUT BTU HR x 1000 BTU OUTPUT vs TEMPERATURE RISE CHART TEMPERATURE RISE 600 CFM 700 900 1000 1100 1200 1400 1600 1800 20...

Страница 15: ...CIFIED REPLACEMENT PARTS MUST BE USED WHEN SERVICING 1 SET HEAT ANTICIPATOR ON ROOM THERMOSTAT AT 0 7 AMPS BLOWER PRIMARY LIMIT WH GR BK IGNITER SURFACE HOT PU RD 15 PIN PLUG C NO SWITCH PRESSURE BR S...

Страница 16: ...ANTICIPATORONROOMTHERMOSTATAT0 7AMPS BLOWER PRIMARYLIMIT WH GR BK IGNITER SURFACE HOT PU RD 15PINPLUG C NO SWITCH PRESSURE BR SENSOR FLAME BK WH ROLLOUTLIMITS RAPIDFLASHES REVERSED115VACPOLARITY VERIF...

Страница 17: ...CIR NEU K5 GAS VALVE HIGH LIMIT AUX LIMIT PRESSURE SWITCH FLAME SENSOR PROBE IGNITOR FP IGN GND MV MLV PS HLO HLI CIRCULATOR BLOWER XFMR HOT XFMR NEU 24 VAC TH RO1 RO2 R TR C Y G W COMPRESSOR CONTACTO...

Отзывы: