WARNING
To avoid risk of electrical shock, personal injury, or death, disconnect electrical power source to unit and
discharge capacitor through a 10,000 ohm resistor before attempting to service, unless test procedures require
power to be connected. Ensure all ground wires are connected before certifying unit as repaired and/or
operational.
©2003 Maytag Appliances Company
16022379 Rev. 0
11
Troubleshooting Information
Symptom
Possible Causes
Corrective Action
Excessive noise.
Fan motor mounting hardware/
Check mounting bolts/bracket
bracket loose.
for tightness. Tighten if
necessary.
Copper tubing improperly routed.
Inspect copper tubing for
excessive vibration. Secure
tubing.
Compressor internal noise.
Inspect compressor for proper
operation. Replace.
No cooling.
No refrigerant charge in sealed system.
Test sealed system for leak.
Recharge unit.
Restiction in sealed system.
Evacuate sealed system.
Remove restriction, recharge
unit.
Compressor faulty.
Check compressor motor
windings for open / shorts.
Replace compressor.
Rotary control faulty.
Ensure all control connections
are tight and secure. Check
control for proper operation
and installation. Replace if
faulty.
Wattage slowly decreases below
Undercharged, restricted strainer or plugged
Test sealed system for proper
minimum specification.
capillary tube.
charge. Ensure system is free
of leaks/restriction. Repair
Evacuate & recharge
sealed system.