background image

6

Obtain from:

American National Standards Institute

25 West 43rd Street, 4th Floor

New York, NY 10036

Transportation Damage

Check the carton upon arrival for external damage. If 

damage is found, a request for inspection by carrier agent 

should be made in writing immediately.

Carefully inspect the unit for damage including damage 

to the cabinetry. Any bolts or screws which may have 

loosened in transit must be re-tightened. In the event of 

damage, the receiver should:

1.  Make notation on delivery receipt of any visible damage 

to shipment or container.

2.  Notify carrier promptly and request an inspection.

3. 

In case of concealed damage, carrier should be notified 

as soon as possible-preferably within 5 days.

4.  File the claim with the following supporting documents:

a. 

Original Bill of Lading, certified copy, or indemnity 

bond.

b.  Original paid freight bill or indemnity in lieu thereof.

c. 

Original invoice or certified copy thereof, showing 

trade and other discounts or reductions.

d.  Copy of the inspection report issued by carrier 

representative at the time damage is reported to 

the carrier. The carrier is responsible for making 

prompt inspection of damage and for a thorough 

investigation of each claim. The distributor or 

manufacturer will not accept claims from dealers 

for transportation damage.

NOTE: When inspecting the unit for transportation 

damage, remove all packaging materials. Recycle 

or dispose of the packaging material according to 

local codes.

WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow the steps outlined below for each 

appliance connected to the venting system being placed into 

operation could result in carbon monoxide poisoning or 

death.

The following steps shall be followed with each appliance 

connected to the venting system placed in operation, while 

any other appliances connected to the venting system are 

not in operation:

1.  Seal any unused openings in the venting system.

2.  Inspect the venting system for proper size and 

horizontal pitch, as required by the National Fuel 

Gas Code, ANSI Z223.1 or the Natural Gas and Propane 

Installation Code, CSA B149.1-15 and these instructions. 

Determine that there is no blockage or restriction, 

leakage, corrosion and other deficiencies which could 

cause an unsafe condition.

3.  As far as practical, close all building doors and 

windows and all doors between the space in which 

the appliance(s) connected to the venting system are 

located and other spaces of the building.

4.  Close fireplace dampers.

5.  Turn on clothes dryers and any appliance not connected 

to the venting system. Turn on any exhaust fans, such 

as range hoods and bathroom exhausts, so they shall 

operate at maximum speed.

 

Do not operate a summer exhaust fan.

6.  Follow the lighting instructions. Place the appliance 

being inspected in operation. Adjust thermostat so 

appliance shall operate continuously.

7. Test for spillage from draft hood appliances at the 

draft hood relief opening after 5 minutes of main 

burner operation. Use the flame of a match or candle.

8.  If improper venting is observed during any of the 

above tests, the venting system must be corrected in 

accordance with the National Fuel Gas Code ANSI Z223.1/

NFPA 54 and/or National Gas and Propane Installation 

Code CSA B149.1-15.

9.  After it has been determined that each appliance 

connected to the venting system properly vents when 

tested as outlined above, return doors, windows, 

exhaust fans, fireplace dampers and any other gas 

burning appliance to their previous conditions of use.

Содержание A/GPU14 M Series

Страница 1: ...Please contact your distributor or our website for the applicable Specification Sheets referred to in this manual This Forced Air Central Unit Design Complies With Requirements Embodied In The America...

Страница 2: ...djustments 16 EEM Motors 16 Limit Check 17 Unit Shut Down 17 Compression Protection Devices 17 Refrigerant Charge Check 17 Cooling Refrigerant Charging Models with TXV 17 Superheat Adjustment 17 Cooli...

Страница 3: ...seated and attached with the PCB or else the unit might not function as intended ID Plug PCB Terminal J9 Adjusting Gas Manifold Pressure Use the below manifold pressure settings Gas Input BTU HR Manif...

Страница 4: ...uilding Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must b...

Страница 5: ...n est n cessaire pour viter le danger d intoxica on au CO pouvant survenir si un appareil produisant du monoxyde de carbone con nue de fonc onner au sein de la zone confin e Esta ven laci n es necesar...

Страница 6: ...n monoxide poisoning or death The following steps shall be followed with each appliance connected to the venting system placed in operation while any other appliances connected to the venting system a...

Страница 7: ...observed when installing the unit IMPORTANT NOTE Remove wood shipping rails prior to installation of the unit All Installations For proper flame pattern within the heat exchanger and proper condensate...

Страница 8: ...constructed using industry guidelines The duct work must be placed into the roof curb before mounting the package unit Curb insulation cant strips flashing and general roofing material are furnished b...

Страница 9: ...400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490 100 38 79 150 305 460 Pressure 50 PSIG or less and Pressure Drop of 0 3 W C Based on 0 60 Specific Gravity Gas Natural Gas Capac...

Страница 10: ...ermostat Location Mount the thermostat approximately five feet above the floor in an area that has an inside vibration free wall and has good air circulation Movement of air must not be obstructed by...

Страница 11: ...30 35 40 45 50 SUPPLY WIRE LENGTH FEET 200 6 4 4 4 3 3 2 2 150 8 6 6 4 4 4 3 3 100 10 8 8 6 6 6 4 4 50 14 12 10 10 8 8 6 6 Wiring Table CIRCULATING AIR AND FILTERS Airflow Conversion Units can easily...

Страница 12: ...All units may be externally filtered Refer to the unit filter size chart in the appendix for filter size information Filters installed external to the unit should be sized in accordance with their man...

Страница 13: ...tisfied 5 The compressor and outdoor fan will be de energized when the thermostat opens 6 The indoor blower continues to run at low cool speed for approximately 60 seconds after the thermostat is sati...

Страница 14: ...be as specified on the unit rating plate with all other household gas fired appliances operating The line pressure supplied to the gas valve must be within the Inlet Gas Supply Pressure range specifie...

Страница 15: ...ressure tap 5 Turn ON the gas supply 6 Turn ON power and close thermostat R and W contacts to provide a call for heat 7 Using a leak detection solution or soap suds check for leaks at outlet pressure...

Страница 16: ...give the correct air temperature rise through the unit as marked on the rating plate External Static Pressure Check The total external static pressure must be checked on this unit to determine if the...

Страница 17: ...ect electrical power before inspecting or servicing the unit NOTE All compressor protection devices reset automatically energizing the contactor and outdoor fan WARNING Do not bypass safety devices Re...

Страница 18: ...Record the gauge pressure and the temperature of the line 4 Compare the hi pressure reading to the Required Liquid Line Temperature chart Find the hi pressure value on the left column Follow that line...

Страница 19: ...is outside the acceptable range for the null value the control enters a five minute lockout After the lockout timer has expired the control resumes normal operation During inducer operation including...

Страница 20: ...nlet and flue outlet hoods are not blocked by debris which would prevent adequate combustion air and a properly operating vent system Filter Replacement or Cleaning A return air filter is not supplied...

Страница 21: ...ormation on the yearly inspection consult the User Manual It is recommended that a qualified servicer inspect and service the unit at least once each year Turn the unit on at the thermostat Wait a few...

Страница 22: ...LASH RETRIES EXCEEDED RED 1 HOUR FIXED 10 FLASHES HIGH LIMIT SWITCH RECOVERY TIMER EXPIRED RED 1 HOUR OR HARD LOCKOUT RAPID FLASH CLEAR ERROR HISTORY GREEN N A 2 FLASHES PRESSURE SENSOR NULL ERROR RED...

Страница 23: ...U1442 M41 47 51 40 42 1 2 Large A GPU1448 M41 47 51 40 42 1 2 Large A GPU1461 M41 47 51 40 42 1 2 Large Model Unit Dimensions Inches Height Chassis Size W H W H A GPU1424 M41 16 16 16 16 A GPU1430 M41...

Страница 24: ...PRIMARY LIMIT SWITCH RC RUN CAPACITOR TON ON DELAY TIMER RELAY TR TRANSFORMER VM VENT MOTOR WIRE CODE BLACK BLUE BROWN GREEN GRAY ORANGE PINK PURPLE RED TAN WHITE YELLOW BK BL BR GR GY OR PK PU RD TN...

Страница 25: ...2 R2 PU 3 5 4 3 2 1 YL GR LINE VOLTAGE 208 230V 1PH 60Hz R C RD L1 L2 G R W Y C 5 4 3 2 1 GR COM TR BR RD BK RD YL OR BR WH BK OR YL BR 1 2 BK WH VM GR GR GR BL BL HPS LPS PU R C G Y2 Y1 W1 1 TO THERM...

Страница 26: ...instructions D gaugement conforme aux codes d installation locaux aux exigences du fournisseur de gaz et aux instructions d installation du fabricant NOTE Roof overhang should be no more than 36 RECO...

Страница 27: ...38 41 502 159 X 773 237 1011 324 0 8 444 165 828 245 42 444 165 X 690 245 948 329 PU1430060M41 Rise Range 30 60 E S P T1 FAN ONLY SPEED T2 HEATING SPEED T3 HEATING SPEED T4 COOLING SPEED T5 COOLING SP...

Страница 28: ...677 0 7 644 196 966 305 52 899 278 56 1451 550 1629 686 0 8 587 206 901 315 54 832 285 59 1397 556 1578 693 PU1448080M41 Rise Range 30 60 E S P T1 FAN ONLY SPEED T2 HEATING SPEED T3 HEATING SPEED T4 C...

Страница 29: ...ssor motor is hermetically sealed and does not require additional oiling Annual Inspection Qualified Servicer Only Your package unit should be inspected by a qualified installer or service agency at l...

Страница 30: ...iquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Circuit Pressure Suction L...

Страница 31: ...31 PAGE LEFT INTENTIONALLY BLANK...

Страница 32: ...out us contact us You can also scan the QR code on the right for the product brand you purchased to be directed to the feedback page Our continuing commitment to quality products may mean a change in...

Отзывы: