WARNING
To prevent death, personal injury or property damage due to fire or explosion, a qualified servicer must determine
the reason the rollout protection device opened before the device is reset.
R
OLLOUT
P
ROTECTION
D
EVICE
R
ELOCATION
Furnaces installed horizontal right-to-left airflow, require
the rollout protection device be relocated. This device
closes the gas valve if the burner flames are not drawn into
the heat exchanger.
Supply
Air
Return
Air
Vent
Right To Left Installation
To relocate:
1. Disconnect electrical power.
WARNING
To prevent death or personal injury due to electric
shock, disconnect electrical power.
2. Remove the cover from the burner box. Save the
screws that held it in place. (
Note:
There are several
screw holes, but only four screws. This is intentional,
and not a manufacturing defect.)
3. As shipped, the rollout protection device is located
near the flame sensor end of the manifold assembly.
Remove and save the mounting screws.
4. For most installations, it will not be necessary to re-
move the wires from the rollout protection device.
5. For horizontal-left installations, a hole is provided
near the igniter end of the manifold assembly. Insert
the rollout protection device into this hole and attach
with screws removed in Step 3.
Rollout Switch Relocation
6. Secure rollout wires to manifold and insure no wires
can come in contact with burners or other hot sur-
faces.
7. Push the button to confirm the rollout control is in the
closed position.
8. Replace the cover on the burner box, replacing the
screws from Step 2.