7.58
High overrange visual warning limit value
Display:
HIGH dISP
Range:
Any display value or
OFF
Default Value:
OFF
High overrange limit value - the display can be set to show an overrange message if the display
value rises above the
HIGH dISP
setting. For example if
HIGH dISP
is set to
1000
then once
the display reading rises above
1000
the message
-or-
will flash on and off or the display value
will flash on and off instead of the normal display units (see
dISP
function
). This message
can be used to alert operators to the presence of an input which is above the high limit. If this
function is not required it should be set to
OFF
by pressing the
^
and
v
buttons simultaneously
at this function.
Note: this function operates on frequency/rate display only.
7.59
Display visual warning flashing mode
Display:
dISP
Range:
FLSH
or
-or-
Default Value:
FLSH
Display overrange warning flashing mode - this function is used in conjunction with the
Lo dISP
and
HIGH dISP
functions. The
dISP
function can be set to
FLSH
or
-or-
. If the display
warning value set at the
Lo dISP
or
HIGH dISP
function is exceeded and the
dISP
function
is set to
FLSH
then the display value will flash on and off every second as a visual warning. If the
display warning value set at the
Lo dISP
or
HIGH dISP
function is exceeded and the
dISP
function is set to
-or-
then the
-or-
message will flash on and off once a second as a visual
warning. The warning flashes will cease and the normal display value will be seen when the value
displayed is higher than the low limit and lower than the high limit.
Note: this function operates on frequency/rate display only.
7.60
SET terminal input function
Display:
S.INP
Range:
Lo
or
hiGh
Default Value:
hiGh
Sets, in conjunction with the SET terminal input, the count up/down operation of the totaliser.
The totaliser may be made to count up or count down via this function and if required made to
toggle between up and down count mode using an external contact closure between SET and GND
terminals. The
S.INP
function and the SET terminal input connection may be used in one of the
modes shown in the table below.
S.INP
Setting
SET terminal
Operation mode
Lo
Open i.e. no connection to SET terminal
Count down
Lo
Closed i.e. SET terminal shorted to GND terminal
Count up
hiGh
Open i.e. not connection to SET terminal
Count up
hiGh
Closed i.e. SET terminal shorted to GND terminal
Count down
PM4TRMAN-2.7-0