Elec tri cal In stal la tion

The PM4 Panel Meter is designed for continuous operation and no power switch is fitted to the unit.

It is recommended that an external switch and fuse be provided to allow the unit to be removed for servicing.

The plug in, screw type, terminal blocks allow for wires of up to 2.5mm

2

 to be fitted. Connect the

wires to the appropriate terminals as indicated below. Refer to connection details provided in this chapter to
confirm proper selection of voltage, polarity and input type before applying power to the instrument. When
power is applied to the instrument will cycle through a display sequence indicating the software version and
other  status  information,  this  indicates  that  the instrument  is  functioning.  Acknowledgement  of correct
operation may be obtained by applying an appropriate input to the instrument and observing the reading.
The use of screened cable is recommended for signal inputs.

For wiring details for optional outputs refer to the separate “PM4  Panel Meter Optional Output

Addendum” booklet supplied when options are fitted.

Page 6 of 27

PM4RT8MAN-1.4-0

1

2 3

4 5 6

MAINS  EARTH

AC  ACTIVE

AC  NEUTRAL

COM

REMOTE

INPUT

RELAY  1  

RTD1

RTD5

RTD2

RTD6

RTD3

RTD7

RTD4

RTD8

GND

GND

N/O

(DC+)

(DC-)

A B

H

C D E F

J K

7

13

8

14

9

15

10

16

11

17

12

18

In stru ment rear panel - 2 wire connection

1

2 3

4 5

6

MAINS  EARTH

AC  ACTIVE

AC  NEUTRAL

COM

RELAY  1  

RTD1

RTD3

RTD1  3W

RTD3  3W

RTD2

RTD4

RTD2  3W

RTD4  3W

GND

GND

N/O

(DC+)

(DC-)

A

B

H

C D E F

J K

7

13

8

14

9

15

10

16

11

17

12

18

REMOTE

INPUT

In stru ment rear panel - 3 wire connection

Содержание PM4-RT8

Страница 1: ...PM4 RT8 Multi Input RTD Process Monitor Controller Operation and Instruction Manual ...

Страница 2: ...6 RTD connection examples 7 Power supply connections 7 Relay connections 7 Remote input connections 7 Explanation of Functions 8 Easy alarm relay adjustment access facility 9 Error messages 23 Function Table 24 Specifications 26 Technical Specifications 26 Output Options 26 Physical Characteristics 26 Guarantee and Service 27 RT08 25F13 Page 2 of 27 PM4RT8MAN 1 4 0 ...

Страница 3: ...s 1 1 Basic setup The steps below allow a basic setup for temperature display Refer to the Explanation of Functions chapter for a descriptionof the functionsmentioned belowand for a description of other functions which may be required The basic setup requirements to obtain temperature displays for each input are 1 Connect the inputs as shown in Electrical Installation chapter 2 Enter CAL mode as s...

Страница 4: ...ilable as an option for panel mount instruments Prepare a panel cut out of 45mm x 92mm 1 mm 0 mm see diagram below Insert the instrument into the cut out from the front of the panel Then from the rear of the instrument fit the two mounting brackets into the recess provided see diagram below Whilst holding the bracket in place tighten the securing screws being careful not to over tighten as this ma...

Страница 5: ... 2 Remove 4 x self tapping screws from back cover remove back cover by pulling it away from the instrument 3 Using a screwdriver remove the earth screw which passes through the case then slide out the board or boards 4 Configure the PCB links as required see appropriate chapter 5 Slide PCB back into the case 6 Replace the earth screw which passes through the case 7 Refit back cover and fix with th...

Страница 6: ...rmation this indicates that the instrument is functioning Acknowledgement of correct operation may be obtained by applying an appropriate input to the instrument and observing the reading The use of screened cable is recommended for signal inputs For wiring details for optional outputs refer to the separate PM4 Panel Meter Optional Output Addendum booklet supplied when options are fitted Page 6 of...

Страница 7: ...yas standard with connections on terminals 5 and 6 Extra relays are optionally available The relay is a single pole single throw type form A and is rated at 5A 240VAC into a resistive load The relay contact is voltage free and may be programmed for normally open or normally closed operation 4 4 Remote input connections Terminals 7 8 are the remote input terminals The operation selected by the R IN...

Страница 8: ...ssages when the message is seen you can release the button Move to step 2 below 2 When the wake up messages have finished and the display has settled down to its normal reading press then release the button Move to step 3 below 1 When the wake up messages have finished and the display has settled down to its normal reading press then release the button 3 Within 2 seconds of releasing the button pr...

Страница 9: ...ast one alarm must have asetpoint nothing will happen ifallthealarm setpoints are set to OFF 3 The SP AC function must be set to allow access to the relays required e g if set to A1 2 then the easy access will work only with alarm relays 1 and 2 even if more relays are fitted 4 The instrument must be in normal measure mode i e if the instrument is powered up so that it is in CAL mode then the easy...

Страница 10: ...lay at around the setpoint value The hysteresis setting operates as follows In the high alarm mode once the alarm is activated the input must fall below the setpoint value minus the hysteresis value to reset the alarm e g if A1Hi is to 50 0 and A1Hy is set to 3 0 then the setpoint output relay will activate once the display value goes above 50 0 and will reset when the display value goes below 47 ...

Страница 11: ...g on or off When set to OFF the relay will reset automatically when the display shows the input is not in alarm condition If a 5 digit display with alarm annunciators is used the annunciator will light solidly when the input is in alarm condition and will be extinguished when the relay resets If set to on the relay will latch when it is activated by an alarm condition and can only be manually rese...

Страница 12: ...e of the instrument Note The bAr and bAr_ settings are referenced from the 7 segment display readings not the bargraph scale values The bargraph scale may scaled differently to the 7 segment display as shown on the right where bargraph scale is 0 to 100 yet the display is showing 675 3 In this example the bargraph scale may be indicating percentage fill of a tank whilst the 7 segment display is in...

Страница 13: ...dle of the display If the seven segment display value is positive the bargraph will rise If the seven segment display value is negative then the bargraph will fall e g when scaling the display use the bAr_ and bAr functions e g bAr_ 0 and bAr 100 will give a bargraph with all the bottom half segments lit at a 7 segment display reading of 100 and all the top segments lit with a 7 segment display re...

Страница 14: ...w value seen only when the dual analog retransmission option is fitted See REC_ function for description of operation See also REC2 function analog output 2 mode rEC Ch 2 Value Second analog recorder retransmission output high value seen only when the dual analog retransmission option is fitted See REC function for description of operation See also REC2 function analog output 2 mode dCPt 0 or 0 1 ...

Страница 15: ...he letter A will then be displayed alongside the average value dIFF the difference between the highest and lowest temperatures will be displayed When scrolling through the displays using the or v button the message dIFF will be displayed prior to the reading and if ch r or ch L is selected at the dISPunit function the letter d will be displayed alongside the difference reading dIF1 the largest dif...

Страница 16: ... will be a display message to indicate this when the F button has been pressed e g Ch1 CAL End UCAL Ch1 UCAL Ch 2 etc n a Uncalibration of selected channel used to set the selected channel back to the factory calibration values This function should only be used when calibration problems exist and it is necessary to clear the calibration memory To clear the memory press the and v buttons simultaneo...

Страница 17: ...not show the channel number instead shows the letter H if the dISPunit function is set to show a channel number Lo Operates on the lowest of the inputs at the time e g when set to Lo if R INP is set to P HLd peak hold then when the remote input is activated the inputs will be scanned and the lowest of all the inputs will be displayed From then on the display will only change if this low channel va...

Страница 18: ...HLd dIF1 Operates on the difference between channel 1 the remaining channels e g when set to dIF1 if R INP is set to P HLd peak hold then when the remote input is activated the inputs will be scanned and the largest difference between channel 1 and the remaining channels will be displayed from then on the display will show the maximum difference until the remote input is released The letter d will...

Страница 19: ...ch display to give an indication of display type Page 19 of 27 PM4RT8MAN 1 4 0 SPFN ChnI R INP set to HiLo See P HLd for further description Operates as above Hi and Lo but will toggle between high and low readings each time remote input is activated SPFN ChnI R INP set to Lo See P HLd for further description SCAN Shows whichever channel is or has been the lowest HIGH Shows whichever channel is or...

Страница 20: ...hing operation SPFN chnI SCAN HIGH Lo AUGE dIFF dIF1 ch1 ch2 to ch8 Remote or P button function mode of operation This function sets the operation mode for the remote input R INP function or P button P but function operation See R INP function for a description of the operation of the SPFNchnI functions ACCS OFF EASY NONE or ALL Access mode the access mode function ACCS has four possible settings ...

Страница 21: ...el 1 ch1 ch2 etc relay operates from the selected channel e g If ch2 is chosen and the A1Hifunction is set to 100 then relay one will activate if channel 2 input is 100o or higher bAR HIGH Lo AUGE dIFF dIF1 ch1 ch2 ch3 ch4 ch5 ch6 ch7 or ch8 Bargraph operation mode applicable only to bargraph displays The following choices are available for bargraph operation mode HIGH bargraph indicates the highe...

Страница 22: ...thout conversion to ASCII Cont Sends ASCII form of display data every time display is updated POLL Controlled by computer or PLC as host Host sends command via RS232 485 and instrument responds as requested A buS A special communications mode used with Windows compatible optionalPCdownload software Refer to the user manualsupplied with this optional software Addr 0 to 31 Set unit address for polle...

Страница 23: ...d of this value if a 5 digit display is used In these circumstances it may be necessary to remove the display units C or reduce the resolution by setting no decimal point places Display shows NO ACCS or NO SPAC this message indicates that access to FUNC mode has been blocked by either the R INP function or the ACCS function Enter CAL mode and check the setting of these functions and alter if requi...

Страница 24: ... bAr tYPE Bargraph operation mode bAr S dot d dot or C bAr bAr DGOP Digital output mode bcd b SCL bin or bin2 bin2 dG OP Digital retransmission output polarity A Lo or A Hi A Lo bcd Strt BCD retransmission start value Value in memory 0 dIG_ Scaled digital output low reading Value in memory 0 dIG Scaled digital output high reading Value in memory 1000 rEC_ Analog retransmission 1 output low limit V...

Страница 25: ...IGH Lo AUGE dIFF dIF1 ch1 ch2 ch3 ch4 ch5 ch6 ch7 or ch8 HIGH REC Analog retransmission mode output 1 HIGH Lo AUGE dIFF dIF1 ch1 ch2 ch3 ch4 ch5 ch6 ch7 or ch8 HIGH REC2 Analog retransmission mode output 2 HIGH Lo AUGE dIFF dIF1 ch1 ch2 ch3 ch4 ch5 ch6 ch7 or ch8 HIGH bAUd RAtE Baud rate 300 600 1200 2400 4800 9600 19 2 or 38 4 9600 Prty Parity select NONE EUEN or ODD NONE O PUt Serial communicati...

Страница 26: ...e supply type is factory configured Power Consumption AC supply 4 VA max DC supply depends on display type options Typical consumption for PM4 with no options is 100mA 12VDC and 50mA 24VDC Output standard 1 relay Form A Voltage free output rated 5A 240VAC resistive load Relay Action Programmable N O or N C 7 2 Output Options Extra Relays Same specs as Relay 1 up to 3 extra relays Analog Retransmis...

Страница 27: ... manufacturer freight paid and if accepted for free repair will be returned to the customers address in Australia free of charge When returning the product for service or repair a full description of the fault and the mode of operation used when the product failed must be given In any event the manufacturer has no other obligation or liability beyond replacement or repair of this product Modificat...

Отзывы: