M0309_N_Series_ABS_700-3kVA_User_Manual V2.8 2012-06-12
13
5.
Start-up/Shutdown
Once the UPS is installed, make sure it is located on a sturdy, well-ventilated surface, and that
the exhaust fans and ventilation grills are not obstructed. Below is the necessary information for
operation of the unit. Normally the UPS runs automatically, but on those few occasions such as
just after installation start-up or shutdown procedures maybe required.
5.1.
Turn On Procedure:
-
Ensure that installation was correct and successful and that the input power cable
is connected to a well-grounded outlet.
-
The UPS can be started by pushing the “ON/OFF” button, located on the front
panel, for at least three seconds.
-
The UPS should now start its self-test testing the internal functions, main
synchronization and inverter startup. After a successful test inverter power will
be supplied via the outlets.
-
During the self-test, the LCD will display “Ready on”. The LED will light up
when output power has commenced and the LCD will display “Line mode”.
-
Switch on the loads.
5.2.
Turn Off / Shutdown Procedure:
-
Shutdown and turn off the loads.
-
Push the “ON/OFF” button on the front panel for five seconds. The alarm will
sound and the UPS will shutdown.
-
The LCD will display “UPS OFF” for a few seconds.
NOTE: In case of an emergency situation, the Emergency Power Off (EPO) located
on the back of the unit should be used
.