Alvarado SU3500 Скачать руководство пользователя страница 10

Supervisor 3500 Installation Instructions

Page 10 

For assistance: [email protected]  +1 (909) 591-8431 PUD3673R1-1

  

Communication Requirements

Internal Card Reader Installation Requirements (Optional)

User Training

Pre-Installation Checklist

Signal Inputs and Outputs To / From Access Control System 

Inputs

 - Signal inputs from outside systems are wired into the SU3500’s I/O control board. There are two types of input 

signals, momentary dry contacts (MDC) and sustained dry contacts (SDC). All input signals must be normally open, voltage-

free, dry contacts, with the exception of the fire alarm input, which can be configured (via jumper on the I/O control board) to 

accept either a normally open or normally closed sustained contact. MDC’s must be at least 100ms in duration to register. 

While the SU3500 can accept signals up to 2 seconds in duration, the suggested MDC input duration is 1 second or less to 

support rapid throughput in high volume applications. 

Outputs

 – Signal outputs are available from the SU3500’s I/O control board. Outputs are normally open, voltage-free, 

momentary dry contacts. The output signal length is 300ms in duration. 

Inability to Provide Specified Inputs

 - If the access control system does not have dry contact outputs, isolation relays 

should be used. NEVER connect signal lines containing voltage directly to the I/O control board.

Network Communication

A networked PC with Alvarado's TCP/IP control and monitoring software is required. Adhere to IEEE standards for network cabling 

requirements.

It is the installer's responsibility to ensure the following steps are completed before beginning the installation.

Card readers or other physical access devices may be installed in the reveal, under the lid on either or both right-hand sides of 

the lane. Card readers / physical access devices are not supplied by Alvarado. Generally, mullion sized card readers are installed 

inside the cabinet. For larger-sized card readers, contact Alvarado to verify compatibility prior to installation.

The physical dimensions of the card reader cannot exceed: 

1.00" H x 2.75" W x 6.25" D (25mm x 70mm x 159mm).

All personnel that will be involved with operating the SU3500 should be trained in the proper method of operation. Detailed 

operation instructions are outside the scope of this manual, but can be found in the 

SU3500

 

User Guide 

(also included with the 

product). If further training is desired, contact Alvarado for information regarding on-site training services.

1. 

All components and hardware to be installed have been unpacked, correctly identified, and moved to the installation location.

2. 

The turnstile configuration and layout has been confirmed with the site manager.

3.  All applicable requirements in the Pre-Installation Requirements section have been met.

Environmental Requirements

•  DO

 

NOT

 install the product outdoors. This product is intended for indoor use only. 

•  DO NOT

 install the SU3500 where infrared lighting (strobe lights, flash photography, etc.) is in the direct path 

of the 

optical sensors. Interference may affect the performance of the turnstile.

The following are suggested operating temperature and humidity ranges for the SU3500:

Operation

Non-Operation/Storage

Temperature Range

10° - 32°C / 50° - 90°F

0° - 40°C / 32° - 104°F

Humidity Range (Non-Condensing)

15% - 85% RH

--

Operating the SU3500 outside the suggested temperature and humidity ranges may negatively affect 

turnstile performance and could potentially cause damage to turnstile components.

  

CAUTION

Содержание SU3500

Страница 1: ...Inc 12660 Colony Street Chino CA 91710 Phone 1 909 591 8431 Fax 1 909 628 1403 support alvaradomfg com www alvaradomfg com PUD3673R1 1 Supervisor 3500 SU3500 Optical Turnstile with Motorized Barrier W...

Страница 2: ...Turnstile Layout 14 Baseplate Assembly Optional 15 Installation Instructions 16 Anchoring the Turnstile 16 Internal Card Reader Installation 18 Wiring Instructions 19 Primary Power 19 Crossover Cable...

Страница 3: ...Alvarado parts to repair a damaged turnstile Closely follow the handling instructions for moving or lifting the turnstile during installation Power off the turnstile before connecting or disconnectin...

Страница 4: ...er Cabinets are used to create additional lanes for multi lane configurations Each additional lane includes the parts below Single Lane Parts List Center Cabinet Parts List Per Center Cabinet Concrete...

Страница 5: ...atus display that communicates lane status to the user A card reader is normally installed during installation underneath the lid below the user status display Center cabinets contain both master and...

Страница 6: ...enabled Running Ethernet cabling to the SU3500 provides a number of benefits 1 It allows implementation of Alvarado s TCP IP control and monitoring software 2 It allows easy implementation of SU3500...

Страница 7: ...g com 1 909 591 8431 Page 7 For ease of installation and service allow 6 of space between cabinets and walls or other surfaces All dimensions are approximate Space Requirements 22 Lane Plan View Eleva...

Страница 8: ...ease of installation and service allow 6 of space between cabinets and walls or other surfaces All dimensions are approximate Space Requirements 36 Lane Elevation View Plan View Footprint Drawing Fig...

Страница 9: ...uggests the use of surge protection on the high voltage power line to further protect electronics Fig 5 SU3500 Conduit Lines Seal the floor area around the conduits running up and into the cabinets Th...

Страница 10: ...on Card readers or other physical access devices may be installed in the reveal under the lid on either or both right hand sides of the lane Card readers physical access devices are not supplied by Al...

Страница 11: ...ocation they will be installed 2 Unlock each end panel with the key provided To remove slide each unlocked end panel up slightly and then pull it away from the cabinet See Figure 6 for more details Wh...

Страница 12: ...7 for more details Removing a Side Panel Slide Across Pins Lift to Free Side Panel from Pins FIGURE 4 3 0 2 Removing the Side Pane Removing a Side Panel Slide Across Pins Lift to Fre Panel fro FIGURE...

Страница 13: ...r cabinet if applicable 1 Remove each shim after the cabinet panel has been removed by pulling firmly on the orange pull tab Figure 9 IMPORTANT Motor Shim 1 per motor Orange Pull Tab Fig 9 Removing Mo...

Страница 14: ...witch should always be located on the secured side Unsecured Side Unsecured Side Secured Side Secured Side Power Key Switch Power Key Switch Power Key Switch Power Key Switch Power Key Switch Power Ke...

Страница 15: ...led with appropriate holes as needed for concealment Determine which side plate to remove and remove it by unfastening the 4 screws as shown in Figure 12 Place the baseplate carefully in the marked lo...

Страница 16: ...ptimum performance Use the following procedure to square each cabinet with respect to the floor and other cabinets A Measure the distance from the inside wall of one cabinet to the inside wall of the...

Страница 17: ...of the anchor must be inserted into the hole first Use a hammer to tap the anchors into place if needed Ensure that the anchors are flush with the concrete floor 6 If not already done pull all wires A...

Страница 18: ...ot pull this power from the SU3500 power supply 1 Locate the card reader mounting bracket Figure 16 2 Using a Phillips head screwdriver remove the card reader bracket mounting screws Figure 16 3 Insta...

Страница 19: ...consist of the following Terminal 110V 220V Ground Green Green Yellow Neutral White Blue Line Black Brown 1 Locate the pre installed power terminal block and attached wiring located inside the leg on...

Страница 20: ...ned dry contacts SDC All input signals must be normally open N O voltage free dry contacts with the exception of the fire alarm input which can be configured via jumper on the I O control board to acc...

Страница 21: ...or one authorized passage until passage occurs or timeout 10 EXTALRX Unauthorized Presence Exit MDC An output occurs when there is entry into the lane area from the exit direction without authorizatio...

Страница 22: ...Key Control If this option has been ordered for your turnstiles two 3 position key switches are installed on the turnstile Turning the key to one of the three positions allows each turnstile directio...

Страница 23: ...ate the ENTPAS and GND terminals 2 Using a wire jumper connect the ENTPAS and GND terminals Figure 21 Exit Direction 1 Locate the EXTPAS and GND terminals 2 Use a wire jumper to connect the EXTPAS and...

Страница 24: ...es can be found in the SU3500 User Guide Flashing Passage Mode Description User Status Display Open Closed Status Light Controlled Passage The barrier wings are closed securing the lane Upon receipt o...

Страница 25: ...Appendix A on Page 29 for instructions on setting the barrier wing Home Closed Position The keys to power the turnstile ON OFF are packaged in the hardware box that was shipped with the turnstile Pow...

Страница 26: ...Unsecured Side Unauthorized Entry shown Authorized Entry shown Secured Side Unsecured Side TEST PROCEDURE TURNSTILE RESPONSE Enter the turnstile without authorization Unauthorized Entry Exit alarm so...

Страница 27: ...Free Passage direction Barriers open away from the user entering the turnstile Barriers close after passage completion Enter the turnstile User Status Light red icon is illuminated Open Closed Status...

Страница 28: ...as shown in Figure 25 Turning the key to one of three positions overrides all existing settings placing the turnstile in Controlled Passage mode Free Passage mode or No Passage mode depending on the...

Страница 29: ...ch programs and files field 5 Enter the following command ping XXX XXX XXX XXX where XXX XXX XXX XXX is the IP address of the turnstile Figure 28 6 A successful ping will result in the message shown i...

Страница 30: ...s move smoothly between the open and closed positions 3 Access Control Integration Installed card readers are successfully reading credentials Valid credentials are activating the turnstile 4 Barrier...

Страница 31: ...ctions Barriers operate erratically Barriers do not move Digital position encoder is not in place Verify the digital position encoder is secured to the pulley shaft with all the locks tabs in place Fi...

Страница 32: ...operation mode 2 Press the Test Mode button for two seconds The D2 LED will be lit solid You are now in test mode Figure A1 3 Move the barrier wing a couple of inches in both directions and then plac...

Страница 33: ...uration Three Lane Configuration LANE 2 LANE 2 LANE 3 LANE 1 LANE 1 Master Cabinet Master Cabinet Center Cabinet Center Cabinet Slave Cabinet Center Cabinet Slave Cabinet Symbology Description Conduit...

Страница 34: ...not provided Wire gauge recommendations for 30 50 and 100 ft runs are provided on Page 36 If your installation requires runs beyond 100 ft ensure wire gauge is appropriate and in compliance with local...

Страница 35: ...onduit holes on the enclosure Figure C3 4 Locate the pre installed primary power terminal block Figure C3 There is one primary power terminal block per enclosure 5 Attach each primary power wire to th...

Страница 36: ...urnstiles Fig C4 Power Supply Output Terminal Block Fig C5 Turnstile Power Terminal Block The 24VDC V and GND V terminals are common NOTE If connecting to multiple turnstiles it is recommended to labe...

Страница 37: ...ort alvaradomfg com 1 909 591 8431 Page 37 LANE 1 MASTER CABINET CENTER CABINET SLAVE CABINET CENTER CABINET LANE 2 LANE 3 110VAC 220VAC INPUT POWER SUPPLY ENCLOSURE 24VDC OUTPUT TO CIRCUIT BREAKER Ex...

Страница 38: ...ation Instructions Page 38 For assistance support alvaradomfg com 1 909 591 8431 PUD3673R1 1 24VDC CONDUIT HOLES 110 220VAC CONDUIT HOLE Power Supply Enclosure Dimensions 15 80 401 4 9 50 241 3 6 23 1...

Страница 39: ...ble Connection Diagrams MASTER SLAVE Master Cabinet Slave Cabinet SLAVE SLAVE MASTER MASTER Master Cabinet Center Cabinet Slave Cabinet LANE 1 LANE 2 SLAVE SLAVE SLAVE MASTER MASTER MASTER Master Cabi...

Страница 40: ...vision Date Author Description 1 0 07 18 14 A Flores Initial creation Replaces SU3500 Installation and Maintanence Guide PUD2890 1 1 11 13 15 A Flores Updated crossover cable length to 8 Appendix B Mu...

Страница 41: ...PUD3673R1 1 For assistance support alvaradomfg com 1 909 591 8431 Page 41 This page left intentionally blank...

Страница 42: ...2014 Alvarado Manufacturing Company Inc This work may not be reproduced published or redistributed in whole or in part without the express prior written permission of Alvarado...

Отзывы: