ALUTHERM
|
Boilers 32
ALUTERM A 170 - 300
|
Installation, user and service manual
|
instructions for user
Heating
Alutherm A 170 - 300
Note: Maximum allowed draught is 120 Pa, this means that in case of vertical flue the maximum length is limited to 30 mtrs
Boiler type
1
2
3
4
5
6
7
8
Component
A 170
A 210
A 260
A 300
Pressure drop [Pa]
Flue gas
[Pa]
Air
[Pa]
Flue gas
[Pa]
Air
[Pa]
Flue gas
[Pa]
Air
[Pa]
Flue gas
[Pa]
Air
[Pa]
Pipe length 1 m
Ø 250mm
0,4
0,7
1,0
1,4
Pipe length 1 m
Ø 150mm
1,4
2,1
3,1
4,2
Bend 90°
Ø 250mm
2,5
4,0
5,7
7,8
Bend 90°
Ø 150mm
5,3
8,3
12,0
16,4
Bend 45°
Ø 250mm
1,7
2,6
3,7
5,1
Bend 45°
Ø 150mm
2,3
3,5
5,1
6,9
Terminal C33
Ø200mm,Ø150mm
12,4
19,4
27,9
36,9
Terminal B23
Ø200mm
3,7
5,8
8,4
11,1
Terminal C53
Ø200mm,Ø150mm
3,7
12,2
5,8
19,0
8,4
27,4
11,1
36,3
Condensate trap
Ø200mm T + Bend 90°
5,0
8,0
11,4
15,4
Expander 110/150
0,7
1,0
1,5
2,1
Air filter
35
45
50
60