ALUTHERM
|
Boilers 30
ALUTERM A 170 - 300
|
Installation, user and service manual
|
instructions for user
Heating
Alutherm A 170 - 300
6.5.4
C53
Roof and wall terminals (see page 43) and expanders and/or condensate trap/collector must be obtained by M&G.
For pressure drop calculation of appliance type C53 use the table for pressure drop per component and the table for total pressure drop calculation.
See page 32.
For total available pressure drop see table on page 33.
6.5.5 C63
C63 appliances may only be equipped with Gastec QA materials and terminals or according NEN 14989-2
Note: When using a C63 type flue configuration, it is essential to ensure that C63 is allowed in the country where the boiler is installed.
It is recommended to use a full aluminium flue system. A PP (Temperature class T120) or stainless-steel flue system can also be used (See TPW table
below). In this case the condensate must be drained before it flows back into the aluminium parts of the boiler. Otherwise aggressive condensate
from the non-aluminium flue system can corrode the aluminium parts of the boiler. A condensate trap/collector must be mounted just before
entering the silencer(s) of the boiler (also see 6.6.1 general).
T-P-W Class table
Temperature range
T120
Pressure range
P1
Condensate resistance (W=wet / D=Dry)
W
The minimal combustion products temperature, mass flow rate and CO2 are given in the table below.
Type
part load
Vol. Flue m3/h
Vol. Air m3/h
CO2 %
T Fluegas ºC
rho kg/m3
A 170
33,6
43
38
9,1
30
1,12
A 210
42
54
47
9,1
30
1,12
A 260
50,4
65
57
9,1
30
1,12
A 300
58
75
65
9,1
30
1,12
The maximum allowed recirculation rate under wind conditions is 10 %
Maximum allowable combustion air temperature 45 °C
The tables below give an indication of maximum lengths (in mtrs) for parallel air supply and flue outlet pipes. Also, the equivalent of pipe length in
mtrs of bends 90 ° and 45 ° is given
Maximum lengths (in mtrs) for parallel air supply
Type
max. allowed
pressure drop (*)
Parallel Air/Flue gas
Ø110/ø200
Parallel
Air/Flue gas ø180/ø180
Parallel Air/Flue gas
Ø150/ø200
Right with air filter box
Parallel Air/Flue gas
ø200/ø200
A 170
150 Pa
13 m
112 m**
83 m**
63 m**
A 210
150 Pa
9 m
75 m**
53 m**
37 m**
120 m**
A 260
150 Pa
6 m
45 m**
36 m**
24 m**
82 m**
A 300
150 Pa
4 m
33 m**
26 m**
16 m**
60 m**
(**): Maximum allowed draught is 120 Pa; this means that in case of vertical flue the maximum length is limited to 30 mtrs