7. Maintenance
334
ATTENTION:
It is recommended the use of alphanumeric characters for the tag and module name (uppercase or
lowercase and the text does not start with numbers). In the field “description” use alphanumeric
characters (uppercase or lowercase), blank and period (".").The use of characters other than those
mentioned above is not recommended.
ATTENTION:
When using ETD - Electronic Tag on Display function, Diagnostic Explorer or Web Server to
display the tag of I/O points, the tag name is truncated in the first 24 characters after the string
"Application." of the tag name. Ex. For the tag "Application.UserPrg.MyTest.ON", only the string
"UserPrg.MyTest.ON" will be displayed on the graphic display.
ATTENTION:
When using ETD - Electronic Tag on Display function, Diagnostic Explorer or Web Server to view
the description of the tag of I/O points, the field will be truncated after the first 48 characters of the
tag description.
ATTENTION:
When using ETD - Electronic Tag on Display function, Diagnostic Explorer or Web Server to view
the module name, the field will be truncated after the first 24 characters of the module name
description.
Short and long press
Table 7-9 indicates times
Pressing
Type
Minimum
Time
Maximum
Time
Indication
Condition
No press
-
59.99 ms
-
Short
press
60 ms
0.99 s
Press and key
release within the
defined period
Long press
1 s
20 s
More than 1 s
pressing
Key
Locked
20.01 s
∞
More than 20 s
pressing
Table 7-9. Diagnostics Button Pressing Times
Not Loading the Application at Startup
If necessary, you can choose not to load an existing application on the CPU during its startup. For
that, energize the CPU via diagnostics button, by pressing it for at least two seconds. During the CPU
startup the display shows a message warning that the application will not be loaded and will go into
Stop Mode. In case of a login, MasterTool Xtorm software indicates that there is no application on
the CPU. For reloading the application, reboot the CPU or download a new application.
Power Supply Failure
Hadron Xtorm Series Power Supply presents a failure detection system according to the levels
defined in its technical features (see Main Features).