- 2 -
WayPoint17A
Overview:
WayPoint Outdoor Power Supplies provide 24VAC and/or 28VAC distributed via two (2), four (4) or eight (8) outputs
for powering CCTV cameras, heaters, and other video accessories.
WayPoint AC Reference Chart:
Altronix
Model Number
Output Voltage
Total
Output
Current
(Power)
Number
and Type
of Outputs
Fuse
Output
Ratings
PTC
Output
Ratings
Input Current Draw
Product
Weight
115VAC
60Hz
230VAC
50Hz
WayPoint17AU
24VAC
7.25A
2
5A/32V*
-----
2.0A
1A
5.95kg
28VAC
6.25A
24VAC and 28VAC
6.25A
1 of each
WayPoint17ADU
24VAC
7.25A
2
-----
2.5A
5.95kg
28VAC
6.25A
24VAC and 28VAC
6.25A
1 of each
WayPoint17A4U
24VAC
7.25A
4 Fused
5A/32V*
-----
5.95kg
28VAC
6.25A
WayPoint17A4DU
24VAC
7.25A
4 PTCs
-----
2.5A
5.95kg
28VAC
6.25A
WayPoint17A8U
24VAC
7.25A
8 Fused
5A/32V*
-----
6.1kg
28VAC
6.25A
WayPoint17A8DU
24VAC
7.25A
8 PTCs
-----
2.5A
6.1kg
28VAC
6.25A
*Lower rated fuses can be used.
Specifications:
Installation Instructions:
Unit should be installed in accordance with The National Electrical Code and all applicable Local Regulations.
1. Remove back plane from enclosure prior to mounting (do not discard hardware).
2. Mark and drill desired inlets on the enclosure to facilitate wiring (Fig. 1, pg. 4).
Note: Inlets for conduit fittings should only be made on the bottom of the enclosure.
UL Listed NEMA type 4X rated conduit connector/hubs shall be used for the appropriate size inlets.
3. Mount unit in desired location. Mark and drill holes to line up with the top and bottom holes of the enclosure flange.
Secure enclosure with appropriate fasteners (Fig. 5, pg. 7 and Fig. 10, pg. 8).
4. Mount back plane to enclosure with hardware.
5. Set the input voltage selector switch for 115VAC or 230VAC operation (Figs. 2-4, pgs. 4-6)
6. To facilitate wire entry utilize weather-tight NEMA 4 rated connectors, bushings, and cable.
7. Set illuminated master power disconnect circuit breaker to the [OFF] position (Figs. 2-4, pgs. 4-6).
8. Connect unswitched AC power (115VAC/230VAC, 50/60 Hz) to terminals marked [L, N] (Figs. 2-4, pgs. 4-6).
Green branch wire connects to earth (safety) ground lug .
Wire gauge range of connectors is 14 AWG to 11 AWG (1.6 mm to 2.5 mm diameter).
9. Set illuminated master power disconnect circuit breaker to the [RESET/ON] position (Figs. 2-4, pgs. 4-6).
10. WayPoint17A4U/A4DU, WayPoint17A8U/A8DU are factory set for 24VAC operation.
For 28VAC operation, adjust unit prior to mounting and applying power as follows:
Change the wire position so that the black wire [28V] is connected to the terminal marked [P] and
the yellow wire [24V] is connected to the terminal marked [S].
Agency Listings:
• UL/cUL Listed for Information Technology Equipment
(UL 60950-1) and Equipment to be Installed Outdoors
(UL 60950-22).
• CE European Conformity.
Input:
• Input: 115VAC, 60Hz, 2A or 230VAC, 50Hz, 1A.
Output:
• Output options:
a. 24VAC or 28VAC.
b. Both 24VAC and 28VAC (WayPoint17AU/ADU only).
Visual Indicators:
• Individual power output LED indicators.
Visual Indicators
(cont’d)
:
• Illuminated master power switch.
Features:
• Surge suppression.
• Spare fuses included.
Accessories:
• Optional PMK1 Pole Mount Kit simplifies installation of
outdoor units.
Enclosure:
• NEMA 4/4X, IP66-11 Rated enclosure for outdoor use.
• Enclosure Dimensions (H x W x D approx.):
13.31” x 11.31” x 5.59”
(338.074 mm x 287.274 mm x 141.986 mm).