- 4 -
T1RSH3F8
LED Diagnostics:
eFlow6NB:
Red (DC)
Green (AC/AC1)
Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery is supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
ACMS8:
LED
ON
OFF
LED 1- LED 8 (Red)
Output relay(s) de-energized.
Output relay(s) energized.
FACP
FACP input triggered (alarm condition).
FACP normal (non-alarm condition).
Green Output 1-8
12VDC
–
Red/Green Output 1-8
24VDC
–
Terminal Identification:
eFlow6NB:
Terminal Legend
Function/Description
L, N
Factory connected to line cord (non power-limited).
– DC +
Factory set for 12VDC or 24VDC nominal @ 6A continuous output (non power-limited output).
Trigger EOL
Supervised
Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open, normally closed
from an FACP output circuit (power-limited input).
NO, GND RESET
FACP interface latching or non-latching (power-limited).
+ AUX –
Auxiliary Class 2 power-limited output rated @ 1A (unswitched).
AC Fail
NC, C, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when
AC power is present. Contact rating 1A @ 30VDC (power-limited).
Bat Fail
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present.
Contact rating 1A @ 30VDC. A removed battery is reported within 5 minutes. Battery reconnection is reported
within 1 minute (power-limited).
– BAT +
Stand-by battery connections. Maximum charge current 1.54A (non power-limited).
ACMS8:
Terminal Legend
Function/Description
+ PWR1 –
12 or 24VDC input from Power Supply.
+ PWR2 –
12 or 24VDC input from Power Supply.
+ INP1 – through
+ INP8 –
Eight (8) independently controlled Normally Open (NO), Normally Closed (NC),
Open Collector Sink or Wet Input Triggers.
C, NC
FACP Dry NC output. With EOL JMP intact, will provide 10k resistance in a normal condition.
GND, RST
FACP interface latching or non-latching
GND, EOL
EOL Supervised FACP Input terminals
– F, + F, – R, + R
FACP Signaling Circuit Input and Return terminals
Output 1 through
Output 8
NO, C, NC, COM
Eight (8) selectable 5VDC-24VDC independently controlled outputs [Fail-Safe (NC) or Fail-Secure (NO)]
and eight (8) independently controlled Form “C” Relay outputs.
Fuses are rated 2.5A each.