Altronix STRIKEIT2 Скачать руководство пользователя страница 4

 

- 4 - 

StrikeIt2

LED Diagnostics:

LED

LED Status

Panic Device Power Controller Status

AC Power Green

On

Normal operating condition .

Off

Loss of AC .

Red

On

24VDC present on the output (unit is triggered) .

Off

Loss of 24VDC on the output (unit is not triggered) .

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test: 

Under normal load conditions the DC output voltage should be checked for proper 

 

voltage level .

Battery Test: 

Under normal load conditions check that the battery is fully charged, check specified 

 

voltage both at battery terminal and at the board terminals marked [– BAT +] to 

 

ensure that there is no break in the battery connection wires .

 Note: Maximum charging current under discharge is 300mA .
 Note: 

Expected battery life is 5 years; however, it is recommended changing 

 

batteries in 4 years or less if needed .

Caution: 

For continuous protection against risk of electric shock and fire hazard, replace input 

 

fuse with the same type and rating 6 .3A/250V . Do not expose to rain or moisture; 

 

indoor use only . 

Terminal Identification:

Terminal Legend

Function/Description

– AUX  +

23 .2-24VDC Auxiliary Output @ 0 .5A .

– BAT +

23 .2-24VDC Stand-by Battery Connection (Two (2) 12VDC batteries wired in series) .

– OUT +

Connect 24VDC Panic Hardware Device, up to 16A for 300 ms ., 0 .5A on hold .

GND / NO

Normally Open [NO] trigger input controls output . 
A maintained contact closure will extend the unlock period .

Wiring Distance Table:

InRush
Current

Wire Gauge

Electric Butt or Pivot

Max distance from Power Supply

to frame side of opening

EPT

Max distance from Power Supply to

frame side of opening

8A

14 AWG Stranded

75 ft .

100 ft .

8A

12 AWG Stranded

175 ft .

200 ft .

12A

14 AWG Stranded

60 ft .

75 ft .

12A

12 AWG Stranded

80 ft .

100 ft .

16A

14 AWG Stranded

40 ft .

75 ft .

16A

12 AWG Stranded

60 ft .

80 ft .

Содержание STRIKEIT2

Страница 1: ...Rev 050608 More than just power TM Panic Device Power Controller Installation Guide Altronix Corp 140 58th St Brooklyn NY...

Страница 2: ...Overview pg 3 Specifications pg 3 Installation Instructions pg 3 LED Diagnostics pg 4 Maintenance pg 4 Terminal Identification pg 4 Wiring Distance Table pg 4 Typical Application Diagram pg 5 Enclosu...

Страница 3: ...all the two lower screws and make sure to tighten all screws Enclosure Dimensions pg 4 Secure cabinet to earth ground 2 Connect AC power 115VAC 60Hz to the terminals marked L G N Fig 1 pg 5 Fig 2 pg 6...

Страница 4: ...ecommended changing batteries in 4 years or less if needed Caution For continuous protection against risk of electric shock and fire hazard replace input fuse with the same type and rating 6 3A 250V D...

Страница 5: ...t2 5 Typical Application Diagram OUT L G N GND NO BAT Aux Trg Panic Hardware Device 24VDC REX PIR Access Control Panel Rechargeable Batteries 12VDC 12VDC 115VAC power mains non power limited 6 3A 250V...

Страница 6: ...A 250V Do not expose to rain or moisture Tamper Switch OUT L G N GND NO BAT Aux 6 3A 250V Fig 2a Fig 2b Edge of Enclosure to Access Control Panel or U L Listed Reporting Device Enclosure Honeywell mod...

Страница 7: ...StrikeIt2 7 Notes...

Страница 8: ...mm 1 25 4mm 1 25 4mm 0 6 15 24mm 0 6 15 24mm 1 125 28 575mm 0 6 15 24mm 3 625 184 15mm Enclosure Dimensions H x W x D approximate 8 5 x 7 5 x 3 5 215 9mm x 190 5mm x 88 9mm Altronix is not responsible...

Отзывы: