StrikeIt2 

- 3 -

Overview:

Altronix StrikeIt2 operates one (1) 24VDC panic hardware device . It is designed to handle the high current surge 
panic hardware locking devices demand . In addition, an auxiliary power output provides power for accessory 
devices such as card readers, keypads, REX PIRs, electronic timers, relays, etc .

Specifications:

Agency Approval:

• 

UL 294  

Access Control

   

System 

Units .

• 

CSA Standard C22.2   Signal Equipment .

 

No.205-M1983  

• 

CSFM 

California State

     

Fire Marshal Approved .

Input:

•  115VAC, 60Hz, 7A .
•  One (1) N/O trigger input .

Output:

•  One (1) 23 .2-24VDC lock output rated up to 16A 
  for 300ms, 0 .5A continuous hold current .*
•  One (1) 23 .2-24VDC filtered regulated auxiliary 
  output rated @ 0 .5A continuous supply current*
 

* Note: Total combined current for the outputs 

    may not exceed 1A .

Battery Backup:

•  Battery leads included .
•  Built-in charger for sealed lead acid or 
  gel type batteries .
•  Automatic switch over to stand-by battery 
  when AC fails .
•  Maximum charge current 0 .3A .
•  When 4AH batteries are used, battery capacity 
  for emergency stand-by is at least a 1/2 hour .

Visual Indicators:

•  Green AC Power LED indicates 115VAC present .
•  Red LED indicates presence of 24VDC .

Mechanical:

•  Enclosure Dimensions (H x W x D approx .):
  8 .5” x 7 .5” x 3 .5” (215 .9mm x 190 .5mm x 88 .9mm)
•  Enclosure accommodates up to two (2) 
  12VDC/4AH batteries .

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with 
all local codes and authorities having jurisdiction . Product is intended for indoor use only .
1 .  Mount unit in the desired location within protected premises (Maximum Wiring Distance Table, pg . 5) . Mark 
  and predrill holes in the wall to line up with the top two keyholes in the enclosure . Install two upper fasteners 
  and screws in the wall with the screw heads protruding . Place the enclosure’s upper keyholes over the two 
  upper screws; level and secure . Mark the position of the lower two holes . Remove the enclosure . Drill the 
  lower holes and install the two fasteners . Place the enclosure’s upper keyholes over the two upper screws . 
  Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 4) . 
  Secure cabinet to earth ground .
2 .  Connect AC power (115VAC, 60Hz) to the terminals marked [L, G, N] (Fig. 1, pg. 5 & Fig. 2, pg. 6) . 
  The AC LED (Green) will illuminate, indicating power is present .
  Keep power-limited wiring separate from non power-limited wiring (115VAC, 60Hz Input, 
  Battery Wires). Minimum 0.25” spacing must be provided 
(Fig. 2, pg. 6)
  CAUTION: Do not touch exposed metal parts. 
  Shut branch circuit power before installing or servicing equipment. 
  There are no user serviceable parts inside. 
  Refer installation and servicing to qualified service personnel. 
3 .  Measure output voltage at the terminals marked [– AUX +] and [– OUT +] before connecting devices 
  (Fig. 1, pg. 5 & Fig. 2b, pg. 6) . This helps avoiding potential damage .
 

Note: Voltage will be present on the output when the unit is not triggered and electric panic hardware 

  is not connected .
4 .  Connect 24VDC panic hardware device to the terminals marked [– OUT +] (Fig. 1, pg. 5 & Figs. 2 & 2b, pg. 6) . 
  Be sure to observe polarity . Voltage should dissipate across output terminals when load is properly connected . 
5 .  Connect Normally Open [NO] Dry Contacts from actuating devices such as an Access Control Panel, 
  REX PIR, Keypad, etc . to the terminals marked [GND, NO] (Fig. 1, pg. 5 & Fig. 2b, pg. 6) .
6 .  Connect auxiliary devices to be powered (Keypads, REX motion detectors, electronic timers, external relays) 
  to the auxiliary power output terminals marked [– AUX +] (Fig. 1, pg. 5 & Fig. 2b, pg. 6) . 
7 .  When using stand-by batteries, they must be lead acid or gel type . 4AH batteries will provide a 1/2 hour of 
  backup time . Connect two (2) 12VDC batteries wired in series to the terminals marked [– BAT +] . 
  For Access Control applications batteries are optional . When batteries are not used, a loss of AC will result in 
  the loss of output voltage (Fig. 2b, pg. 6) .
8 .  Mount UL Listed tamper switch (Honeywell model 112 or equivalent) at the top of the enclosure . Slide the 
  tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 2a, pg. 6) . 
  Connect tamper switch wiring to the Access Control Panel input or the appropriate 
  UL Listed reporting device . To activate alarm signal open the door of the enclosure .
9 .  Upon completion of the wiring secure enclosure door with screws or cam lock .

Содержание STRIKEIT2

Страница 1: ...Rev 050608 More than just power TM Panic Device Power Controller Installation Guide Altronix Corp 140 58th St Brooklyn NY...

Страница 2: ...Overview pg 3 Specifications pg 3 Installation Instructions pg 3 LED Diagnostics pg 4 Maintenance pg 4 Terminal Identification pg 4 Wiring Distance Table pg 4 Typical Application Diagram pg 5 Enclosu...

Страница 3: ...all the two lower screws and make sure to tighten all screws Enclosure Dimensions pg 4 Secure cabinet to earth ground 2 Connect AC power 115VAC 60Hz to the terminals marked L G N Fig 1 pg 5 Fig 2 pg 6...

Страница 4: ...ecommended changing batteries in 4 years or less if needed Caution For continuous protection against risk of electric shock and fire hazard replace input fuse with the same type and rating 6 3A 250V D...

Страница 5: ...t2 5 Typical Application Diagram OUT L G N GND NO BAT Aux Trg Panic Hardware Device 24VDC REX PIR Access Control Panel Rechargeable Batteries 12VDC 12VDC 115VAC power mains non power limited 6 3A 250V...

Страница 6: ...A 250V Do not expose to rain or moisture Tamper Switch OUT L G N GND NO BAT Aux 6 3A 250V Fig 2a Fig 2b Edge of Enclosure to Access Control Panel or U L Listed Reporting Device Enclosure Honeywell mod...

Страница 7: ...StrikeIt2 7 Notes...

Страница 8: ...mm 1 25 4mm 1 25 4mm 0 6 15 24mm 0 6 15 24mm 1 125 28 575mm 0 6 15 24mm 3 625 184 15mm Enclosure Dimensions H x W x D approximate 8 5 x 7 5 x 3 5 215 9mm x 190 5mm x 88 9mm Altronix is not responsible...

Отзывы: