Overview:
Altronix StrikeIt2 operates one (1) 24VDC panic hardware device . It is designed to handle the high current surge
panic hardware locking devices demand . In addition, an auxiliary power output provides power for accessory
devices such as card readers, keypads, REX PIRs, electronic timers, relays, etc .
Specifications:
Agency Approval:
•
UL 294
Access Control
System
Units .
•
CSA Standard C22.2 Signal Equipment .
No.205-M1983
•
CSFM
California State
Fire Marshal Approved .
Input:
• 115VAC, 60Hz, 7A .
• One (1) N/O trigger input .
Output:
• One (1) 23 .2-24VDC lock output rated up to 16A
for 300ms, 0 .5A continuous hold current .*
• One (1) 23 .2-24VDC filtered regulated auxiliary
output rated @ 0 .5A continuous supply current*
* Note: Total combined current for the outputs
may not exceed 1A .
Battery Backup:
• Battery leads included .
• Built-in charger for sealed lead acid or
gel type batteries .
• Automatic switch over to stand-by battery
when AC fails .
• Maximum charge current 0 .3A .
• When 4AH batteries are used, battery capacity
for emergency stand-by is at least a 1/2 hour .
Visual Indicators:
• Green AC Power LED indicates 115VAC present .
• Red LED indicates presence of 24VDC .
Mechanical:
• Enclosure Dimensions (H x W x D approx .):
8 .5” x 7 .5” x 3 .5” (215 .9mm x 190 .5mm x 88 .9mm)
• Enclosure accommodates up to two (2)
12VDC/4AH batteries .
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with
all local codes and authorities having jurisdiction . Product is intended for indoor use only .
1 . Mount unit in the desired location within protected premises (Maximum Wiring Distance Table, pg . 5) . Mark
and predrill holes in the wall to line up with the top two keyholes in the enclosure . Install two upper fasteners
and screws in the wall with the screw heads protruding . Place the enclosure’s upper keyholes over the two
upper screws; level and secure . Mark the position of the lower two holes . Remove the enclosure . Drill the
lower holes and install the two fasteners . Place the enclosure’s upper keyholes over the two upper screws .
Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 4) .
Secure cabinet to earth ground .
2 . Connect AC power (115VAC, 60Hz) to the terminals marked [L, G, N] (Fig. 1, pg. 5 & Fig. 2, pg. 6) .
The AC LED (Green) will illuminate, indicating power is present .
Keep power-limited wiring separate from non power-limited wiring (115VAC, 60Hz Input,
Battery Wires). Minimum 0.25” spacing must be provided (Fig. 2, pg. 6).
CAUTION: Do not touch exposed metal parts.
Shut branch circuit power before installing or servicing equipment.
There are no user serviceable parts inside.
Refer installation and servicing to qualified service personnel.
3 . Measure output voltage at the terminals marked [– AUX +] and [– OUT +] before connecting devices
(Fig. 1, pg. 5 & Fig. 2b, pg. 6) . This helps avoiding potential damage .
Note: Voltage will be present on the output when the unit is not triggered and electric panic hardware
is not connected .
4 . Connect 24VDC panic hardware device to the terminals marked [– OUT +] (Fig. 1, pg. 5 & Figs. 2 & 2b, pg. 6) .
Be sure to observe polarity . Voltage should dissipate across output terminals when load is properly connected .
5 . Connect Normally Open [NO] Dry Contacts from actuating devices such as an Access Control Panel,
REX PIR, Keypad, etc . to the terminals marked [GND, NO] (Fig. 1, pg. 5 & Fig. 2b, pg. 6) .
6 . Connect auxiliary devices to be powered (Keypads, REX motion detectors, electronic timers, external relays)
to the auxiliary power output terminals marked [– AUX +] (Fig. 1, pg. 5 & Fig. 2b, pg. 6) .
7 . When using stand-by batteries, they must be lead acid or gel type . 4AH batteries will provide a 1/2 hour of
backup time . Connect two (2) 12VDC batteries wired in series to the terminals marked [– BAT +] .
For Access Control applications batteries are optional . When batteries are not used, a loss of AC will result in
the loss of output voltage (Fig. 2b, pg. 6) .
8 . Mount UL Listed tamper switch (Honeywell model 112 or equivalent) at the top of the enclosure . Slide the
tamper switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 2a, pg. 6) .
Connect tamper switch wiring to the Access Control Panel input or the appropriate
UL Listed reporting device . To activate alarm signal open the door of the enclosure .
9 . Upon completion of the wiring secure enclosure door with screws or cam lock .