Overview:

Altronix SMPWP Series DC Outdoor Power Supply/Chargers provide 12VDC or 24VDC and are designed to be 

conveniently located where power is required.

SMPWP Series Reference Chart:

Altronix 

Model Number

Output

Current

 Output

Voltage

SW1

115VAC/60Hz

Input

Current Draw

230VAC/50Hz

Input

Current Draw

12VDC

24VDC

SMP3WP

2.5A

12VDC or 24VDC

ON

OFF

0.95A

0.6A

SMP5WP

3.5A

12VDC or 24VDC

ON

OFF

0.95A

0.6A

SMP7WP

6A

12VDC or 24VDC

ON

OFF

1.9A

N/A

SMP7WPV

6A

12VDC or 24VDC

ON

OFF

N/A

0.95A

Specifications:

Input:

•  Input: 115VAC, 60Hz or 230VAC, 50Hz.

Output:

•  12VDC or 24VDC selectable output 

•  Filtered and electronically regulated output.

•  Thermal overload and short circuit protection.

Battery Backup:

•  Built-in charger for sealed lead acid or 

  gel type batteries. 

•  Maximum charge current: 500mA

•  Automatic switch over to stand-by battery.

•  Includes battery leads.

Features:

•  AC and DC power LED indicators.

•  Ease of installation saves time and eliminates 

  costly labor.

Accessories:

•  Optional PMK1 Pole Mount Kit simplifies 

  installation of outdoor units.

Enclosure:

•  NEMA 4/4X, IP66-11 Rated enclosure for 

  outdoor use.

•  Enclosure Dimensions (H x W x D approx.):

  12” x 8” x 6” (304.8mm x 203.2mm x 152.4mm)

Installation Instructions:

Wiring methods should be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all 

local codes and authorities having jurisdiction. 

1.  Remove backplane from the enclosure prior to mounting (do not discard hardware).

2.  Mark and drill desired inlets on the enclosure to facilitate wiring 

(Fig. 1, pg. 3).

3.  Mount unit in the desired location. For wall mounting refer to 

Fig. 3, pg. 6

.

 

For pole mounting installation refer to 

pg. 6 - (Using Optional Altronix Pole Mount Kit PMK1 - not included)

.

4.  Install backplane inside the enclosure with hardware.

5.  Set power switch to the OFF position 

(Fig. 2c, pg. 4).

6.  Connect AC power to the terminals marked [L & N]. 

 

Green branch wire connects to earth (safety) ground lug     . 

(Fig. 2, pg. 4)

 

Wire gauge range of connectors is 14 AWG to 11 AWG (1.6mm to 2.5mm diameter).

7.  Select the desired DC output voltage by setting SW1

 

to the appropriate position 

(Reference Chart above) 

 

(Fig. 2a, pg. 4)

8.  Set power switch to the ON position 

(Fig. 2b, pg. 4).

9.  Measure output voltage at the terminals marked [– DC +] before connecting devices  

(Fig. 2b, pg. 4)

 

This helps avoiding potential damage.

 

Note:

 Power supplies mounted in weatherproof enclosures should be derated by approximately 50%

 

due to the harsh environmental conditions.

10.  Set power switch to the OFF position 

(Fig. 2c, pg. 4).

11.  Connect devices to be powered to the terminals marked [– DC +] 

(Fig. 2b, pg. 4, Fig. 3b, pg. 5)

.

12.  Connect optional stand-by battery to the terminals marked [– BAT +]. Battery leads included. 

 

If batteries are required, they need to be mounted in a separate NEMA rated enclosure adjacent to the power 

 supply 

(Fig. 2b, pg. 4, Fig. 3b, pg. 5)

.

 

Note:

 When batteries are not used, a loss of AC will result in a loss of output voltage.

13.  Set power switch to the ON position 

(Fig. 2c, pg. 4).

14.  Upon completion of the wiring secure enclosure door with latches and optional lock.

Ground Lug

L        G       

N

- BAT+

OFF       ON

- DC 

+

AC

DC

Input

115VAC or

220VAC

OFF - 24V ON - 12V

ON

CAUTION

HIGH VOLTAGE

- BAT+

- DC +

OFF       ON

OFF - 24V

ON - 12V

ON

Содержание SMPWP Series

Страница 1: ...t SMP7WPV 6A 12VDC or 24VDC 230VAC input SMPWP Series DC Outdoor Power Supply Chargers Models Include Rev 040622 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ______________________________________________ Phone ___________________ Installation Guide ...

Страница 2: ... desired inlets on the enclosure to facilitate wiring Fig 1 pg 3 3 Mount unit in the desired location For wall mounting refer to Fig 3 pg 6 For pole mounting installation refer to pg 6 Using Optional Altronix Pole Mount Kit PMK1 not included 4 Install backplane inside the enclosure with hardware 5 Set power switch to the OFF position Fig 2c pg 4 6 Connect AC power to the terminals marked L N Green...

Страница 3: ...reen AC Power Supply Status ON ON Normal operating condition ON OFF Loss of AC Stand by battery supplying power OFF ON No DC output Short circuit or thermal overload condition OFF OFF No DC output Loss of AC Discharged or no battery present Terminal Identification Terminal Legend Function Description DC SMP3WP 12VDC or 24VDC 2 5A supply current SMP5WP 12VDC or 24VDC 3 5A supply current SMP7WP 12VD...

Страница 4: ... SMPWP Series Installation Guide Fig 2 SMPWP Series Ground Lug L G N BAT OFF ON DC AC DC Input 115VAC or 220VAC OFF 24V ON 12V ON CAUTION HIGH VOLTAGE BAT DC OFF ON OFF 24V ON 12V ON Fig 2a Fig 2c Fig 2b ...

Страница 5: ...ay be of sufficient magnitude to constitute an electric shock The exclamation point within an equilateral triangle is intended to alert the user to the presence of impor tant operating and maintenance servicing instructions in the literature accompanying the appliance CAUTION To reduce the risk of electric shock do not open enclosure There are no user serviceable parts inside Refer servicing to qu...

Страница 6: ...of the strap through the locking mechanism on the strap then tighten the screw with flat head screwdriver or 5 16 hex socket driver Fig 5 pg 6 and Fig 7 pg 6 3 Attach the bottom bracket to the enclosure by inserting bolts through the flange of the enclosure and into the bracket tightening bolts with a 7 16 hex socket Fig 6 pg 6 4 Thread the second wormgear quick release strap through the slots on ...

Страница 7: ...SMPWP Series Installation Guide 7 Notes ...

Страница 8: ...e 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com IISMPWP Series D06V MEMBER Enclosure Dimensions H x W x D approximate 12 x 8 x 6 304 8mm x 203 2mm x 152 4mm GALVANIZED MOUNTING PANEL CARBON STEEL SHEET 13 330 2mm 4 05 103mm 6 152 4mm 8 203 2mm 4 21 107mm 12 304 8mm 6 7 170 2mm 9 84 250mm 0 08 2mm 14 355 6mm ...

Отзывы: