Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
Altronix Corp.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
IISMP7WP - Rev. 061609
F16I
MEMBER
0.75
"
0.75
"
11.25
"
12.00
"
10.00
"
8.77
"
8.00
"
7.40
"
0.50
"
2.00
"
0.77
"
6.00
"
6. When using stand-by batteries, they must be lead acid or gel type. Connect battery to terminals marked [- BAT +]
(battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation.
Note: When batteries are not used a loss of AC will result in the loss of output voltage.
LED Diagnostics:
Terminal Identification:
Enclosure Dimensions:
12”H x 8”W x 6”D
Red (DC)
Green (AC) Power Supply Status
ON
ON
Normal operating condition.
ON
OFF
Loss of AC, Stand-by battery supplying power.
OFF
ON
No DC output.
OFF
OFF
Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Legend
Function/Description
L, G, N
Connect 115VAC to these terminals: L to Hot, N to Neutral, G to ground (if used).
-- DC +
12VDC or 24VDC @ 6 amp continuous supply current.
-- BAT +
Stand-by battery connections. Maximum charge rate 700mA.