background image

Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

Altronix Corp.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: [email protected], Lifetime Warranty, Made in U.S.A.
IISMP7WP - Rev. 061609

F16I

MEMBER

0.75

"

0.75

"

11.25

"

12.00

"

10.00

"

8.77

"

8.00

"

7.40

"

0.50

"

2.00

"

0.77

"

6.00

"

6. When using stand-by batteries, they must be lead acid or gel type. Connect battery to terminals marked [- BAT +] 

(battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation.
Note: When batteries are not used a loss of AC will result in the loss of output voltage.

LED Diagnostics:

Terminal Identification:

Enclosure Dimensions:

12”H x 8”W x 6”D

Red (DC)

Green (AC) Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC, Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Legend

Function/Description

L, G, N

Connect 115VAC to these terminals: L to Hot, N to Neutral, G to ground (if used).

-- DC +

12VDC or 24VDC @ 6 amp continuous supply current.

-- BAT +

Stand-by battery connections. Maximum charge rate 700mA.