6.  When using stand-by batteries, they must be lead acid or gel type. Connect battery to the terminals marked [– BAT +] 
 

(battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation (Fig. 4, pg. 3).

 

Note: When batteries are not used, a loss of AC will result in the loss of output voltage.

7.  Connect appropriate signaling notification devices to the AC Fail & Low Bat supervisory relay outputs marked [NC, C, NO] 
 

(supervised models only) (Fig. 4a, pg. 3).

LED Diagnostics:

Power Supply Board

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Power Distribution Module

Green

Power Distribution Module Status

ON

Normal operating condition.

Terminal Identification:

Power Supply Board

Terminal Legend

Function/Description

L, G, N

Connect 115VAC to these terminals: L to Hot, N to Neutral.

---  DC +

12VDC / 24VDC @ 6A continuous output.

AC FAIL
NC, C, NO

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally
energized when AC power is present. Contact rating 1A @ 120VAC / 28VDC.

Low Battery
NC, C, NO

Used to indicate low battery condition, e.g. connect to alarm panel. 
Relay normally energized when DC power is present. Contact rating 1A @ 120VAC / 28VDC.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC, 
24VDC output threshold set @ approximately 21VDC. 

---  BAT +

Stand-by battery connections. Maximum charge rate 0.7A.

Power Distribution Module

Terminal Legend

Function/Description

 PD4/PD4CB 

 PD8/PD8CB 

 PD16W/PD16WCB 

1P to 4P

1P to 8P

1P to 16P

Positive DC power outputs

1N to 4N

1N to 8N

1N to 16N

Negative DC power outputs

Fig. 1

Fig. 2

Power Distribution Module(s):

 

- 2 -  

SMP7CTX Series