2.  Slide [Power ON/OFF] switch t o OFF position.
3.  Set SW1 on the power supply board to the desired DC output voltage
 

(Power Supply Voltage Output Specification Chart).

4.  Connect AC power to the terminals marked [L & N].
 

Use 18 AWG or larger for all power connections (Battery, DC output).

 

Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/Low Battery reporting).

5.  Slide [Power ON/OFF] switch to ON position.
 

Keep power-limited wiring separate from non power-limited wiring (115/230VAC / 60Hz Input, Battery Wires).  

 

Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment.

 

There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.

 

Note: Measure output voltage before connecting devices. This helps avoiding potential damage. 

6.  Slide [Power ON/OFF] switch t o OFF position.
7.  Connect devices to be powered:
 

a.  For Power Supply Board: connect to the terminals marked [– DC + ]. 

 

b.  For Power Distribution Module(s): connect devices to be powered to the terminal pairs 1 to 4 marked  

 

    [1P & 1N] through [4P & 4N] (Fig. 2, pg. 4) or 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3, pg. 4)

 

  or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 4, pg. 4), carefully observing correct polarity.
 

Note: Power switch is used to disconnect the L (HOT) terminal from the rest of the board. When servicing the unit, 

 

AC mains should be removed.

8.  When using stand-by batteries, they must be lead acid or gel type. Connect battery to the terminals marked
 

[– BAT +] (battery leads included). Use two (2) 12VDC batteries connected in series for 24VDC operation.

 

Note: When batteries are not used, a loss of AC will result in the loss of output voltage.

9.  Connect appropriate signaling notification devices to AC Fail & Low Bat supervisory relay outputs 
 

marked [NC, C, NO] (Fig. 1a, pg. 3).

10.  Slide [Power ON/OFF] switch to ON position.

LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Power Supply Board:

Terminal Legend

Function/Description

L, G, N

Connect 115VAC/230VAC to these terminals: L to Hot, N to Neutral.

– DC +

12VDC / 24VDC @ 4A continuous non power-limited output.

AC FAIL 

NC, C, NO

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally 

energized when AC power is present. Contact rating 1A @ 120VAC / 28VDC.

Low Battery 

NC, C, NO.

Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized 

when DC power is present. Contact rating 1A @ 120VAC / 28VDC. 

Low battery threshold: 12VDC output threshold set @ approximately 10.5VDC,

24VDC output threshold set @ approximately 21VDC.

– BAT +

Stand-by battery connections. Maximum charge rate 0.5A.

PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module:

Terminal Legend

Function/ Description

PD4/PD4CB

PD8/PD8CB

PD16W/PD16WCB

1P to 4P

1P to 8P

1P to16P

Positive DC power outputs.

1N to 4N

1N to 8N

1N to 16N

Negative DC power outputs.

 

- 2 -  

SMP5CTX Series

Содержание SMP5CTX Series

Страница 1: ...4A 0 95A 0 5A 4A SMP5PMCTX P SMP5PMCTXX SMP5PMP4 PD4 4 P 3 5A SMP5PMP4CB PD4CB P 2 5A SMP5PMP8 PD8 8 P 3 5A SMP5PMP8CB PD8CB P 2 5A SMP5PMP16 PD16W 16 P 3 5A SMP5PMP16CB PD16WCB P 2 5A Specifications...

Страница 2: ...must be lead acid or gel type Connect battery to the terminals marked BAT battery leads included Use two 2 12VDC batteries connected in series for 24VDC operation Note When batteries are not used a l...

Страница 3: ...es power mains line voltage input If stand by battery batteries are connected the DC output remains on ON OFF LED Diagnostics Red Green Power Supply Status DC AC ON ON Normal operating condition ON OF...

Страница 4: ...UTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices From Power Supply Board Factory Installed Used on PTC Models Fig 2 Fig 3 Power Distribution Module s common outputs pr...

Страница 5: ...Also available to accommodate up to two 2 12VDC 12AH batteries please contact Altronix 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625...

Страница 6: ...5 0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm 1 75 44 45mm 1 75 44 45mm 4 5 114 3mm 1 25 31 75mm 4 5 114 3mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91...

Страница 7: ...Notes SMP5CTX Series 7...

Страница 8: ...pecifications are subject to change without notice 140 58th Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix com Lifetime warranty Made i...

Отзывы: