SMP3CTX series

5.  Connect devices to be powered:
  a. For Power Supply Board connect to the terminals marked [– DC +]. 
  b. For Power Distribution Module(s) connect devices to be powered to the terminal pairs 1 to 4 marked  
  [1P & 1N] through [4P & 4N] (Fig. 2, pg. 3), 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3, pg. 3), or 1 to 16 
  marked [1P & 1N] through [16P & 16N] (Fig. 4, pg. 3), carefully observing correct polarity.
 

*Note: Power switch is used to disconnect the L (HOT) terminal from the rest of the board (Fig. 1a, pg. 3).

  When servicing the unit, AC mains should be removed.
6.  When using stand-by batteries, they must be lead acid or gel type. Connect battery to the terminals marked [– BAT +] 
  (battery leads included).
 

12VDC operation: Use one (1) 12VDC battery.

 

24VDC operation: Use two (2) 12VDC batteries connected in series.

 

Note: When batteries are not used, a loss of AC will result in the loss of output voltage.

For supervised models only:
7.  Connect appropriate signaling notification devices to AC Fail & Low Bat supervisory relay outputs 
  marked [NC, C, NO] (Fig. 1b, pg. 3).

LED Diagnostics:

Red (DC) Green (AC) Power Supply Status
ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Power Supply Board:

Terminal Legend Function/Description
L, G, N

Connect 115VAC/230VAC to these terminals: L to Hot, N to Neutral.

–  DC +

12VDC / 24VDC @ 2.5 amp continuous output.

*AC FAIL 
NC, C, NO

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally 
energized when AC power is present. Contact rating 1 amp @ 120VAC / 28VDC.

*Low Battery 
NC, C, NO

Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally
energized when DC power is present. Contact rating 1 amp @ 120VAC / 28VDC.
Low battery threshold:
12VDC output threshold set @ approximately 10.5VDC, 
24VDC output threshold set @ approximately 21VDC.

–  BAT +

Stand-by battery connections. Maximum charge rate 0.5 amp.

*Note: Supervised models only

PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module:

Terminal Legend

Function/ Description

PD4/PD4CB PD8/PD8CB

PD16W/PD16WCB

1P to 4P

1P to 8P

1P to16P

Positive DC power outputs.

1N to 4N

1N to 8N

1N to 16N

Negative DC power outputs.