5.  Measure output voltage before connecting devices. This helps avoiding potential damage.
 

Keep power-limited wiring separate from non power-limited wiring (220VAC, 50/60Hz Input, 

 

Battery Wires). Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. 

 

Shut branch circuit power before installing or servicing equipment. 

 

There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.

6.  Slide [Power ON/OFF] switch t o OFF position.
7.  Connect devices to be powered:
 

a.  For Power Supply Board connect to the terminals marked [– DC +]. 

 

b. For Power Distribution Module(s) connect devices to be powered to the terminal pairs 1 to 4 marked  

 

  [1P & 1N] through [4P & 4N] (Fig. 3, pg. 6), 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 4, pg. 6), 

  or 1 to 16 marked [1P & 1N] through [16P & 16N] (Fig. 5, pg. 6), carefully observing correct polarity.
 

Note: Power switch is used to disconnect the L (HOT) terminal from the rest of the board (Fig. 1a, pg. 4, 

 

Fig. 2a, pg. 5).

 

When servicing the unit, AC mains should be removed.

8.  When using stand-by batteries, they must be lead acid or gel type. 
 

Connect battery to the terminals marked [– BAT +] (battery leads included).

 

Note: When batteries are not used, a loss of AC will result in the loss of output voltage.

For supervised models only:
9.  Connect appropriate signaling notification devices to AC Fail and Low Bat supervisory relay outputs 
 

marked [NC, C, NO] (Fig. 1b, pg. 4 or Fig. 2b, pg. 5).

10. Slide [Power ON/OFF] switch to ON position.

LED Diagnostics:

Power Supply Board

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Power Distribution Module

Green

Power Distribution Module Status

ON

Normal operating condition.

OFF

No Power Output.

Terminal Identification:

Power Supply Board:

Terminal Legend

Function/Description

L, G, N

Connect 220VAC to these terminals: L to Hot, N to Neutral.

– DC +

24VDC @ 10A continuous output.

*AC FAIL 
NC, C, NO

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. 
Relay normally energized when AC power is present. 
Contact rating 1A @ 120VAC / 28VDC.

*Low Battery 
NC, C, NO

Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally
energized when DC power is present. Contact rating 1A @ 120VAC / 28VDC.
Low battery threshold:
24VDC output threshold set @ approximately 21VDC.

– BAT +

Stand-by battery connections. Maximum charge rate 0.7A.

*Note: Supervised models only

PD4/PD4CB/PD8/PD8CB/PD16W/PD16WCB - Power Distribution Module:

Terminal Legend

Function/Description

PD4/PD4CB

PD8/PD8CB

PD16W/PD16WCB

1P to 4P

1P to 8P

1P to16P

Positive DC power outputs.

1N to 4N

1N to 8N

1N to 16N

Negative DC power outputs.

Содержание SMP10C24X220 Series

Страница 1: ...X220 SMP10PMC24X220 Single Output SMP10PM24P4220 Four 4 Fuse Protected Outputs SMP10PM24P8220 Eight 8 Fuse Protected Outputs SMP10PM24P16220 Sixteen 16 Fuse Protected Outputs SMP10PM24P4CB220 Four 4 P...

Страница 2: ...x 122 BTU Hr System AC input VA requirement 310 5VA Mechanical Enclosure Dimensions H x W x D approx 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm Accommodates up to two 2 12VDC 7AH batteries Installati...

Страница 3: ...dels only 9 Connect appropriate signaling notification devices to AC Fail and Low Bat supervisory relay outputs marked NC C NO Fig 1b pg 4 or Fig 2b pg 5 10 Slide Power ON OFF switch to ON position LE...

Страница 4: ...to the presence of important operating and maintenance servicing instructions in the literature accompanying the appliance CAUTION To reduce the risk of electric shock do not open enclosure There are...

Страница 5: ...able 12VDC Stand by Battery Optional Rechargeable 12VDC Stand by Battery L 5A 250V OFF ON LOW BAT NC C NO NC C NO AC FAIL BAT DC AC DC Board 115VAC power mains Di Optio 12VD Optional Rechargeable 12VD...

Страница 6: ...UTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED DC Output to devices From Power Supply Board Factory Installed ON OFF SW1 Used on PTC Models Power Distribution Module s common outputs protec...

Страница 7: ...SMP10C24X220 Series 7 Notes...

Страница 8: ...s BC300 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm Enclosure accommodates up to two 2 12VDC 7AH batteries Also available to accommodate up to two 2 12VDC 12AH batteries please contact Altronix 1 40 3...

Отзывы: