ReServ1

- 3 -

Stand-by Specifications:

Terminal Identifications:

OLS120 Power Supply/Charger Board

ReServ1B Circuit Board

LED Diagnostics:

OLS120 Power Supply/Charger Board

ReServ1B Circuit Board

Stand-by Battery

4 amp (100VA) Load at 24VAC and/or 12VDC max.

2 - 12VDC/7AH

45 minutes

2 - 12VDC/12AH

90 minutes

Terminal Legend

Function/Description

L, G, N

Connect 115VAC to these terminals: L to Hot, N to Neutral, G to ground (if used).

+ DC ---

24VDC @ 4 amp continuous output.

AC Fail
NO, C, NC

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. Relay normally
energized when AC power is present. Contact rating 1 amp @ 28VDC.

Low Battery
NO, C, NC

Used to indicate low battery condition, e.g. connect to alarm panel. NO, C, NC Relay normally
energized when DC power is present. Contact rating 1 amp @ 28VDC.
Low battery threshold:
24VDC output threshold set @ approximately 21VDC.

---     BAT +

Stand-by battery connections. Maximum charge rate .5 amp.

Terminal Legend

Function/Description

Input +  ---

24VDC from OLS120 power supply/charger.

24VAC - N, P 1-8

24VAC outputs.

12VDC - + 1 --    to + 4 --  

12VDC outputs.

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC, Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

LED

LED State

Description

24VAC Output
1-8

ON

Normal operating condition.

OFF

Loss of output power.

12VDC Output
1-4

ON

Normal operating condition.

OFF

Loss of output power.

Low Voltage
Input

ON

Voltage input is low.

OFF

Normal operating condition.

Shutdown

ON

No Power. Batteries are discharged.

OFF

Normal operating condition.

Содержание ReServ1

Страница 1: ...el and secure Mark the position of the lower two holes Remove the enclosure Drill the lower holes and install the two fasteners Place the enclosure s upper keyholes over the two upper screws Install the two lower screws and make sure to tighten all screws Enclosure Dimensions pg 4 Secure enclosure to earth ground 2 Slide power switch to OFF position Fig 1a pg 2 3 Connect AC power mains to terminal...

Страница 2: ...W BATTERY SHUTDOWN Protected outputs Common outputs OUT1 OUT2 OUT3 OUT4 24 VAC outputs 1 2 3 4 5 6 7 8 N P IC4 12VDC Aux Out Input 24VDC Fig 1a Fig 1b Fig 1c Fig 1d Fuse Replacement 1 Before replacing fuses slide switch to OFF position 2 Replace AC outputs fuses F1 or F4 with fuses rated 3 amp 32V Replace DC outputs fuses F1 or F4 with fuses rated 3 amp 32V Automotive Blade Fuse OUT1 OUT2 OUT3 OUT...

Страница 3: ...o alarm panel NO C NC Relay normally energized when DC power is present Contact rating 1 amp 28VDC Low battery threshold 24VDC output threshold set approximately 21VDC BAT Stand by battery connections Maximum charge rate 5 amp Terminal Legend Function Description Input 24VDC from OLS120 power supply charger 24VAC N P 1 8 24VAC outputs 12VDC 1 to 4 12VDC outputs Red DC Green AC Power Supply Status ...

Страница 4: ... York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix com Made in U S A IIReServ1 Rev 120108 B26I MEMBER 5 10 6 5625 3 25 3 25 5 10 5 10 3 25 1 00 10 50 1 00 1 00 1 00 1 40 1 20 1 40 1 20 0 75 0 75 11 00 12 50 3 25 0 9375 0 9375 1 40 4 85 4 85 1 40 1 20 Bottom Top Right Left Enclosure Dimensions 13 5 H x 13 W x 3 25 D ...

Отзывы: