background image

- 4 - 

ReServ

LED Diagnostics (cont’d):

ReServ Board

LED

LED State

Unit Status

Output 

LEDs

ON

------

Normal operating condition.

------

OFF Loss of 24VAC and/or 12VDC output power.

Low Battery

ON

------

Stand-by batteries are low.

------

OFF Normal operating condition.

Shutdown

ON

------

Loss of 24VAC and/or 12VDC output power. Discharged stand-by battery.

------

OFF Normal operating condition.

Audio Signal Diagnostics:

ReServ Unit

Audio Signal

Unit Status

Single Periodic Beep

AC Fail.

Double Periodic Beep Low Battery or No Battery.

Terminal Identification:

Power Supply Board

Terminal

Legend

Function/Description

L, G, N

Connect 115VAC 60Hz to these terminals: L to hot, N to neutral.

--  DC +

24VDC non power-limited output. 

AC FAIL 

NO, C, NC

Form “C” dry contacts used to instantaneously signal the loss AC to local annunciation devices, with 

AC present terminals marked NO and C are open, NC and C are closed. When loss of AC occurs ter-

minals marked NO and C are closed, NC and C are open.

BAT FAIL 

NO, C, NC

Form “C” dry contacts used to signal low battery voltage or loss of battery voltage. Under normal con-

ditions terminals marked NO and C are open, NC and C are closed. During a trouble condition termi-

nals marked NO and C are closed, and NC and C are open.

--  BAT +

Stand-by battery connections. Maximum charge current 0.7A.

ReServ Board

Terminal

Legend

Function/Description

Input

---  24VDC +

24VDC input from power supply board.

N, P 1-16

24VAC and/or 12VDC outputs. 

The lightning flash with arrow head symbol within an equilateral triangle is intended to alert the user to the

presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may be of sufficient

magnitude to constitute an electric shock.

The exclamation point within an equilateral triangle is intended to alert the user to the presence of important 

operating and maintenance (servicing) instructions in the literature accompanying the appliance.

CAUTION: To reduce the risk of electric shock do not open enclosure.

There are no user serviceable parts inside. Refer servicing to qualified

service personnel. 

Содержание ReServ1

Страница 1: ...A total supply current 24VAC and 2A total supply current 12VDC PTC protected power limited outputs ReServ2 Sixteen 16 true sine wave regulated 24VAC outputs 4A total supply current PTC protected power limited outputs ReServ3 Sixteen 16 regulated 12VDC outputs 8A total supply current PTC protected power limited outputs Rev 082510 More than just power ...

Страница 2: ...ies 4A 100VA max load at 24VAC Two 2 12VDC 7AH 45 minutes Two 2 12VDC 12AH 90 minutes ReServ3 Stand by Batteries 8A 100VA max load at 12VDC Two 2 12VDC 7AH 45 minutes Two 2 12VDC 12AH 90 minutes When using 12AH batteries or larger a separate UL Listed battery enclosure must be installed Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods Out...

Страница 3: ...s devices to the terminals marked P 1 4 N 1 4 Fig 1 pg 5 Connect 24VAC cameras devices to the terminals marked 5 16 Fig 1 pg 5 ReServ2 Connect 24VAC cameras devices to the terminals marked 1 16 Fig 2 pg 6 ReServ3 Connect 12VDC cameras devices to the terminals marked P 1 16 N 1 16 Fig 3 pg 7 7 Connect batteries to the terminals marked BAT Figs 1 3 pg 5 7 Use two 2 12VDC batteries connected in serie...

Страница 4: ...osed NC and C are open BAT FAIL NO C NC Form C dry contacts used to signal low battery voltage or loss of battery voltage Under normal con ditions terminals marked NO and C are open NC and C are closed During a trouble condition termi nals marked NO and C are closed and NC and C are open BAT Stand by battery connections Maximum charge current 0 7A ReServ Board Terminal Legend Function Description ...

Страница 5: ...arately Supervised Non power limited CAUTION Risk of explosion if battery is replaced by an incorrect type Dispose of used batteires according to the instructions Non power limited 5A 250V Unswitched 115VAC 60Hz 3 5A power mains non power limited 24VAC Power Limited Outputs 12VDC Power Limited Outputs Note Two 2 12VDC rechargeable batteries connected in series required power limited AC DC ...

Страница 6: ...able Battery order separately Supervised Non power limited CAUTION Risk of explosion if battery is replaced by an incorrect type Dispose of used batteires according to the instructions Non power limited 5A 250V Unswitched 115VAC 60Hz 3 5A power mains non power limited Note Two 2 12VDC rechargeable batteries connected in series required power limited 24VAC Outputs AC DC ...

Страница 7: ...rect type Dispose of used batteires according to the instructions Non power limited 5A 250V Unswitched 115VAC 60Hz 3 5A power mains non power limited Note Two 2 12VDC rechargeable batteries connected in series required 12VDC Power limited Outputs P N 3 OUT 4 3 4V adjust P N 5 OUT 6 5 6V adjust P N 7 OUT 8 7 8V adjust P N 9 OUT 10 9 10V adjust P N 11 OUT 12 11 12V adjust P N 13 OUT 14 13 14V adjust...

Страница 8: ...onix com Lifetime Warranty Made in U S A IIReServ F15P 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm 1 0 25mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 0 75 19mm 0 75 19mm 0 9375 24mm 0 9375 24mm 11 0 279mm 12 5 318mm Enclosure Dimensions H x W x D approximate ...

Отзывы: