Fig. 1
Fig. 1a
Fig. 1b
Fig. 1c
Fig. 1d
set for 28VAC.
XFMR*
ALTRONIX CORP.
BROOKLYN, NY 11220
MADE IN USA
XFMR*
N
P
S
AC Power
LED's
AC Power
LED's
AC Power
LED's
AC Power
LED's
Divider
Removable Terminal
Block
(Green Wire
Earth GND)
Fuse
Fuse
S
P
N
S
P
N
24VAC Output
(Factory Set)
28V
AC (Black)
24V
AC (Y
ellow)
COM (Brown)
28V
AC (Black)
24V
AC (Y
ellow)
COM (Brown)
28VAC Output
Illuminated
Power Disconnect
Circuit Breaker with
manual reset
P
N
S
Strain Relief
Line Cord
Fig. 1e
Class 2 Rated Power Limited Outputs.
Except
for
R2416UL,
R2416300UL,
R2416600UL
and
R2416ULCB
when
PTC1
Used
on PTC
Models
5.
Set
power
disconnect
circuit
breaker
to
RESET
(ON)
position
(Fig. 1d, pg. 3).
6. Measure output voltage before connecting devices. This helps avoid potential damage.
All terminals with common suffix (P) “1P, 2P...” are the same polarity.
7. Set power disconnect circuit breaker to OFF position (Fig. 1d, pg. 3).
8. Connect devices to removable terminal blocks marked [1P & 1N through 16P & 16N] (Fig. 1a, pg. 3).
When wiring is completed on terminal blocks they can be locked down by tightening screw flanges.
9.
Upon
completion
of
wiring,
set
power
disconnect
circuit
breaker
to
RESET
(ON)
position
(Fig. 1d, pg. 3).
10.
Green
power
LEDs
on
faceplate
will
illuminate
when
power
is
present.
When
an
output
is
in
a
trouble
condition
(blown
fuse
or
tripped
PTC)
the
corresponding
LED
will
not
be
illuminated
(Fig. 1, pg. 3).
a. Blown
fuse
(R2416UL,
R2416300UL
&
R2416600UL)
- Set
power
disconnect
circuit
breaker
on
back
of unit to the OFF position (Fig. 1e, pg. 3).
Remove
front
faceplate
to
access
fuses.
Replace
with
fuses
rated
@
3.5A/250VA
(Altronix
model
#
Fuse1).
b.
Tripped
PTC
(R2416ULCB,
R2416300ULCB
&
R2416600ULCB)
- To
reset
PTC,
set
power
switch
on
back
of unit to the OFF position. After approximately 30 secs. set power disconnect circuit breaker to
the
ON
(RESET)
position
(Fig. 1d, pg. 3).
11. Illuminated power disconnect circuit breaker with manual reset:
OFF position - Switch not Illuminated. Outputs not powered.
RESET
(ON)
position
- Circuit
breaker
illuminated.
Outputs
powered.
Circuit
breaker
tripped
- Circuit
breaker
is
not
Illuminated.
Power
LEDs
on
faceplate
are
not
illuminated.
Outputs not powered.
To
reset
circuit
breaker
set
power
disconnect
circuit
breaker
to
RESET
(ON)
position
(Fig. 1d, pg. 3).
R2416ULseries
- 3