Altronix PT72724 Скачать руководство пользователя страница 2

Overview:

Model PT2724 is an extremely versatile two channel 365 Day 24 Hour Timer / Controller designed to support a wide range of appli-
cations. Such applications include: Home and Building Automation, Security, Access Control, Lighting Control, Etc.
The PT2724 is equipped with two independently controlled form “C” relay contact that provides many latching and/or momentary
operations during a program schedule of your choice. The 
EE-Prom memory allows for programming of unit prior to/or during field installation. Events may be set for single or multiple oper-
ations on a daily and/or weekly schedule. The block programming feature enables repeating an event on any combination of consec-
utive days. PT2724 will compensate for daylight savings time if desired. It automatically adjusts for leap year and individually
selected holiday exceptions can be programmed to over-ride regularly scheduled events. 

Specifications:

• 12 to 24 volts AC or DC operation
• Standby current: 10mA (relay off) 50mA for each channel (relay on).
• Two (2) form “C” relay contacts are rated 

10amp @120VAC/28VDC.

• Tandem relay mode (converts 2 SPDT contacts to 1 DPDT contact).
• EE-Prom program memory protected against power loss.
• Accurate crystal controlled clock.
• Momentary and/or Latching Events.
• 50 individually programmed daily/weekly events per channel.
• Block programming capacity can accommodate a total of 350 events per week per channel.
• 10 programmable Holiday dates per channel.
• “First man in” option.
• Alphanumeric LCD display simplifies programming.
• Standard or Daylight Savings Time settings.
• Automatic compensation for leap year.
• Built-in charger for 12VDC sealed lead acid or gel type batteries (Max charge current 100mA).
• Lithium battery backup maintains clock (optional).
• User friendly programming.
Board dimensions: 5.25” x 3.5” x 1.5”

Installation Instructions:

1. Mount PT2724A in desired location / enclosure.

Carefully Review:
Basic Operation

(pg. 2)

Terminal Identification Table

(pg. 3)

Push Button Layout and Description

(pg. 3-4)

Programming Instructions

(pgs. 4-7)

2. Connect 12 to 24 Volts AC or DC to terminals marked [+ DC --   ~AC~  ]. (when using DC carefully observe polarity).
3. Connect 12VDC battery (optional) to terminals marked [+ BAT --   12VDC].
4. Insert lithium battery (optional/not included. Order part LB2032) in battery 

holder as shown in fig. 1 pg. 3. with the + positive side facing up.

5. Connect devices to be controlled to the dry relay outputs of either Channel A or Channel B.

Note: It is important when connecting DC powered electromechanical devices such as Mag Locks, Electric Strikes, Bells, Relays,
etc. to  install a catch diode across the pos (+) and neg (-) terminals of the device. Connect diode as close to the device as 
possible with the banded side facing the pos (+) terminal. This will reduce the possibility of interference.

6. Program clock and desired event schedule (see programming instructions pg. 4-7).

Basic Operation:

PT2724 controls two independently operated dry form “C” relays. Relays can be programmed to: turn on (latch), turn off (release
latch) or pulse (momentary toggle) at a specified time and day (this is referred to as an event). Events are programmed via the push
buttons and LCD display. Events may be programmed to occur on any day of the week at any time. In addition, events may be pro-
grammed as a block event which repeat at a specific time on two (2) or more consecutive days (i.e. MO-FR,  SU-TH, etc) Multiple
combinations of individual and block events may be programmed. Holiday exceptions are individually selected by date and will
over-ride all regularly scheduled events.
The four (4) output relay modes consist of:
Relay OFF - De-energizes the relay until a relay ON event is detected 
Relay ON - Energizes the relay until a relay OFF event is detected. 

PT2724 - Two Channel 

365 Day 24 Hr. Timer/Controller

IIPT2724-Rev. 060500
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.

2

Содержание PT72724

Страница 1: ...PT72724 365 Day 24 Hr Timer Controller Installation Programming Guide for ...

Страница 2: ...esired location enclosure Carefully Review Basic Operation pg 2 Terminal Identification Table pg 3 Push Button Layout and Description pg 3 4 Programming Instructions pgs 4 7 2 Connect 12 to 24 Volts AC or DC to terminals marked DC AC when using DC carefully observe polarity 3 Connect 12VDC battery optional to terminals marked BAT 12VDC 4 Insert lithium battery optional not included Order part LB20...

Страница 3: ...bserve polarity AC BAT 12VDC standby battery input battery leads provided 12VDC FM When this terminal is connected to DC neg the First Man in feature is enabled Both relays will remain in their present position until this connection is terminated At that time relays will resume normal operation and latest scheduled events will occur PT 2724 SET ENTER UP DWN FM BAT 12VDC DC AC ALTRONIX CORP BKLYN N...

Страница 4: ...NTER to SET EVENT Depress ENTER A01 OFF SU 00 00 Note A01 indicates Channel A event 01 When cursor appears you are able to scroll through events Depress ENTER until the flashing cursor appears under OFF relay function position in display Now select type of operation required by scrolling using the UP and DWN push buttons until either ON Relay ON latching mode OFF Relay OFF latching mode PL Relay P...

Страница 5: ...hrough Sunday depress WE followed SU 2 Daylight Savings Programming The cursor will appear under DS auto clock adjust daylight savings mode in display To change mode depress UP or DWN once ST clock does not adjust standard time mode will appear in display Depress ENTER to accept correct selection Note Select DS for areas that observe daylight savings or ST for areas that don t observe daylight sav...

Страница 6: ...T until ENTER to SET EVENT Depress ENTER A01 ON TU 00 00 Now scroll using UP and DWN push buttons to the event you wish to delete depress ENTER to move flashing cursor under relay option then depress UP and DWN push buttons until DIS is displayed depress ENTER to confirm G Delete All Events This will delete all previously programmed events Depress SET until ENTER to CLR MEM Depress ENTER CLEAR MEM...

Страница 7: ...th Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 web site www altronix com e mail info altronix com Lifetime Warranty Made in U S A MEMBER Event Relay Day Block Holiday Dates Event Type Customer Event Log ...