background image

 

PT2724 

- 5 -

 Depress 

ENTER

 until the flashing cursor appears under OFF (relay function) position in display. 

  Now select type of event required, by scrolling using the 

UP

 and 

DWN

 push buttons until either:

 

ON - Relay ON (latching mode), OFF - Relay OFF (latching mode), PL - Relay Pulse ( momentary)

  appears in display. Depressing 

ENTER

 will make selection.

  When selecting the pulse mode, PL01 will appear in the display. It is now necessary to assign the length 
  of time (duration of relay activation). The pulse can range in length from 1 second minimum to 15 seconds 
  maximum and is selected by using 

UP

 or 

DWN

 push buttons, then depressing 

ENTER

 to accept.

 

Note: If pulse duration is not selected, relay output defaults to 1 second.

  Next, select individual day of the week and time (military) by scrolling using 

UP

 and 

DWN

 push buttons 

  and depress 

ENTER

 to accept. You may continue to program events by repeating the previous steps or exit 

  programming by depressing 

SET

.

 

Note: When programming additional events, it is necessary to select the next consecutive event number 

  following the last event program to continue.
 

Note: When it is required to have the same event repeated on two (2) or more consecutive days of the 

  week (Block Programming), the event must be programmed as a block by selecting 

BK

 in the day field.

 

Note: To program the consecutive days of the week refer to Setting Block Event (weekly repeat) and 

 

Daylight Savings Time

 - section C1 below.

  2. Adding Events
 Depress 

SET

 until 

 

appears on display.

 Depress 

ENTER

  

 

appears on display.

Depress 

ENTER

. If the event is not programmed, the cursor will move to the OFF (relay function) position. 

If the event is programmed, the cursor will move to the position and the programmed information of the event 
will be displayed. At this point depress the 

UP

 button to step up through the programmed events. When an 

unprogrammed event is reached, the cursor will move to the OFF (relay function position). At this point refer to 
setting events or setting holiday events.

C.  Setting Block Events (weekly repeat) and Daylight Savings Time:
 

Select channel A or B by moving slide switch SW3 to appropriate position.

 Note: 

Channel cannot be changed in the middle of programming events. To change channelsyou must exit 

  programming then change channel switch position then enter program mode again.

 Depress 

SET

 until 

appears on display.

 Depress 

ENTER

will appear on display.

  1. Block Event Programming
    Flashing cursor will appear at the location of the first day of the week desired. Depress 

UP

 and 

DWN

 

    to select day. Depress 

ENTER

 to confirm selection, then cursor will appear at the location of the last 

    day of the week desired. Depress 

UP

 and 

DWN

 

to select day. Depress 

ENTER

 to confirm selection. 

    1) Monday through Thursday depress 

MO

 followed by 

TH

.

    2) Wednesday through Sunday depress 

WE

 followed 

SU

.

  2. Daylight Savings Programming
    The cursor will appear under DS (auto clock adjust daylight savings mode) in display. To change mode 
  depress 

UP

 or 

DWN

 once ST (clock does not adjust standard time mode) will appear in display. 

  Depress 

ENTER

 to accept correct selection.

  

Note: Select 

DS

 for areas that observe daylight savings or 

ST

 for areas that don’t observe 

  daylight 

savings.

>

 A01   OFF

BK 00:00

>

ENTER to

SET EVENT

>

A01   OFF

SU 00:00

ENTER to

SET BK

A=SA/SU

TIME=DS

Содержание PT2724

Страница 1: ...More than just power TM Rev 020317 Two 2 Channel 365 Day 24 Hr Timer Controllers Models include PT2724 Timer module PT2724E Timer module in enclosure Installation Guide ...

Страница 2: ...oliday dates per channel First man in option Features cont d Standard or Daylight Savings Time settings Automatic compensation for leap year Visual Indicators Alphanumeric LCD display simplifies programming Battery Backup Built in charger for 12VDC sealed lead acid or gel type batteries Max charge current 100mA Optional lithium battery backup maintains clock Order Altronix part LB2032 Mechanical P...

Страница 3: ... an existing programmed event Pulse Momentarily energizes the relay for a selectable time period of 1 sec to 15 secs Time is displayed in 24 hr military format Terminal Identification Table Terminal Legend Function Description NO C NC CH A NO C NC CH B Dry Contact outputs used to switch controlled devices When these relays are energized ON the NC and C terminals are open and the NO and C terminals...

Страница 4: ...ess ENTER to scroll until flashing cursor appears under DS daylight savings mode in display To change mode depress UP or DWN until ST standard time mode will appear in display Depress ENTER to accept correct selection Note The flashing cursor denotes location of data entry selection to be made If an entry was made in error or requires changing depress SET to backspace make the correct selection an...

Страница 5: ...f the event is not programmed the cursor will move to the OFF relay function position If the event is programmed the cursor will move to the position and the programmed information of the event will be displayed At this point depress the UP button to step up through the programmed events When an unprogrammed event is reached the cursor will move to the OFF relay function position At this point ref...

Страница 6: ...nel A or B by moving slide switch SW3 to appropriate position Note Channel cannot be changed in the middle of programming events To change channels you must exit programming then change channel switch position then enter program mode again It is now necessary to assign these holiday events specific calendar dates which they are to occur on Depress SET until appears on display Depress ENTER appears...

Страница 7: ...ON and Channel B is set to OFF The ON command will override the OFF and both relays will remain ON PT2724 Board Dimensions L x W x H approximate 5 25 x 3 6 x 1 133 4mm x 91 4mm x 25 4mm 5 25 133 4mm 3 6 91 4mm 0 14 3 6mm 0 14 3 6mm 4 9 124 5mm 2 4 61mm Ø0 156 3 9mm PT2724E Enclosure Dimensions H x W x D approximate 8 5 x 7 5 x 3 5 215 9mm x 190 5mm x 88 9mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1...