Voltage Output Selection Table:

Output VDC

Switch Position

Max. Load DC

12VDC

SW1 - ON

2.5A

24VDC

SW1 - OFF

2.5A

LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output. Short circuit or thermal overload condition.

OFF

OFF

No DC output. Loss of AC. Discharged or no battery present. 

 

Terminal Identification:

Terminal Legend

Function/Description

L, G, N

Connect 115VAC/230VAC to these terminals: L to Hot, N to Neutral, G to ground.

– DC +

12VDC / 24VDC @ 2.5A continuous supply current. 

AC FAIL 

NC, C, NO

Used to notify loss of AC power, e.g. connect to audible device or alarm panel. 

Relay normally energized when AC power is present. 

Contact rating 1A @ 115VAC / 28VDC.

Low Battery 

NC, C, NO

Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally

energized when DC power is present. Contact rating 1A @ 115VAC / 28VDC.

Low battery threshold: 

 

12VDC output threshold set @ approximately 10.5VDC. 

 

24VDC output threshold set @ approximately 21VDC.

– BAT +

Stand-by battery connections. Maximum charge rate 0.5A.

OFF - 24V

ON - 12V

ON

OFF    ON

L

G

N

LOW BAT

NC    C   NO     NC  C   NO

AC FAIL

--- BAT +

---  DC  +

AC

DC

5A 250V