NetWaySP1BT Series Powered

   Installation  Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes 

and authorities having jurisdiction. All units should be installed by a trained service personnel.

   Installation:

1.  Remove backplane from enclosure prior to drilling. Do not discard hardware. 

 

Note:

 Make sure that hardware will not interfere with components of the circuit board.

2.  Mark and drill desired inlets on the enclosure to facilitate wiring

Maximum NEMA type 4X rated fittings 

 

to be used are 0.5”. Follow manufacturer’s specifications for the appropriate size opening. 

 

Note:

 Inlets for conduit fittings should only be made on the bottom of the enclosure. 

 

To facilitate wire entry utilize weather-tight NEMA rated connectors 

(supplied)

, bushings, and cable.

3.  Clean out the inside of enclosure before remounting circuit boards/backplane.

4.  Mounting NEMA4/4X rated enclosure 

(Enclosure Dimensions, pg. 9, 10)

:

 

Wall mount:

 

Mount unit in desired location. Mark and drill holes to line up with the top and bottom 

 

 

   

hole of the enclosure flange. Secure enclosure with appropriate fasteners (e. g. screws 

 

 

   

and anchors; bolts and locking nuts, etc.) that are compatible with mounting surface and 

 

 

   

are of sufficient length/construction to ensure a secure mount 

(Fig. 6, pg. 8)

.

 

Pole Mount:

 

Refer to Fig. 7 - 11, pg. 8

5.  Mount backplane in enclosure with hardware.

Power Connection:

Before powering unit, set input voltage selection switch to proper Input Voltage position 

(Fig. 2a, pg. 5, Fig. 3a, pg. 6). Units are factory set for 115VAC.

1.  Connect AC power from overcurrent protective device circuit breaker

 

(20A @ 115VAC, 60Hz or 16A @ 230VAC, 50/60Hz) to the terminals marked [L, N] on power supply 

 board 

(Fig. 2, 3, pg. 5, 6)

. Connect ground lug to earth or green branch wire on backplane (12AWG min.).

 

Use 14AWG or larger for all power connections (Battery, DC output, AC input). 

 

Keep power-limited wiring separate from non power-limited wiring by utilizing separate knockouts/

 

inlets. Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing 

 

equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified 

 

service personnel.

3. 

Battery Backup

 (if desired): Connect four (4) 12VDC batteries wired in series to terminals marked 

 

[– BAT +] 

(Fig. 3, pg. 5)

, carefully observing polarity. 

 

When use of stand-by batteries is desired, they must be lead acid or gel type. 

 

Note:

 When batteries are not used, a loss of AC will result in the loss of output voltage.

Input/Data Connections:

1.  Connect structured cable from port marked [Data Port] on NetWaySP1BT to a PoE midspan/endspan 

 

(Fig. 1, pg. 4)

.

2.  Connect fiber optic cable to a fiber SFP module. Connect the module to the port marked [SFP] on the 

 

NetWaySP1BT. Connect the other end of fiber cable to an SFP module of a remote device. 

 

SFP LED will illuminate indicating data connection 

(Fig. 1, pg. 4)

.

3.  Using 4-pair CAT5e or higher cable connect PoE load device to be powered to the port marked

 

[802.3bt Output] on NetWaySP1BT. After authentication and classification have been established, 

 

[PoE Signal] LED will illuminate indicating PoE presence.

Ethernet Data Port

Yellow LED

10/100 Mbps

Green LED 1000 Mbps

IEEE 802.3af, 802.3at and 802.3bt

compliant port rated up to 90W max

48VDC to 56VDC

Input

--    +

SFP LED Indicates

data connection

PoE LED indicates PoE present

One (1) Gb SFP port

for Fiber

48-56VDC

–  Input +

802.3bt

Output

Data

Port

Fiber

Signal

PoE

Signal

SFP

Fig. 1

Содержание NetWaySP1BTWP

Страница 1: ...er Injector with Integral Power NEMA4 4X rated outdoor enclosure Accommodates up to four 4 12VDC 4AH batteries Installation Guide NetWaySP1BTWP Series 802 3bt Media Converter Injectors with Integral P...

Страница 2: ...ltronix SFP Modules pg 3 Installation Instructions pg 4 Installation pg 4 Power Connection pg 4 Input Data Connections pg 4 NetWaySP1BTWP pg 5 NetWaySP1BTWPX pg 6 Typical Application pg 7 Technical Sp...

Страница 3: ...hen AC fails Environmental Refer to Environmental Conditions on page 5 LED Indicators Refer to Fig 4 Pg 4 Yellow and Green LEDs RJ45 jacks Yellow left LED 10 100 Mbps Green right LED 1000 Mbps Green P...

Страница 4: ...or 16A 230VAC 50 60Hz to the terminals marked L N on power supply board Fig 2 3 pg 5 6 Connect ground lug to earth or green branch wire on backplane 12AWG min Use 14AWG or larger for all power connec...

Страница 5: ...BAT To stand by batteries 115 230VAC Input 115VAC 230VAC 115VAC L G N Ground NetWaySP1BT 802 3bt Converter Injector Input 48 56VDC Output IEEE 802 3bt 90W 48 56VDC Input 802 3bt Output Data Port Fiber...

Страница 6: ...WaySP1BT 802 3bt Converter Injector Input 48 56VDC Output IEEE 802 3bt 90W 48 56VDC Input 802 3bt Output Data Port Fiber Signal PoE Signal SFP Optional rechargeable 12VDC 4AH battery Optional recharge...

Страница 7: ...liant output port rated up to 90W max Input Power Requirements 115VAC 60Hz 2 5A or 230VAC 50 60Hz 1 3A Indicators Yellow and Green LEDs RJ45 jacks IP Link status 10 100 1000 Base T active PoE Green LE...

Страница 8: ...height of the top Pole Mount bracket is achieved tighten the straps down by sliding open end of the strap through the locking mechanism on the strap then tighten the screw with flat head screwdriver o...

Страница 9: ...S 0 375 9 5mm PADLOCK EYE 0 32 8 1mm MOUNTING HOLE TYP 4 PLACES 8 00 203 2mm STAINLESS STEEL PIANO HINGE 10 75 273 1mm 10 00 254mm 8 25 209 6mm 10 25 260 4mm 12 00 304 8mm 13 50 342 9mm 10 32 X 0 25 6...

Страница 10: ...162 8mm 10 32 X 0 250 BRASS INSERT 4 PLCS 14 54 369 3mm 16 74 425 2mm 0 125 3 2mm 14 25 362mm 14 00 355 6mm 12 23 310 6mm 17 53 445 3mm 16 00 406 4mm 1 67 42 4mm 5 00 127mm 16 73 425mm 15 3 388 6mm 6...

Страница 11: ...NetWaySP1BT Series Powered 11 Notes...

Страница 12: ...not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Made i...

Отзывы: