NetWaySP1BT Series
- 7 -
Wall Mount Installation:
1- Place unit at desired location and secure with mounting
screws
(not included) (Fig. 5, pg. 7).
Fig. 5
Pole Mounting Using Optional Pole Mount Kit PMK1:
This installation should be made by qualified service personnel . This product contains no serviceable parts . PMK1
outdoor pole mount kits is designed to simplify the installation of Altronix outdoor rated power supplies and acces-
sories housed in models WP1, WP3 and WP4 NEMA rated enclosures . PMK1 can be mounted on 2” to 8” (50 .8mm
to 203 .2mm) diameter round or 5” (127mm) square poles . Brackets are designed for use with the Wormgear Quick
Release Straps (two included) .
1 . Thread one (1) wormgear quick release strap through the slots on the back of a mounting bracket
(Fig. 6, pg. 7)
.
2 . Once the desired height of the top Pole Mount bracket is achieved, tighten the straps down by sliding open
end of the strap through the locking mechanism on the strap, then tighten the screw with
flat head screwdriver or 5/16” hex socket driver
(Fig. 7, pg. 7 and Fig. 9, pg. 7)
.
3 . Attach the bottom bracket to the enclosure by inserting bolts through the flange of the enclosure and into the
bracket, tightening bolts with a 7/16” hex socket
(Fig. 8, pg. 7)
.
4 . Thread the second wormgear quick release strap through the slots on the back of the bottom mounting
bracket
(Fig. 9, pg. 7)
.
5 . Mount enclosure onto the top bracket by inserting bolts through flange of the enclosure and into the bracket,
tightening bolts with a 7/16” hex socket
(Fig. 8, pg. 7)
.
6 . Tighten the straps of the bottom bracket down by sliding the open end of the strap through the locking
mechanism on the strap, then tighten screw with flat head screwdriver or 5/16” hex socket driver
(Fig. 7, 9, pg. 7)
.
7 . Clip excess straps .
Fig. 6
Fig. 7
Fig. 8
Fig. 9
Fig. 10
2” to 8”(50.8mm to 203.2mm)
diameter round pole
Fig. 10a
5” (127mm) square pole