Maximal Expandable Power Systems 

- 5 -

Power Supply Board Terminal Identification:

Terminal 
Legend

 Function/Description

L, G, N

Connect 115VAC 60Hz to these terminals: L to hot, N to neutral .

+ DC –

Refer to Maximal Series Configuration Chart, pg. 3. 

AC FAIL
NC, C, NO

Indicates loss of AC power . To meet with UL requirements it is mandatory to connect visual 
notification devices, connecting audible notification devices is optional . Relay normally 
energized when AC power is present . Contact rating 1A @ 28VDC . AC or brownout fail is 
reported within 1 minute of event .

BAT FAIL
NC, C, NO

Indicates low battery condition, e .g . connect to alarm panel . Relay normally energized when 
DC power is present . Contact rating 1A @ 28VDC . A removed battery is reported within 5 
minutes . Battery reconnection is reported within 1 minute .
Low battery threshold:
12VDC output threshold set @ approximately 10 .5VDC .
24VDC output threshold set @ approximately 21VDC .

+ BAT –

Stand-by battery connections . 
AL400ULXB2, AL600ULXB, and AL1012ULXB (Power Supply Board) maximum charge 
current is 0 .7A . AL1024ULXB2 (Power Supply Board) maximum charge current is 3 .6A .

Power Supply Board Stand-by Battery Specifications

Altronix
Model

Power Supply

Board

Battery

20 min. of

Backup

4 hr. of

Backup

24 hr. of

Backup

60 hr. of

Backup

Maximal11E
Maximal13E

AL400ULXB2

(Refer to Fig. 1a, 1b 

on pg. 5 for Switch 

[SW1] location 

and position)

12VDC/40AH*

N/A

4A

1A

300mA

24VDC/12AH

N/A

200mA

N/A

N/A

24VDC/40AH*

N/A

3A

1A

300mA

Maximal13E
Maximal33E
Maximal35E
Maximal37E

AL600ULXB

(Refer to Fig. 1a, 1b 

on pg. 5 for Switch 

[SW1] location

and position)

12VDC/40AH*

N/A

6A

1A

300mA

24VDC/12AH

N/A

200mA

N/A

N/A

24VDC/40AH*

N/A

6A

1A

300mA

Maximal35E
Maximal55E
Maximal75E

AL1012ULXB

(Factory set at 

12VDC)

12VDC/12AH

10A

Battery capacity 

for emergency 

stand-by at least 

20 mins .

N/A

N/A

Maximal37E
Maximal75E
Maximal77E

AL1024ULXB2

(Factory set at 

24VDC)

24VDC/12AH

8A

1 .5A

200mA

100mA

24VDC/65AH*

N/A

8A

1 .5A

500mA

* Note: Additional battery enclosure required (Figs. 3-7, pgs, 7-11).

Power Supply Board Output Voltage Settings:

Fig. 1

+  DC   

--- 

 

SW1

OFF - 24V

ON - 12V

ON

Fig. 1a - AL400ULXB2 / AL600ULXB Power Supply Board

Fig. 1b

ON

OFF - 24V

ON - 12V

Содержание Maximal11E

Страница 1: ...C or 24VDC 6A Power Supply 2 12VDC or 24VDC 6A Maximal37E Power Supply 1 24VDC 10A Power Supply 2 12VDC or 24VDC 6A Maximal75E Power Supply 1 12VDC 10A Power Supply 2 24VDC 10A Maximal13E Power Supply...

Страница 2: ...ation pg 5 Power Supply Board Stand by Battery Specifications pg 5 Power Supply Board Output Voltage Settings pg 5 NEC Power Limited Wiring Requirements for Maximal11E pg 7 NEC Power Limited Wiring Re...

Страница 3: ...6A 12VDC 6A 24VDC 6A 24VDC 6A 24VDC 6A Maximal35E AL1012ULXB AL600ULXB 2 6 1A 5A 250V 15A 32V AL1012ULXB 12VDC 10A 12VDC 6A 12VDC 10A 24VDC 6A Maximal37E AL1024ULXB2 AL600ULXB 2 7 9A 5A 250V 15A 32V A...

Страница 4: ...s to be powered to the terminals marked DC Fig 2 pg 6 6 For Access Control applications batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage When t...

Страница 5: ...AL600ULXB and AL1012ULXB Power Supply Board maximum charge current is 0 7A AL1024ULXB2 Power Supply Board maximum charge current is 3 6A Power Supply Board Stand by Battery Specifications Altronix Mod...

Страница 6: ...ttery Optional 12VDC Rechargeable Battery Optional 12VDC Rechargeable Battery Optional Ground Wire Line Earth Ground Neutral Line Neutral Input 115VAC 60Hz BAT FAIL L G N DC NO C NC NO C NC BAT AC FAI...

Страница 7: ...rent conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or F...

Страница 8: ...erent conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or...

Страница 9: ...require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable...

Страница 10: ...ire different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gaug...

Страница 11: ...erent conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or...

Страница 12: ...0 8mm 6 25 158 75mm 6 25 158 75mm 4 101 6mm 4 101 6mm 2 50 8mm 4 101 6mm 8 9 226 06mm 8 4 213 36mm 7 177 8mm 7 177 8mm 7 177 8mm 8 4 213 36mm 8 5 215 9mm 8 5 215 9mm 7 5 190 5mm 10 254mm 1 5 38 1mm 1...

Отзывы: