background image

 

- 4 - 

MaxiFit3FE/MaxFit5FE/MaxFit7FE Expandable Power Systems

Fig. 1 - eFlow Board configuration

Power Supply Board Output Voltage Settings:

LED Diagnostics:

Red (DC)

Green (AC/AC1)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Red (Bat)

Battery Status

ON

Normal operating condition.

OFF

Battery fail/low battery.

L

G

N

NC  C  NO 

NC  C  NO

BAT FAIL

AC FAIL

--- 

 DC  

+

AC

AC1

DC

--- 

BA

+

+ AUX –

TRIGGER EOL

SUPERVISED

5A 250V

5A 250V

10A 32V

10A

NO          GND

RESET

enable
disable

1 min.
2 hr.

AC DELAY   SHUTDOWN

O

N

1a

1b

1g

1h

1e

1f

1d

1c

1i

OFF   

--- 

  24V

ON   

--- 

  12

V

ON

--- 

 DC  

+

OFF - 24V
ON - 12V

ON

ON

OFF - 24V

ON - 12V

Fig. 2

Fig. 2a

Содержание Maximal Fit Series

Страница 1: ...24VDC 6A MaxFit5FE 12VDC 10A MaxFit7FE 24VDC 10A Rev MFEPS080119 More than just power TM Installing Company _________________ Service Rep Name _______________________________________ Address ________...

Страница 2: ...appropriate for the particular end productapplication and wired in accordance with the products installation instructions Class 1 wiring methods separation of circuits and proper fire rated enclosure...

Страница 3: ...d a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired they must be lead acid or gel type Connect battery to the terminals marked BAT Fig 1g pg 4 Use tw...

Страница 4: ...is supplying power OFF ON No DC output OFF OFF Loss of AC Discharged or no stand by battery No DC output Red Bat Battery Status ON Normal operating condition OFF Battery fail low battery L G N NC C N...

Страница 5: ...4 AC FAIL NC C NO Indicates loss of AC power e g connect to audible device or alarm panel Relay normally energized when AC power is present Contact rating 1A 30VDC power limited Fig 1b pg 4 BAT FAIL N...

Страница 6: ...8 CB VR6 C PD16W CB D NetWaySP3B NetWay4EB NetWaySP4B NetWaySP8B Fig 3a Tamper Switch To Access Control Panel or UL Listed Reporting Device Edge of Enclosure Enclosure External Jacketed Shield Incorre...

Страница 7: ...7 MaxiFit3FE MaxFit5FE MaxFit7FE Expandable Power Systems Notes...

Страница 8: ...81 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIMaxFit3FE 5FE 7FE Series H21S MEMBER MaxFit Enclosure Dimensions approximate 20 5 x 16 5 x 6 25...

Отзывы: