MaxiFit3FE/MaxFit5FE/MaxFit7FE Expandable Power Systems 

- 3 -

MaxFitFE Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI,
The Canadian Electrical Code, Part 1 and with all local codes and authorities having jurisdiction. The product 
must be located indoors within the protected premises. 

1.  Mount unit in desired location. Mark and predrill holes in the wall to line up with the top three keyholes in 

 

the enclosure. Install three upper fasteners and screws in the wall with the screw heads protruding. Place 

 

the enclosure’s upper keyholes over the three upper screws; level and secure. Mark the position of the 

 

lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the 

 

enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to 

 

tighten all screws (Enclosure Dimensions, pg. 8).

2.  Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, N] (Fig. 1a, pg. 4). Use 14 AWG 

 

or larger for all power connections. Secure green wire lead to earth ground. 

 

For Fire Alarm applications the outputs are “Special Applications” only.

 

Keep power-limited wiring separate from non power-limited wiring (120VAC 60Hz Input, Battery Wires). 

 

Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. 

 

Shut branch circuit power before installing or servicing equipment.

  

There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.

3.  Select desired DC output voltage by setting SW1 to the appropriate position, (MaxFit3FE) (Fig. 2a, pg. 4).
 

MaxFit5FE power supply is factory set at 12VDC.

 

MaxFit7FE power supply is factory set at 24VDC (Stand-by Battery Specifications, pg. 5).

4.  Measure output voltage before connecting devices. This helps avoiding potential damage.

5.  Connect devices or Altronix sub-assembly modules to be powered to the terminals marked [– DC +] 

 

(Fig. 1h, pg. 4). For auxiliary device connection, this output will not be affected by

 

Low Power Disconnect or Fire Alarm Interface. Connect device to the terminals

 

marked [+ AUX –] (Fig. 1f, pg. 4). Refer to page 2 for non power-limited applications.

6.  For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result 

 in the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.

 

Connect battery to the terminals marked [– BAT + ] (Fig. 1g, pg. 4). Use two (2) 12VDC batteries connected 

 

in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), CL12120 

 

(12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 batteries of 

 

an appropriate rating.

7.  Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 4) supervisory

 

relay outputs.

8.  To delay AC reporting for 2 hrs., set DIP switch [AC Delay] to OFF position (Fig. 1c, pg. 4).

 

To delay AC reporting for 1 min., set DIP switch [AC Delay] to ON position (Fig. 1c, pg. 4).

 

Note: Must be set to ON position for Burglar Alarm Applications.

9.  To enable Fire Alarm Disconnect set DIP switch [Shutdown] to ON position. (Fig. 1c, pg. 4).

 

To disable Fire Alarm Disconnect set DIP switch [Shutdown] to OFF position. (Fig. 1c, pg. 4).

10.  Trigger terminals are end of a line resistor supervised (10k Ohms). Opening or shorting trigger terminals 

 

will cause [DC] output to shutdown (Fig. 1d, pg. 4).

11.  Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching

 

[Trigger EOL Shutdown] (Fig. 1d, pg. 4).

12.  For Access Control Applications: mount UL Listed tamper switch (Altronix Model TS112 or equivalent) at 

 

the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2” from the 

 

right side (Fig. 3a, pg. 6). Connect tamper switch wiring to the Access Control Panel input or the appropriate 

 

UL Listed reporting device.

13.  Please ensure that the cover is secured with the provided key lock.

Wiring:

Use 18 AWG or larger for all low voltage power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:  Under normal load conditions the DC output voltage should be checked for proper 

 

voltage level (MaxFitFE Configuration Chart, pg. 2).

Battery Test: 

Under normal load conditions check that the battery is fully charged, check specified 

 

voltage at the battery terminals and at the board terminals marked [– BAT +] to 

 

ensure that there is no break in the battery connection wires.

Note: 

Maximum charge current 1.54A.

Expected battery life is 5 years; however, it is recommended to change batteries within 4 years or less if necessary.

Содержание Maximal Fit Series

Страница 1: ...24VDC 6A MaxFit5FE 12VDC 10A MaxFit7FE 24VDC 10A Rev MFEPS080119 More than just power TM Installing Company _________________ Service Rep Name _______________________________________ Address ________...

Страница 2: ...appropriate for the particular end productapplication and wired in accordance with the products installation instructions Class 1 wiring methods separation of circuits and proper fire rated enclosure...

Страница 3: ...d a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired they must be lead acid or gel type Connect battery to the terminals marked BAT Fig 1g pg 4 Use tw...

Страница 4: ...is supplying power OFF ON No DC output OFF OFF Loss of AC Discharged or no stand by battery No DC output Red Bat Battery Status ON Normal operating condition OFF Battery fail low battery L G N NC C N...

Страница 5: ...4 AC FAIL NC C NO Indicates loss of AC power e g connect to audible device or alarm panel Relay normally energized when AC power is present Contact rating 1A 30VDC power limited Fig 1b pg 4 BAT FAIL N...

Страница 6: ...8 CB VR6 C PD16W CB D NetWaySP3B NetWay4EB NetWaySP4B NetWaySP8B Fig 3a Tamper Switch To Access Control Panel or UL Listed Reporting Device Edge of Enclosure Enclosure External Jacketed Shield Incorre...

Страница 7: ...7 MaxiFit3FE MaxFit5FE MaxFit7FE Expandable Power Systems Notes...

Страница 8: ...81 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIMaxFit3FE 5FE 7FE Series H21S MEMBER MaxFit Enclosure Dimensions approximate 20 5 x 16 5 x 6 25...

Отзывы: