- 2 -  

MaxFit Kits Fused Installation Guide

Overview:

Altronix fused Access Power Controller kits distribute and switch power to access control systems and accessories. They convert a 120VAC 

60Hz input into eight (8) or sixteen (16) independently controlled 12VDC or 24VDC fuse protected outputs. These Fail-Safe/Fail-Secure power 

outputs may be converted to dry form “C” contacts. Relays are activated by an open collector sink or normally open (NO) dry trigger input from 

an Access Control System, Keypad, Push Button, REX PIR, etc. Units will route power to a variety of access control hardware devices including: 

Mag Locks, Electric Strikes, Magnetic Door Holders, etc. The FACP Interface enables Emergency Egress, Alarm Monitoring, or may be used 

to trigger other auxiliary devices. The fire alarm disconnect feature is individually selectable for any or all of the eight (8) Fail-Safe/Fail-Secure 

power outputs. Additional fuse protected outputs provide power for connected devices.

Configuration Chart:

Altronix

Model 

Number

Power Supply Board Input Fuse Rating

Power Supply Board Battery Fuse Rating

120VAC 60Hz Input Current (A)

Maximum Supply

Current for Main 

and Aux. Outputs on 

Power Supply board 

and ACM8/ACMS8 

Access Power 

Controllers’ outputs

Nominal DC 

Output Voltage

Fail-Safe/Fail-Secure or  Dry Form “C” Outputs

Additional Fused  Outputs

ACM8 Board  Input Fuse Rating

ACM8 Board Output Fuse Rating

ACMS8 Board  Input Fuse Rating

ACMS8 Board Output Fuse Rating

PDS8 Board Input Fuse Rating

PDS8 Board Output Fuse Rating

PD8UL/PD16W Board Output Fuse Rating

[DC]

[Aux]

Output 

Range 

(VDC)

Output 

Range 

(VDC)

MaxFit7F8AP

6.3A/

250V

15A/

32V

4.5

24VDC @ 9.7A

20.17-

26.4

20.28-

26.4

8

8

10A/

250V

2.5A/

250V

3.5A/

250V

MaxFit7F16AP

24VDC @ 9.4A

16

16

10A/

250V

2.5A/

250V

3.5A/

250V

MaxFit7F8APS

24VDC @ 9.4A

8

8

10A/

250V

2.5A/

250V

10A/

32V

3A/

32V

MaxFit7F16APS

24VDC @ 9.4A

16

16

15A/

32V

3A/

32V

3.5A/

250V

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction. 

Product is intended for indoor use only. 

1.  Mount unit in desired location. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install 

 

three upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three 

 

upper screws, level and secure. Mark the position of the lower three holes. Remove the enclosure. Drill the lower holes and install 

 

the three fasteners. Place the enclosure’s upper keyholes over the three upper screws. Install the three lower screws and make sure to 

 

tighten all screws 

(Enclosure Dimensions, pg. 8)

.

2.  Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, N] 

(Fig. 2-5, pg. 3-6)

. Use 14 AWG or larger for all power 

 

connections. Secure green wire lead to earth ground.

 

Keep power-limited wiring separate from non power-limited wiring. 

 

Minimum 0.25” spacing must be provided 

(Fig. 2-5, pg. 3-6

).

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. 

 

There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.

3.  Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in

 

desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the 

 

enclosure approximately 2” from the right side 

(Fig. 1, pg. 2)

 

Connect tamper switch wiring to the Access Control Panel input or the appropriate 

 

UL Listed reporting device. To activate alarm signal open the door of the enclosure.

4.  Refer to the 

eFlow Power Supply/Charger Installation Guide

 for eFlow104NB

 

and corresponding 

Sub-Assembly Installation Guides

 for 

 

ACM8, ACMS8, PDS8, VR6, PD8UL and PD16W for further installation instructions.

Fig. 1

Tamper Switch

(included)

To Access Control Panel or

UL Listed Reporting Device

Edge of

Enclosure

Enclosure

Содержание MAXIMAL FIT MaxFit7F8AP

Страница 1: ...upply Charger One 1 ACM8 Fuse Protected Access Power Controller One 1 PDS8 Dual Input Fuse Protected Power Distribution Module One 1 VR6 Voltage Regulator BC750 enclosure MaxFit7F16APS 16 Door Kit wit...

Страница 2: ...4A 16 16 15A 32V 3A 32V 3 5A 250V Installation Instructions Wiring methods shall be in accordance with the National Electrical Code NFPA 70 ANSI and with all local codes and authorities having jurisdi...

Страница 3: ...ections power limited ACM8 Outputs to Devices non power limited PD8UL Outputs to Devices non power limited Connect red battery lead to the terminal marked BAT and to the positive terminal of the batte...

Страница 4: ...ad to the terminal marked BAT and to the positive terminal of the battery Connect black battery lead to terminal marked BAT and to the negative terminal of the battery Keep power limited wiring separa...

Страница 5: ...battery Keep power limited wiring separate from non power limited Use minimum 0 25 spacing 12AH Rechargeable batteries are the largest batteries that can fit in this enclosure A UL listed external ba...

Страница 6: ...ed DC Output non power limited Supervisory Connections power limited PD16W Outputs to Devices non power limited ACMS8 Outputs to Devices non power limited ACMS8 Outputs to Devices non power limited Co...

Страница 7: ...e Total Cost of Ownership TCO as well as creat ing a new source of Recurring Monthly Revenue RMR LINQ2 Features UL Listed in the U S and Canada Local or remote control of up to 2 two Altronix eFlow po...

Страница 8: ...1 50 38 1mm 6 25 158 8mm 1 25 31 8mm 1 25 31 8mm 7 00 177 8mm 7 00 177 8mm 7 00 177 8mm 7 00 177 8mm 1 25 31 8mm 1 25 31 8mm 16 50 419 1mm 1 25 31 8mm 0 75 19 1mm 0 569 14 5mm 1 00 25 4mm 1 25 31 8mm...

Отзывы: