MaxFit7F8AP: NEC Power-Limited Wiring Requirements

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 

0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must 

enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different 

conduit knockouts to be used. Any conduit knockouts may be used. For power-limited applications use of conduit is optional. All field wiring 

connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional UL Listed battery enclosure 

must be mounted adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections. 

Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire 

(Fig. 2a)

.

Supervisory Connections, Aux. DC Output to Devices and

Fire Alarm Interface (power-limited)

Input 120VAC, 60Hz

(non power-limited)

DC Output

(non power-

limited)

Supervisory

Connections

(power-limited)

ACM8 Outputs

to Devices

(non power-

limited)

PD8UL Outputs

to Devices

(non power-

limited)

Connect red battery lead to the terminal marked [+ BAT] and to the [positive (+)] terminal of the battery.

Connect black battery lead to terminal marked [BAT –] and to the [negative (–)] terminal of the battery.

Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.

12AH Rechargeable batteries are the largest batteries that can fit in this enclosure. 

A UL listed external battery enclosure must be used if using the 40AH or 65AH batteries.

Optional

Rechargeable

Stand-by Batteries

for UL294

Applications

  

Note:

12V batteries

are required for

ULC-S319

installations.

Tamper Switch

OUTPUT 1     OUTPUT 2         OUTPUT 3         OUTPUT 4          OUTPUT 5        OUTPUT 6         OUTPUT 7        OUTPUT 

8

NC  C  NO COM NC C NO COM  NC  C  NO COM NC C NO COM  NC  C  NO COM NC C NO COM  NC  C NO COM NC C NO COM

 IN  GND IN GND IN GND IN GND

IN  GND IN GND IN  GND IN GND

1            2           3          

4

5           6           7           

8

 INPUT TRIGGER

10A 250V

+INP-  T + RET-

NO  C   NC

FACP            INTERFACE

Power   Control

-      +      -      +

F1                   F2                  F3                   F4                   F5                   F6                   F7

                   F8

MAIN

TRG

FACP

1  2  3  

4

1  2  3  

4

ONON

1  2  3  

4

1  2  3  

4

ONON

N

COMMON   POWER   OUTPUT

S

P

FUSED    POWER    OUTPUT

S

8

D1

INPU

T

P        

N

R1

LE

D

ACM8

PD8UL

eFlow104NB

–   DC   +

–   BAT   +

L         G          

N

External

Jacketed

Shield

Incorrect Wire

Handling

Correct Wire

Handling

Pull back

external jacketed

shield approx. 0.5”.

Wire

Insulation

Solid Copper

Conductors

Fig. 2a

Fig. 2

Содержание MAXIMAL FIT MaxFit7F8AP

Страница 1: ...upply Charger One 1 ACM8 Fuse Protected Access Power Controller One 1 PDS8 Dual Input Fuse Protected Power Distribution Module One 1 VR6 Voltage Regulator BC750 enclosure MaxFit7F16APS 16 Door Kit wit...

Страница 2: ...4A 16 16 15A 32V 3A 32V 3 5A 250V Installation Instructions Wiring methods shall be in accordance with the National Electrical Code NFPA 70 ANSI and with all local codes and authorities having jurisdi...

Страница 3: ...ections power limited ACM8 Outputs to Devices non power limited PD8UL Outputs to Devices non power limited Connect red battery lead to the terminal marked BAT and to the positive terminal of the batte...

Страница 4: ...ad to the terminal marked BAT and to the positive terminal of the battery Connect black battery lead to terminal marked BAT and to the negative terminal of the battery Keep power limited wiring separa...

Страница 5: ...battery Keep power limited wiring separate from non power limited Use minimum 0 25 spacing 12AH Rechargeable batteries are the largest batteries that can fit in this enclosure A UL listed external ba...

Страница 6: ...ed DC Output non power limited Supervisory Connections power limited PD16W Outputs to Devices non power limited ACMS8 Outputs to Devices non power limited ACMS8 Outputs to Devices non power limited Co...

Страница 7: ...e Total Cost of Ownership TCO as well as creat ing a new source of Recurring Monthly Revenue RMR LINQ2 Features UL Listed in the U S and Canada Local or remote control of up to 2 two Altronix eFlow po...

Страница 8: ...1 50 38 1mm 6 25 158 8mm 1 25 31 8mm 1 25 31 8mm 7 00 177 8mm 7 00 177 8mm 7 00 177 8mm 7 00 177 8mm 1 25 31 8mm 1 25 31 8mm 16 50 419 1mm 1 25 31 8mm 0 75 19 1mm 0 569 14 5mm 1 00 25 4mm 1 25 31 8mm...

Отзывы: