MaxiFit11FE/13FE/33FE/35FE/37FE/55FE/75FE/77FE Expandable Power Systems Installation Guide

NEC Power-Limited Wiring Requirements:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit 

wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited 

circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One 

such example of this is shown below. Your specific application may require different conduit

knockouts to be used. Any conduit knockouts may be used. For power-limited

applications use of conduit is optional. All field wiring connections must be made

employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). 

Optional battery enclosure must be mounted adjacent to the power supply via Class 1

wiring methods. For Canadian installations use shielded wiring for all connections.

Note: Refer to wire handling drawing below for the proper way to install the

CM or FPL jacketed wire 

(Fig. 3b)

.

Fig. 3

A ACM8(CB), ACMS8(CB)

B

ACM4(CB), LINQ8PD(CB),

PD4UL(CB), PD8UL(CB),

MOM5, PDS8(CB), VR6

C PD16W(CB)

D NetWaySP3B, NetWay4EB,

NetWaySP4B, NetWaySP8B 

Tamper Switch

Optional

Rechargeable

Stand-by Battery

for UL294

Applications

  

Note:

12V batteries

are required for

ULC-S319

installations.

Input 120VAC, 60Hz

(non power-limited)

 

 

Supervisory Connections, Aux. Outputs to Devices and

Fire Alarm Interface (power-limited)

  CAUTION: When power supply board is set for 12VDC use

  only one (1) 12VDC stand-by battery. 

  Connect red battery lead to the terminal marked [+ BAT] and to

  the [positive (+)] terminal of the battery. 

  Connect black battery lead to terminal   marked [BAT –] and to

  the [negative (–)] terminal of the battery.

Keep power-limited wiring separate from non power-limited. 

  Use minimum 0.25" spacing.

  12AH Rechargeable batteries are the largest batteries that

  can fit in this enclosure. 

  An external battery enclosure must be

  used if using the 40AH or 65AH batteries.

NC  C  NO  NC

C  NO

AC FAI

LB

AT FAIL

TRIGGER

AC

DC

AC1

EOL

NO

GN
D

SUPERVISED

RESE

T

+AUX-

-  BAT  +

-  DC  +

L     G     

N

A

B

C

D

A

B

C

Power

Supply/

Charger

NC  C  NO  NC

C  NO

AC FAIL

BAT FAIL

TRIGGER

AC

DC

AC1

EOL

NO

GN
D

SUPERVISED

RESET

+AUX-

-  BAT  +

-  DC  +

L     G     

N

Power

Supply/

Charger

DC Output

(non power-limited)

Battery

(non power-limited)

DC Output

(non power-limited)

Battery

(non power-limited)

Fig. 3a

Tamper Switch

(included)

To Access Control Panel or

UL Listed Reporting Device

Edge of

Enclosure

Enclosure

External

Jacketed

Shield

Incorrect Wire

Handling

Correct Wire

Handling

Pull back

external jacketed

shield approx. 1/2”.

Wire

Insulation

Solid Copper

Conductors

Fig. 3b

Содержание MAXIMAL FIT MaxFit11FE

Страница 1: ...one ___________________ MaxFit FE Series Expandable Power Systems Models Include Installation Guide MaxFit11FE 12VDC 24VDC 4A 12VDC 24VDC 4A MaxFit13FE 12VDC 24VDC 4A 12VDC 24VDC 6A MaxFit33FE 12VDC 2...

Страница 2: ...10 1 13 2 10 05 13 2 10 1 13 2 10 05 13 2 20 28 26 4 20 2 26 4 20 28 26 4 20 2 26 4 20 28 26 4 20 2 26 4 MaxFit13FE eFlow4NB eFlow6NB 4A 6A 1 1 2 7 5A 250V 7 5A 32V eFlow4NB 10A 32V eFlow6NB 730 eFlo...

Страница 3: ...VAC present AC input and DC output LED indicators Short circuit and overload protection Enclosure accommodates up to four 4 12VDC 12AH batteries Enclosure dimensions H x W x D 20 5 x 16 5 x 6 25 520 7...

Страница 4: ...5 To disable Fire Alarm Disconnect set DIP switch Shutdown to OFF position Fig 1c pg 5 10 Trigger terminals are end of a line resistor supervised 10k Ohms Opening or shorting trigger terminals will ca...

Страница 5: ...Stand by battery is supplying power OFF ON No DC output OFF OFF Loss of AC Discharged or no stand by battery No DC output Red Bat Battery Status ON Normal operating condition OFF Battery fail low bat...

Страница 6: ...ower limited Fig 1b pg 5 BAT FAIL NC C NO Indicates low battery condition e g connect to alarm panel Relay normally energized when DC power is present Contact rating 1A 30VDC A removed battery is repo...

Страница 7: ...r Switch Optional Rechargeable Stand by Battery for UL294 Applications Note 12V batteries are required for ULC S319 installations Input 120VAC 60Hz non power limited Supervisory Connections Aux Output...

Страница 8: ...5 31 8mm 8 75 222 3mm 8 75 222 3mm 1 50 38 1mm 1 50 38 1mm 6 25 158 8mm 1 25 31 8mm 1 25 31 8mm 7 00 177 8mm 7 00 177 8mm 7 00 177 8mm 7 00 177 8mm 1 25 31 8mm 1 25 31 8mm 16 50 419 1mm 1 25 31 8mm 0...

Отзывы: