MaxiFit11FE/13FE/33FE/35FE/37FE/55FE/75FE/77FE Expandable Power Systems Installation Guide
- 6 -
Terminal Identification:
Terminal
Legend
Function/Description
L, N
Connect 120VAC 60Hz to these terminals: L to hot, N to neutral.
Do not use terminal marked [G]
(Fig. 1a, pg. 5)
.
+ DC –
Refer to
MaxFitFE Series Configuration Chart, pg. 2 (Fig. 1h, pg. 5).
Trigger EOL
Supervised
Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open,
normally closed from an FACP output circuit (power-limited input)
(Fig. 1d, pg. 5)
.
NO, GND RESET FACP interface latching or non-latching (power-limited)
(Fig. 1e, pg. 5)
.
+ AUX –
Auxiliary Power-Limited output rated @ 1A (unswitched)
(Fig. 1f, pg. 5)
.
AC FAIL
NC, C, NO
Indicates loss of AC power, e.g. connect to audible device or alarm panel.
Relay normally energized when AC power is present.
Contact rating 1A @ 30VDC (power-limited)
(Fig. 1b, pg. 5)
.
BAT FAIL
NC, C, NO
Indicates low battery condition, e.g. connect to alarm panel.
Relay normally energized when DC power is present. Contact rating 1A @ 30VDC.
A removed battery is reported within 5 minutes.
Battery reconnection is reported within 1 minute (power-limited)
(Fig. 1b, pg. 5)
.
+ BAT –
Stand-by battery connections.
Maximum charge current 1.54A (non power-limited)
(Fig. 1g, pg. 5)
.
Power Supply Board Stand-by Battery Specifications
eFlow4NB:
Battery
Access Control Applications Stand-by
7AH
30 Mins./4A*
12AH
35 Mins./4A*
40AH
Over 4 Hours/4A*
65AH
Over 4 Hours/4A*
eFlow6NB:
Battery
Access Control Applications Stand-by
7AH
10 Mins./6A
12AH
30 Mins./6A*
40AH
Over 4 Hours/6A*
65AH
Over 4 Hours/6A*
eFlow102NB:
Battery
Access Control Applications Stand-by
7AH
5 Mins./10A
12AH
30 Mins./10A*
40AH
Over 2 Hours/10A*
65AH
Over 4 Hours/10A*
eFlow104NB:
Battery
Access Control Applications Stand-by
7AH
5 Mins./10A
12AH
30 Mins./10A*
40AH
Over 2 Hours/10A*
65AH
Over 4 Hours/10A*
*Only these configurations can be utilized in ULC-S319 installations.