Maximal11D/Maximal33D/Maximal55D/Maximal77D/Maximal75D Access Power Controllers (PTC)

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:
 

FACP Supervision: 

To ensure proper connection and operation of the Fire Alarm disconnect 

 

 

hookup . Please follow the appropriate procedure below:

 

Normally Open Input: 

Placing a short between terminals marked [T] and [+ INP] will trigger the 

 

 

Fire Alarm Disconnect . Remove the short to reset .

 

Normally Closed Input: 

Remove the wire from terminal marked [INP –] will trigger the Fire Alarm 

 

 

Disconnect . Replace the wire to terminal marked [INP –] to reset .

 

FACP Signal Circuit Input:  It is necessary to trigger the Fire Alarm System .

 

 

In all of the above scenarios the green TRG LED of the ACM8CBs will 

 

 

illuminate . All outputs selected for Fire Alarm Disconnect will activate 

 

 

releasing locking devices .

  

Note: All outputs [OUT 1 - OUT 8] must be in a normal (de-energized) 

 

 

condition prior to testing . When the unit is configured for Normally Open 

  

(Fig. 13, pg. 18) or Normally Closed (Fig. 15, pg. 18) latching operation, 

 

 

it is necessary to reset the Fire Alarm Disconnect by activating the 

 

 

Normally Closed reset switch .

 

Output Voltage Test: 

Under normal load conditions, the DC output voltage should be checked 

 

 

for proper voltage level (Power Supply Board Stand-by Battery 

 

 

Specifications, pg. 8).

 

Battery Test: 

Under normal load conditions check that the battery is fully charged, check 

 

 

specified voltage at the battery terminals and at the board terminals marked 

 

 

[+ BAT –] to ensure that there is no break in the battery connection wires .

  

Note: AL400ULXB2, AL600ULXB and AL1012ULXB Power Supply 

  

Board 

maximum charge current is 0 .7A . 

  

AL1024ULXB2 

Power Supply Board maximum charge current is 3 .6A .

 

 

Expected battery life is 5 years; however, it is recommended to change 

 

 

batteries within 4 years or less if necessary .

Power Supply Board LED Diagnostics:

LED

Power Supply Status

Red (DC)

Green (AC)

ON

ON

Normal operating condition .

ON

OFF

Loss of AC . Stand-by battery supplying power .

OFF

ON

No DC output . Short circuit or thermal overload condition .

OFF

OFF

No DC output . Loss of AC . Discharged battery .

Red (Bat)

Battery Status

ON

Normal operating condition .

OFF

Battery fail/low battery .

Access Power Controller LED Diagnostics:

LED

ON

OFF

LED 1- LED 8 (Red)

Output relay(s) energized .

Output relay(s) de-energized .

Trg (Green)

FACP input triggered (alarm condition) . FACP normal (non-alarm condition) .

Содержание Maximal D Series

Страница 1: ...upply 1 12VDC 5 5A or 24VDC 5 7A Power Supply 2 12VDC 5 5A or 24VDC 5 7A Sixteen 16 PTC protected Class 2 Rated power limited outputs Maximal55D Power Supply 1 12VDC 9 5A Power Supply 2 12VDC 9 5A Six...

Страница 2: ...y Specifications pg 8 Power Supply Board Output Voltage Settings pg 9 Access Power Controller Typical Application Diagram for each ACM8 pg 9 Maximal11D Maximal33D Maximal55D Battery Hookup and Tamper...

Страница 3: ...ile Numbers Power Supply 1 Power Supply 2 Maximal11D AL400ULXB2 AL400ULXB2 2 5A 16 7A 5A 250V 15A 32V UL File BP6714 UL 294 UL Listed for Access Control System Units General Signaling Equipment Evalua...

Страница 4: ...ct is intended for indoor use only Power Supply Board LED Diagnostics pg 6 Access Power Controller LED Diagnostics pg 6 Power Supply Board Terminal Identification pg 7 Access Power Controller Terminal...

Страница 5: ...g circuit output to the terminals marked INP Connect the FACP EOL to the terminals marked RET polarity is referenced in an alarm condition Jumper located next to TRG LED must be cut Fig 2b pg 8 and Fi...

Страница 6: ...Disconnect by activating the Normally Closed reset switch Output Voltage Test Under normal load conditions the DC output voltage should be checked for proper voltage level Power Supply Board Stand by...

Страница 7: ...24VDC output threshold set approximately 21VDC BAT Stand by battery connections Connect one 1 12VDC battery to the terminals marked BAT for 12VDC operation Fig 3 pg 10 Fig 5 pg 12 Use two 2 12VDC batt...

Страница 8: ...12VDC 40AH N A 3 5A 0 5A 24VDC 40AH N A 2 7A 0 7A Maximal33D AL600ULXB Refer to Fig 1a pg 9 for Switch SW1 location and position 12VDC 40AH N A 5 5A 5 5A 24VDC 40AH N A 5 5A 0 7A Maximal55D Maximal75D...

Страница 9: ...this application corresponding fuse F8 must be removed Keypad NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3...

Страница 10: ...COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 FACP INTERFACE 10A 250...

Страница 11: ...OM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 FACP INTERFACE 10A 250V 1 2 3 4 O N 1 2 3 4 O N LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1...

Страница 12: ...UT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 FACP INTERFACE 10A 250V 1 2 3 4...

Страница 13: ...knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed...

Страница 14: ...cific application may require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be ma...

Страница 15: ...knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed...

Страница 16: ...knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed...

Страница 17: ...OWER INPUT 12 OR 24 VAC OR VDC ACM8 POWER Fig 10 Optional hook up using two 2 isolated power supply inputs Only applicable on Maximal11 CUT JUMPER FROM FACP OUTPUT CIRCUIT FACP OUTPUT EOL TRG NO C NC...

Страница 18: ...PER TRG NO C NC Fig 13 Normally Open FACP Latching trigger input with reset This output has not been evaluated by UL JUMPER N C DRY TRIGGER INPUT TRG NO C NC FACP INTERFACE Fig 14 Normally Closed Non...

Страница 19: ...Maximal11D Maximal33D Maximal55D Maximal77D Maximal75D Access Power Controllers PTC 19 Notes...

Страница 20: ...8mm 2 50 8mm 2 50 8mm 6 25 158 75mm 6 25 158 75mm 4 101 6mm 4 101 6mm 2 50 8mm 4 101 6mm 8 9 226 06mm 8 4 213 36mm 7 177 8mm 7 177 8mm 7 177 8mm 8 4 213 36mm 8 5 215 9mm 8 5 215 9mm 7 5 190 5mm 10 254...

Отзывы: