- 4 - 

Maximal11D/Maximal33D/Maximal55D/Maximal77D/Maximal75D Access Power Controllers (PTC)

•  Sixteen (16) unswitched filtered and electronically regulated aux . power outputs (outputs are rated @ 2 .5A) .
•  ACM8CB maximum current is 2 .5A per output .
•  Red LEDs on ACM8CB board indicate individual outputs are triggered (relays energized) .
•  Fire Alarm disconnect (latching or non-latching) is individually selectable for any or all of the 
  sixteen (16) outputs .
  Fire Alarm disconnect input trigger options:
  a) Normally open (NO) or normally closed (NC) dry trigger input .
  b) Polarity reversal input from FACP signaling circuit .
•  Green LED on ACM8CB board indicates FACP disconnect is triggered .
•  FACP output relay indicates that FACP input is triggered 
  (form “C” contact rated @ 1A/28VDC not evaluated by UL) .
•  Power supply input options:
  a) Factory installed power supplies provide common power for both ACM8CB boards and all connected
    access control devices .
  b) An optional UL Listed power-limited external access control power supply may be connected to isolate 
    the ACM8CB boards from the access control devices (only applicable on Maximal11D).
•  ACM8CB board main fuses are rated @ 10A . Output PTCs are rated @ 2 .5A .
•  Built-in charger for sealed lead acid or gel type batteries . 
  - Maximum charge current is 0 .7A for AL400ULXB2, AL600ULXB and AL1012ULXB power supply boards .
  - Maximum charge current is 3 .6A for AL1024ULXB2 power supply board .
•  Automatic switch over to stand-by battery when AC fails .
•  Zero voltage drop when unit switches over to battery backup (AC failure condition) .
•  Short circuit and thermal overload protection with auto reset . 
•  Green AC input and red DC output LED indicators on power supply board(s) .
•  AC fail supervision (form “C” contact rated @ 1A/28VDC) . 
•  Battery fail and battery presence supervision (form “C” contact rated @ 1A/28VDC) .
•  Enclosure accommodates up to four (4) 12VDC/12AH batteries .
Enclosure dimensions: 26” x 19” x 6 .25” (660 .4mm x 482 .6mm x 158 .8mm) .

MaximalD Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local 
codes and authorities having jurisdiction . Product is intended for indoor use only . 
 

Power Supply Board LED Diagnostics 

(pg. 6)

 

Access Power Controller LED Diagnostics 

(pg. 6)

 

Power Supply Board Terminal Identification 

(pg. 7)

 

Access Power Controller Terminal Identification 

(pg. 7)

 

Power Supply Board Stand-by Battery Specifications 

(pg. 8)

 

Power Supply Board Output Voltage Settings 

(pg. 9)

 

Access Power Controller Typical Application Diagram 

(pg. 9)

 

FACP/Optional Power Supply Hook-up Diagrams 

(pg. 17-18)

1 .  Mount unit in the desired location . Mark and predrill holes in the wall to line up with the top three key
 

holes in the enclosure . Install three upper fasteners and screws in the wall with the screw heads protruding . 

 

Place the enclosure’s upper keyholes over the three upper screws, level and secure . Mark the position of the 

 

lower three holes . Remove the enclosure . Drill the lower holes and install the three fasteners . Place the 

 

enclosure’s upper keyholes over the three upper screws . Install the three lower screws and make sure to 

 

tighten all screws (Enclosure Dimensions, pg. 20) .

2 .  The power supply is pre-wired to the ground (chassis) . Connect main incoming ground to the provided 
 

green grounding conductor lead . Connect unswitched AC power (115VAC, 60Hz) to the terminals marked 

 

[L, N] on both power supply boards . Green “AC” LED on power supply board will turn on . This light can 

 

be seen through the LED lens on the door of the enclosure . Use 14 AWG or larger for all power connections . 

 

Keep power-limited wiring separate from non power-limited wiring (115VAC, 60Hz Input, 

 

Battery Wires). Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing 

 

equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified 

 

service personnel.

3 .  Select desired DC output voltage by setting SW1 to the appropriate position on the power supply board
 

(Maximal11D and Maximal33D) (Fig. 1, pg. 9). Maximal55D power supply is factory set at 12VDC . 

 

Maximal77D power supply is factory set at 24VDC . Maximal75D consists of one (1) power supply board 

 

that is factory set at 12VDC, and one (1) power supply board that is factory set at 24VDC .

4 .  Measure the output voltage of the unit before connecting any devices to ensure proper operation .
 

Improper or high voltage will damage these devices .

Содержание Maximal D Series

Страница 1: ...upply 1 12VDC 5 5A or 24VDC 5 7A Power Supply 2 12VDC 5 5A or 24VDC 5 7A Sixteen 16 PTC protected Class 2 Rated power limited outputs Maximal55D Power Supply 1 12VDC 9 5A Power Supply 2 12VDC 9 5A Six...

Страница 2: ...y Specifications pg 8 Power Supply Board Output Voltage Settings pg 9 Access Power Controller Typical Application Diagram for each ACM8 pg 9 Maximal11D Maximal33D Maximal55D Battery Hookup and Tamper...

Страница 3: ...ile Numbers Power Supply 1 Power Supply 2 Maximal11D AL400ULXB2 AL400ULXB2 2 5A 16 7A 5A 250V 15A 32V UL File BP6714 UL 294 UL Listed for Access Control System Units General Signaling Equipment Evalua...

Страница 4: ...ct is intended for indoor use only Power Supply Board LED Diagnostics pg 6 Access Power Controller LED Diagnostics pg 6 Power Supply Board Terminal Identification pg 7 Access Power Controller Terminal...

Страница 5: ...g circuit output to the terminals marked INP Connect the FACP EOL to the terminals marked RET polarity is referenced in an alarm condition Jumper located next to TRG LED must be cut Fig 2b pg 8 and Fi...

Страница 6: ...Disconnect by activating the Normally Closed reset switch Output Voltage Test Under normal load conditions the DC output voltage should be checked for proper voltage level Power Supply Board Stand by...

Страница 7: ...24VDC output threshold set approximately 21VDC BAT Stand by battery connections Connect one 1 12VDC battery to the terminals marked BAT for 12VDC operation Fig 3 pg 10 Fig 5 pg 12 Use two 2 12VDC batt...

Страница 8: ...12VDC 40AH N A 3 5A 0 5A 24VDC 40AH N A 2 7A 0 7A Maximal33D AL600ULXB Refer to Fig 1a pg 9 for Switch SW1 location and position 12VDC 40AH N A 5 5A 5 5A 24VDC 40AH N A 5 5A 0 7A Maximal55D Maximal75D...

Страница 9: ...this application corresponding fuse F8 must be removed Keypad NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3...

Страница 10: ...COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 FACP INTERFACE 10A 250...

Страница 11: ...OM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 FACP INTERFACE 10A 250V 1 2 3 4 O N 1 2 3 4 O N LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1...

Страница 12: ...UT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 FACP INTERFACE 10A 250V 1 2 3 4...

Страница 13: ...knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed...

Страница 14: ...cific application may require different conduit knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be ma...

Страница 15: ...knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed...

Страница 16: ...knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed...

Страница 17: ...OWER INPUT 12 OR 24 VAC OR VDC ACM8 POWER Fig 10 Optional hook up using two 2 isolated power supply inputs Only applicable on Maximal11 CUT JUMPER FROM FACP OUTPUT CIRCUIT FACP OUTPUT EOL TRG NO C NC...

Страница 18: ...PER TRG NO C NC Fig 13 Normally Open FACP Latching trigger input with reset This output has not been evaluated by UL JUMPER N C DRY TRIGGER INPUT TRG NO C NC FACP INTERFACE Fig 14 Normally Closed Non...

Страница 19: ...Maximal11D Maximal33D Maximal55D Maximal77D Maximal75D Access Power Controllers PTC 19 Notes...

Страница 20: ...8mm 2 50 8mm 2 50 8mm 6 25 158 75mm 6 25 158 75mm 4 101 6mm 4 101 6mm 2 50 8mm 4 101 6mm 8 9 226 06mm 8 4 213 36mm 7 177 8mm 7 177 8mm 7 177 8mm 8 4 213 36mm 8 5 215 9mm 8 5 215 9mm 7 5 190 5mm 10 254...

Отзывы: