background image

 

- 2 - 

LPS3WP12220 Installation Guide

-

AC

DC

BAT +

AC

+

DC

AC-

LPS3

Input 220VAC,

50/60 Hz

Fig. 2

LED Diagnostics:

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Terminal Legend

Function/Description

AC AC

Low voltage AC input (16.5VAC 56VA). Altronix part #T1656220.

– BAT +

Stand-by battery connections.

– DC +

12VDC @ 2.5A continuous output.