- 6 -
LINQ8ACM(CB)
LED Diagnostics:
LED
ON
OFF
LED 1- LED 8 (Red)
Output relay(s) de-energized.
Output relay(s) energized.
FACP
FACP input triggered (alarm condition). FACP normal (non-alarm condition).
Green Output 1-8
12VDC
–
Red Output 1-8
24VDC
–
AC
AC Fail
AC Normal
BAT
Battery Fail
Battery Normal
Input/Output Voltage Ratings:
Input Voltage and Source
Output Voltage Rating
5VDC (from VR6 regulator)
5VDC
12V (from VR6 regulator)
12VDC
12VDC (from external power supply)
11.7-12VDC
24VDC (from external power supply)
23.7-24VDC
Maximum Output of Altronix Power Supplies:
UL Listed or Recognized Power Supply
Output Voltage Setting
Max. Output Current
eFlow4NB
12VDC or 24VDC
4A
eFlow6NB
12VDC or 24VDC
6A
eFlow102NB
12VDC
10A
eFlow104NB
24VDC
10A
VR6
5VDC or 12VDC
6A
Tango1B
12VDC and 24VDC
12VDC @ 5.4A and/or
24VDC @ 2.7A.
65W total.