Altronix eFlow4N8DV Скачать руководство пользователя страница 4

- 4 - 

eFlow6NV Series

LED Diagnostics:

Power Supply/Charger

Red (DC)

Green (AC/AC1)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Power Distribution Module

Green (AC)

Power Distribution Module Status

ON

Normal operating condition.

OFF

No power output.

Terminal Identification:

Power Supply/Charger

Terminal Legend Function/Description

L, N

Connect 220VAC 50/60Hz to these terminals: L to hot, N to neutral (non power-limited)
(Fig. 1a, pg.5).

– DC +

12VDC or 24VDC nominal @ 6 amp continuous output (non power-limited output) (Fig. 1h, pg. 5).

Trigger EOL

Supervised

Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open,

normally closed from an FACP output circuit (power-limited input) (Fig. 1d, pg. 5).

NO, GND RESET FACP interface latching or non-latching (power-limited) (Fig. 1e, pg. 5).
+ AUX – 

Auxiliary power-limited output rated @ 1 amp (unswitched) (power-limited output) (Fig. 1f, pg. 5).

AC Fail 

NC, C, NO

Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized

when AC power is present. Contact rating 1 amp @ 30VDC (power-limited) (Fig. 1b, pg. 5).

Bat Fail

NC, C, NO

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC 

power is present. Contact rating 1 amp @ 30VDC. A removed battery is reported within 5 minutes.

Battery reconnection is reported within 1 minute (power-limited) (Fig. 1b, pg. 5).

– BAT +

Stand-by battery connections. Maximum charge current 1.54 amp (non power-limited) (Fig. 1g, pg. 5).

Terminal Identification:

Power Distribution Module

Terminal Legend

PD8/PD8CB

Terminal Legend

PD16W/PD16WCB

Function/Description

1P to 8P

1P to 16P

Positive DC power outputs.

1N to 8N 

1N to 16N

Negative DC power outputs.

Содержание eFlow4N8DV

Страница 1: ...uts Eight 8 PTC Outputs eFlow6N16V eFlow6NX16V eFlow6N16DV eFlow6NX16DV 6 amp 12VDC or 24VDC 6 amp 12VDC or 24VDC Sixteen 16 Fused Outputs Sixteen 16 PTC Outputs Rev 6NVRP052213 More than just power I...

Страница 2: ...mp 12AH 1 amp 6 amp 0 3 amp 6 amp 25 Mins 6 amp 40AH for eFlow6NXV refer to Fig 8 pg 10 6 amp 6 amp 1 2 amp 6 amp Over 4 Hours 6 amp 65AH for eFlow6NXV refer to Fig 8 pg 10 6 amp 6 amp 1 5 amp 6 amp O...

Страница 3: ...tions batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired they must be lead acid or gel type Connect...

Страница 4: ...output circuit power limited input Fig 1d pg 5 NO GND RESET FACP interface latching or non latching power limited Fig 1e pg 5 AUX Auxiliary power limited output rated 1 amp unswitched power limited ou...

Страница 5: ...ows the circuitry needed for local annunciation Fig 2 Battery trouble indication For Canadian use a red indicating lamp must be visible from the exterior of this enclosure Wire one leg of a power sour...

Страница 6: ...utputs 1N 8N Common Outputs N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED From Power Supply Board Factory Installed DC Output to devices 1P 8P Power Outputs 1N 8N Common...

Страница 7: ...eries that can fit in this enclosure An external battery enclosure must be used if using 12AH 40AH or 65AH batteries Green Lead ground 220VAC power mains Battery and AC Supervision Circuit Battery Con...

Страница 8: ...s optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to the power supply N...

Страница 9: ...C C NO BAT FAIL AC FAIL DC AC AC1 DC BAT AUX TRIGGER EOL SUPERVISED 5A 250V RESET GND NO disable enable 2 hr 1 min AC DELAY SHUTDOWN O N 220VAC power mains Green Lead ground Battery connections DC Out...

Страница 10: ...optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to the power supply No...

Страница 11: ...25 342 9mm x 330 2mm x 82 55mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm...

Страница 12: ...31 75mm 1 25 31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 38 1mm 1...

Страница 13: ...2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24 volt Photoelectr...

Страница 14: ...14 eFlow6NV Series Notes...

Страница 15: ...r any typographical errors Product specifications are subject to change without notice 140 58th Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 website www altronix com e mail info al...

Страница 16: ...1 5 amp 6 amp Over 4 Hours 6 amp Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54 amp Automatic switch over to stand by battery when AC fails Tran...

Отзывы: