- 2 - 

eFlow6NV Series

Overview:

The eFlow6NV power supply/chargers convert a 220VAC (working range 198VAC - 256VAC),

 

50/60Hz input to a 

12VDC or 24VDC nominal output (see Power Supply Configuration Reference Chart and Specifications).

eFlow6NV Series Power Supply Configuration Reference Chart:

Altronix  Model Number

Nominal DC Outputs

Maximum Supply Current for Main and  Aux. Outputs (amp)

Input Rating: 220VAC, 50/60Hz

Input Fuse Rating

Battery Fuse Rating

Ripple Voltage (mV)

Under low battery condition

Power Distribution Modiule

Number of Outputs

Fused Output Ratings

PTC Output Ratings

Accommodates up to 7AH Batteries

Accommodates up to 12AH Batteries

[DC]

[AUX]

12VDC Output Range (volts)

24VDC Output Range (volts)

12VDC Output Range (volts)

24VDC Output Range (volts)

eFlow6NV

10.0-

13.2

20.19-

26.4

10.03-

13.2

20.19-

26.4

6

2.1A 5A/250V 10A/32V 910

N/A

1

3

eFlow6NXV

3

eFlow6N8V

10.0-

13.2

20.19-

26.4

10.03-

13.2

20.19-

26.4

6

2.1A 5A/250V 10A/32V 910

PD8

8

2.5A

3

eFlow6NX8V

2.5A

3

eFlow6N8DV

9.78-

13.2

20.0-

26.4

10.03-

13.2

20.19-

26.4

6

2.1A 5A/250V 10A/32V 910

PD8CB

8

2A

3

eFlow6NX8DV

2A

3

eFlow6N16V

10.0-

13.2

20.19-

26.4

10.03-

13.2

20.19-

26.4

6

2.1A 5A/250V 10A/32V 910

PD16W

16

2.5A

3

eFlow6NX16V

2 - PD8

2.5A

3

eFlow6N16DV

9.78-

13.2

20.0-

26.4

10.03-

13.2

20.19-

26.4

6

2.1A 5A/250V 10A/32V 910

PD16WCB

16

2A

3

eFlow6NX16DV

2 - PD8CB

2A

3

 

European Conformity

Stand-by Specifications:

Battery

Burg. Applications

4 hr. Stand-by/

15 min. Alarm

Fire Applications

24 hr. Stand-by/

5 min. Alarm

Access Control

Applications

Stand-by

7AH

0.4 amp/6 amp

N/A

10 Mins./6 amp

12AH

1 amp/6 amp

0.3 amp/6 amp

25 Mins./6 amp

40AH (for eFlow6NXV refer to Fig. 8, pg. 10)

6 amp/6 amp

1.2 amp/6 amp

Over 4 Hours/6 amp

65AH (for eFlow6NXV refer to Fig. 8, pg. 10)

6 amp/6 amp

1.5 amp/6 amp

Over 4 Hours/6 amp

Specifications:

Input:

• 220VAC (working range 198VAC - 256VAC), 50/60Hz. 

Output:

•  For output voltage and supply current refer to eFlow6NV  
  Series Power Supply Configuration Reference Chart, pg. 2
.

•  Auxiliary output rated @ 1 amp (unswitched).

•  Overvoltage protection.

Battery Backup:

•  Built-in charger for sealed lead acid or gel type batteries.

•  Maximum charge current 1.54 amp.

•  Automatic switch over to stand-by battery when AC fails.

  Transfer to stand-by battery power is instantaneous with
  no interruption.

Fire Alarm Disconnect:

•  Supervised Fire Alarm disconnect (latching or

  non-latching) 10K EOL resistor. Operates on a normally
  open (NO) or normally closed (NC) trigger.

Supervision:

•  AC fail supervision (form “C” contacts).

•  Battery fail and presence supervision (form “C” contacts).

Supervision 

(cont’d)

:

•  Low power shutdown. Shuts down DC output terminals

  if battery voltage drops below 71-73% for 12V units

  and 70-75% for 24V units (depending on the power

  supply). Prevents deep battery discharge.

Fuse Ratings:

•  Refer to eFlow6NV Series Power Supply Configuration 
  Reference Chart, pg. 2.

Visual Indicators:

•  Green AC Power LED indicates 220VAC present.

•  AC input and DC output LED indicators.

Additional Features:

•  Short circuit and overload protection.

•  Unit is complete with power supply, enclosure,

  battery leads and cam lock. 

Enclosure Dimensions 

(approximate H x W x D)

:

eFlow6NV, eFlow6N8V, eFlow6N8DV, 

eFlow6N16V, eFlow6N16DV:

13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.55mm)

eFlow6NXV, eFlow6NX8V, eFlow6NX8DV, 

eFlow6NX16V, eFlow6NX16DV:

15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)

Содержание eFlow4N8DV

Страница 1: ...uts Eight 8 PTC Outputs eFlow6N16V eFlow6NX16V eFlow6N16DV eFlow6NX16DV 6 amp 12VDC or 24VDC 6 amp 12VDC or 24VDC Sixteen 16 Fused Outputs Sixteen 16 PTC Outputs Rev 6NVRP052213 More than just power I...

Страница 2: ...mp 12AH 1 amp 6 amp 0 3 amp 6 amp 25 Mins 6 amp 40AH for eFlow6NXV refer to Fig 8 pg 10 6 amp 6 amp 1 2 amp 6 amp Over 4 Hours 6 amp 65AH for eFlow6NXV refer to Fig 8 pg 10 6 amp 6 amp 1 5 amp 6 amp O...

Страница 3: ...tions batteries are optional When batteries are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired they must be lead acid or gel type Connect...

Страница 4: ...output circuit power limited input Fig 1d pg 5 NO GND RESET FACP interface latching or non latching power limited Fig 1e pg 5 AUX Auxiliary power limited output rated 1 amp unswitched power limited ou...

Страница 5: ...ows the circuitry needed for local annunciation Fig 2 Battery trouble indication For Canadian use a red indicating lamp must be visible from the exterior of this enclosure Wire one leg of a power sour...

Страница 6: ...utputs 1N 8N Common Outputs N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 D1 INPUT R1 LED From Power Supply Board Factory Installed DC Output to devices 1P 8P Power Outputs 1N 8N Common...

Страница 7: ...eries that can fit in this enclosure An external battery enclosure must be used if using 12AH 40AH or 65AH batteries Green Lead ground 220VAC power mains Battery and AC Supervision Circuit Battery Con...

Страница 8: ...s optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to the power supply N...

Страница 9: ...C C NO BAT FAIL AC FAIL DC AC AC1 DC BAT AUX TRIGGER EOL SUPERVISED 5A 250V RESET GND NO disable enable 2 hr 1 min AC DELAY SHUTDOWN O N 220VAC power mains Green Lead ground Battery connections DC Out...

Страница 10: ...optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to the power supply No...

Страница 11: ...25 342 9mm x 330 2mm x 82 55mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm...

Страница 12: ...31 75mm 1 25 31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 38 1mm 1...

Страница 13: ...2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50 4W B 12 24 volt Photoelectr...

Страница 14: ...14 eFlow6NV Series Notes...

Страница 15: ...r any typographical errors Product specifications are subject to change without notice 140 58th Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 website www altronix com e mail info al...

Страница 16: ...1 5 amp 6 amp Over 4 Hours 6 amp Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54 amp Automatic switch over to stand by battery when AC fails Tran...

Отзывы: