background image

 

- 2 - 

eFlow104NB

6.  Connect appropriate signaling notification devices to AC FAIL and BAT FAIL (Fig. 1b, pg. 3) supervisory

 

relay outputs.

7.  To delay AC reporting for 2 hrs. set SW2 to appropriate dip switch position [AC Delay] (Fig. 1c, pg. 3).

8.  To enable or disable Fire Alarm Disconnect set SW2 to appropriate dip switch position [Shutdown] (Fig. 1c, pg. 3).

9.  A short or NO or NC input triggers FACP [Trigger EOL Shutdown] (Fig. 1d, pg. 3).

10.  Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching

 

[Trigger EOL Shutdown] (Fig. 1e, pg. 3).

Wiring:

Use 18 AWG or larger for all low voltage power connections.

Note: Take care to keep power-limited circuits separate from non power-limited wiring (220VAC, Battery)

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level.

Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage (24VDC @ 

26.4) both at battery terminal and at the board terminals marked [--  BAT + ] to ensure that there is no break in the battery 

connection wires.

Note: Maximum charging current under discharges is 1.54A.

Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.

LED Diagnostics:

Green (DC)

Green (AC/AC1)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by batteries supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

Terminal

Legend

Function/Description

L, G, N

Connect 220VAC 50/60Hz to these terminals: L to hot, N to neutral, G to ground (non power-limited)
(Fig. 1a, pg. 3).

--  DC +

24VDC @ 10A continuous output (Fig. 1h, pg. 3).

Trigger EOL

Supervised

Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open,

normally closed from an FACP output circuit (Power-Limited input) (Fig. 1d, pg. 3).

NO, GND

RESET

FACP interface latching or non-latching (Power-Limited) (Fig. 1c, pg. 3).

+ AUX -- 

Auxiliary Power-Limited output rated @ 1A (unswitched) (Power-Limited output) (Fig. 1f, pg. 3).

AC Fail 

NC, C, NO

Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized

when AC power is present. Contact rating 1A @ 30VDC (Power-Limited) (Fig. 1b, pg. 3).

Bat Fail

NC, C, NO

Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power

is present. Contact rating 1A @ 30VDC. A removed battery is reported within 5 minutes.

Battery reconnection is reported within 1 minute (Power-Limited) (Fig. 1b, pg. 3).

--  BAT +

Stand-by battery connections. Maximum charge current 1.54A (non power-limited) (Fig. 1g, pg. 3).