eFlowNA8 Series Installation Guide

Overview:

Altronix eFlowNA8 Series distribute and switch power to access control systems and accessories. They convert a 

120VAC 60Hz input into eight (8) independently controlled 12VDC or 24VDC fuse protected outputs. These power 

outputs can be converted to dry form “C” contacts. Outputs are activated by an open collector sink or normally 

open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. Units 

will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic 

Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables 

Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect 

feature is individually selectable for any or all of the eight (8) outputs.

eFlowNA8 Series Configuration Reference Chart:

Altronix

Model 

Number

120VAC 60 Hz Input (current)

Power Supply Board Input Fuse Rating

Power Supply Board  Battery Fuse Rating

Nominal DC Output 

Voltage Options

Maximum Supply Current for Main and Aux. Outputs (A)

Fuse Protected Outputs Current per ACM8 output (A)

ACM8 Board Input Fuse Rating

ACM8 Board Output Fuse Rating

[DC]

[AUX]

12VDC Output Range (V)

24VDC Output Range (V)

12VDC Output Range (V)

24VDC Output Range (V) 12VDC 24VDC

eFlow4NA8

3.5A

5A/

250V

7.5A/

32V

10.1-

13.2

20.28-

26.4

10.05-

13.2

20.2-

26.4

3.3A

3.6A

8

2.5A 10A/

250V

3.5A/

250V

eFlow6NA8

3.5A

5A/

250V

10A/

32V

10.0-

13.2

20.19-

26.4

10.03-

13.2

20.19-

26.4

5.3A

5.6A

8

2.5A 10A/

250V

3.5A/

250V

eFlow102NA8

3.5A

5A/

250V

15A/

32V

10.03-

13.2

10.03-

13.2

9.3A

8

2.5A 10A/

250V

3.5A/

250V

eFlow104NA8

4.5A 6.3A/

250V

15A/

32V

20.17-

26.4

20.17-

26.4

9.6A

8

2.5A 10A/

250V

3.5A/

250V

*eFlow4NA8 only: 

This unit is classified as Power-Limited stand alone power supply with stand-by battery and it 

is suitable to power: sensors, electro-mechanical devices (e.g. electric door strikes).

*eFlow6NA8, eFlow102NA8, and eFlow104NA8: 

The DC output for these power supplies are not power-limited. 

If a power-limited output is required in the end-product application, the DC output from the power supply must be 

connected to a separately Listed control unit or accessory board that provides power-limited outputs. The product(s) 

providing the power-limited output(s) must be listed as appropriate for the particular end-product application (access 

control), and wired in accordance with the products installation instructions. Class 1 wiring methods, separation of 

circuits, and proper fire-rated enclosures all must be considered when connecting the DC output of the power supply 

to the end-product devices. The auxiliary outputs of these units are power-limited.

UL Listings for US Installations:

UL 294*

 - UL Listed for Access Control System Units.

*Access Control Performance Levels: 

Destructive Attack - I, Endurance Test - IV, Line Security - I, Stand-by Power - II, III, IV

UL Listings for Canadian Installations:

ULC-S319-05

 - Electronic Access Control Systems. Class I Equipment.

CSA C22.2 No.205

 - Signal Equipment.

California State Fire Marshal

European Conformity

Altronix Corp.

140 58th St. Brooklyn, NY

Содержание eFlow102NA8

Страница 1: ...A8 4A 12VDC or 24VDC Eight 8 Fused Outputs eFlow6NA8 6A 12VDC or 24VDC Eight 8 Fused Outputs eFlow102NA8 10A 12VDC Eight 8 Fused Outputs eFlow104NA8 10A 24VDC Eight 8 Fused Outputs eFlowNA8 Series Access Power Controllers with Power Supply Chargers Models Include Rev eACM050919 More than just power TM Installing Company ________________ Service Rep Name ___________________________________ Address ...

Страница 2: ... eFlow6NA8 3 5A 5A 250V 10A 32V 10 0 13 2 20 19 26 4 10 03 13 2 20 19 26 4 5 3A 5 6A 8 2 5A 10A 250V 3 5A 250V eFlow102NA8 3 5A 5A 250V 15A 32V 10 03 13 2 10 03 13 2 9 3A 8 2 5A 10A 250V 3 5A 250V eFlow104NA8 4 5A 6 3A 250V 15A 32V 20 17 26 4 20 17 26 4 9 6A 8 2 5A 10A 250V 3 5A 250V eFlow4NA8 only This unit is classified as Power Limited stand alone power supply with stand by battery and it is su...

Страница 3: ...For output voltage and supply current refer to eFlowNA8 Series Configuration Chart pg 2 Auxiliary Power Limited output rated 1A unswitched Overvoltage protection Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54A Automatic switch over to stand by battery when AC fails Transfer to stand by battery power is instantaneous with no interruption Supervised Fire Alar...

Страница 4: ...r servicing equipment There are no user serviceable parts inside Refer installation and servicing to qualified service personnel 3 Select desired DC output voltage by setting SW1 to the appropriate position on the power supply board eFlow4NA8 and eFlow6NA8 Fig 1 pg 8 eFlow102NA8 power supply is factory set at 12VDC eFlow104NA8 power supply is factory set at 24VDC 4 Measure the output voltage of th...

Страница 5: ... 24VDC operation battery leads included Use batteries Casil CL1270 12V 7AH CL12120 12V 12AH CL12400 12V 40AH CL12650 12V 65AH batteries or UL recognized BAZR2 and BAZR8 batteries of an appropriate rating 11 Battery and AC Supervision outputs Fig 3 pg 9 It is required to connect supervisory trouble reporting devices to outputs marked AC Fail BAT Fail supervisory relay outputs marked NC C NO to appr...

Страница 6: ... 8 pg 10 or Normally Closed Fig 10 pg 10 latching operation it is necessary to reset the Fire Alarm Disconnect by activating the Normally Closed reset switch Output Voltage Test Under normal load conditions the DC output voltage should be checked for proper voltage level refer to eFlowNA8 series Configuration Chart pg 2 Battery Test Under normal load conditions check that the battery is fully char...

Страница 7: ...ntroller Terminal Legend Function Description Power 12VDC or 24VDC from power supply charger factory connected These terminals are paralleled to the Control terminals Control These terminals are paralleled to the Power terminals They can be connected to an external Listed power limited access control power supply to provide isolated operating power for the devices Not evaluated by UL Jumpers J1 an...

Страница 8: ... req d AC or DC Power Supply optional NC C NO COM OUTPUT 1 LED1 F1 NC C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 TRG FACP NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6 NO C NC INP T RET NC C NO COM OUTPUT 7 NC C NO COM OUTPUT 8 Power Control F2 F3 F6 F7 F8 F4 F5 J1 J3 TRG...

Страница 9: ...r all other models Battery and AC Supervision Circuit power limited power limited Input power limited Observe polarity Battery Connections non power limited Green Flying Lead Unswitched 120VAC power mains non power limited Optional Rechargeable Stand by Battery for UL294 Applications Note 12V batteries required for ULC S319 installations Optional Rechargeable Stand by Battery for UL294 Application...

Страница 10: ... wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods For Canadian installations use shielded wiring for all connections Note Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire Fig 4a Fig 4 Fig ...

Страница 11: ...in alarm condition Fig 5 Optional hook up using two 2 isolated power supply inputs Only applicable on eFlow4NA8 not evaluated by UL J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER INPUT 12 OR 24 VAC OR VDC ACM8 POWER CUT JUMPER FROM FACP OUTPUT CIRCUIT FACP OUTPUT EOL TRG FACP NO C NC FACP INTERFACE N O TRIGGER INPUT TRG FACP NO C NC FACP INTERFACE ...

Страница 12: ... TRG FACP Fig 9 Normally Closed Non Latching FACP trigger input Fig 10 Normally Closed Latching FACP trigger input with reset This output has not been evaluated by UL Fig 8 Normally Open FACP Latching trigger input with reset This output has not been evaluated by UL N C RESET SWITCH N O TRIGGER INPUT JUMPER TRG NO C NC FACP Hook Up Diagrams ...

Страница 13: ...eFlowNA8 Series Installation Guide 13 Notes ...

Страница 14: ... 14 eFlowNA8 Series Installation Guide Notes ...

Страница 15: ... 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Enclosure Dimensions BC400 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm Altronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info al...

Страница 16: ...remote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output state change and unit temperature Access control and user managment Restrict read write Restrict users to specific resources Two 2 integral network controlled Form C Relays Three 3 programmable inpu...

Отзывы: